OSHA SearchOSHA records by employer

A. Schulman Custom Compounding NE, Inc.: OSHA inspections and violations

Worcester, Massachusetts · Plastics Material and Resin Manufacturing · NAICS 325211

2inspections
9citation items
$15,000current penalties
Jan 7, 2016last inspection

OSHA has inspected A. Schulman Custom Compounding NE, Inc. 2 times in Massachusetts since 2015.

The latest one began on Jan 7, 2016 on a referral, in Worcester.

Those inspections ended with 9 citation items: 8 serious and 1 other-than-serious.

Penalties were first proposed at $30,000 and now stand at $15,000, 50% lower after settlements or reviews.

Working near live electrical parts comes up most often in these citations: 3 items under 1910.333.

How that compares: the median penalty per cited inspection for manufacturing employers since 2015 is $4,500, and A. Schulman Custom Compounding NE, Inc. averages $7,500 (2 cited inspections).

It reported 2 severe injuries to OSHA since 2015.

A. Schulman Custom Compounding NE, Inc.: OSHA citation items per year, 2015 to 2016
Citation items per year, by inspection date.

Massachusetts · latest 90 days of OSHA records

260employers cited

Get notified the morning OSHA posts each new citation in Massachusetts: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Massachusetts

Checking a subcontractor, a client or your own company? Watch A. Schulman Custom Compounding NE, Inc. and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 341163574 OPENED JAN 7, 2016Closed

Referral · Partial · Safety · 110 employees at the site · Closed Mar 10, 2016

53 Millbrook Street, Worcester, MA 01606 · Plastics Material and Resin Manufacturing · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.23(c)(1) · Guarding floor and wall openings and holes
Serious$4,000$2,000Feb 3, 2016Final
Citation 1, item 2
29 CFR 1910.212(a)(3)(ii) · Machine guarding
Serious$7,000$3,500Feb 3, 2016Final
Citation 2, item 1
29 CFR 1910.305(g)(2)(iii) · Electrical wiring methods
Other-than-serious$0$0Feb 3, 2016Final

Inspection 340856970 OPENED AUG 18, 2015Closed

Referral · Partial · Safety · 130 employees at the site · Closed Apr 8, 2016

53 Millbrook Street., Worcester, MA 01606 · Plastics Material and Resin Manufacturing · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1a
29 CFR 1910.147(c)(4)(i) · Lockout/tagout
Serious$7,000$5,500Sep 16, 2015Final
Citation 1, item 1b
29 CFR 1910.333(a) · Working near live electrical parts
Serious$0$0Sep 16, 2015Final
Citation 1, item 1c
29 CFR 1910.333(b)(2)(ii)(c) · Working near live electrical parts
Serious$0$0Sep 16, 2015Final
Citation 1, item 2a
29 CFR 1910.303(b)(6) · Electrical equipment, general requirements
Serious$5,000$4,000Sep 16, 2015Final
Citation 1, item 2b
29 CFR 1910.305(g)(1)(iv)(a) · Electrical wiring methods
Serious$0$0Sep 16, 2015Final
Citation 1, item 2d
29 CFR 1910.333(b)(2)(iv)(b) · Working near live electrical parts
Serious$7,000$0Sep 16, 2015Final

Severe injury reports

Employers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 2 reports on file.

Dec 30, 2015, Worcester: Amputation · amputations · finger(s), fingernail(s), n.e.c.

On or about December 30, 2015, the employee was working on the plastic extruder on the production floor. The employee's right index finger was amputated after being caught in the machine while flushing the extruder. The guard was not in place at the time.

Aug 12, 2015, Worcester: Hospitalization · electrocutions, electric shocks · body systems

An employee received an electric shock while working on an air scrubber also known as a "smog hog." The employee was hospitalized for a night and received medical treatment.

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.147 · Lockout/tagout

29 CFR 1910.147(c)(4)(i)

(4) Energy control procedure. (i) Procedures shall be developed, documented and utilized for the control of potentially hazardous energy when employees are engaged in the activities covered by this section.

29 CFR 1910.212 · Machine guarding

29 CFR 1910.212(a)(3)(ii)

(ii) The point of operation of machines whose operation exposes an employee to injury, shall be guarded. The guarding device shall be in conformity with any appropriate standards therefor, or, in the absence of applicable specific standards, shall be so designed and constructed as to prevent the operator from having any part of his body in the danger zone during the operating cycle.

29 CFR 1910.23 · Guarding floor and wall openings and holes

29 CFR 1910.303 · Electrical equipment, general requirements

29 CFR 1910.303(b)(6)

(6) Deteriorating agents. Unless identified for use in the operating environment, no conductors or equipment shall be located in damp or wet locations; where exposed to gases, fumes, vapors, liquids, or other agents that have a deteriorating effect on the conductors or equipment; or where exposed to excessive temperatures.

29 CFR 1910.305 · Electrical wiring methods

29 CFR 1910.333 · Working near live electrical parts

Other plastics material and resin manufacturing employers in Massachusetts

Alert subscribers get notified of each newly cited employer in Massachusetts the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.