OSHA SearchOSHA records by employer

Ameren Illinois Company: OSHA inspections and violations

Peoria, Illinois · Electric Power Distribution · NAICS 221122

10inspections
3citation items
$39,240current penalties
Aug 15, 2025last inspection

Ameren Illinois Company has 10 OSHA inspections on record in Illinois, the first in 2014.

OSHA's last visit started on Aug 15, 2025 as part of a related case, in Pekin.

Across those inspections OSHA issued 3 citation items: 2 serious and 1 other-than-serious.

OSHA proposed $39,240 in penalties and the amount has not been reduced.

Most often, OSHA cited 1910.269, electric power generation, transmission, and distribution (3 items).

For context, across all utility employers the median penalty per cited inspection since 2015 is $0. Ameren Illinois Company averages $19,620 over 2 cited inspections in that time.

1 inspection on this page followed a fatal incident.

Ameren Illinois Company also files yearly injury logs with OSHA, summarized below.

It reported 6 severe injuries to OSHA since 2015.

Ameren Illinois Company: OSHA citation items per year, 2014 to 2025
Citation items per year, by inspection date.

Illinois · latest 90 days of OSHA records

414employers cited

Get notified the morning OSHA posts each new citation in Illinois: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Illinois

Checking a subcontractor, a client or your own company? Watch Ameren Illinois Company and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 348440405 OPENED AUG 15, 2025Closed

Unprogrammed related · Partial · Safety · 1 employee at the site · Closed Jan 26, 2026

3420 Court St., Pekin, IL 61554 · Electric Power Distribution · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

Inspection 347017063 OPENED OCT 4, 2023Closed

Referral · Partial · Safety · 5 employees at the site · Closed Jan 29, 2024

4580 East Lost Bridge Road, Decatur, IL 62521 · Electric Bulk Power Transmission and Control · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

Inspection 345439848 OPENED JUL 26, 2021Closed

Referral · Partial · Safety · 250 employees at the site · Closed Jun 13, 2023

1103 South Maple Street, Cambria, IL 62915 · Electric Bulk Power Transmission and Control · OSHA's record · Phone and website on Google Maps

Incident on Jul 23, 2021: Employee is electrically shocked while removing lines from r

At 11:00 p.m. on July 23, 2021, Employee #1, working as part of a two-person crew, was attempting to remove a bolt securing the middle phase line on a 12 kV McGraw Edison Automatic Recloser Type "W" (serial Number 6005) inside the fenced electrical substation, approximately 50 feet by 50 feet. While applying an electrical drill, Employee #1 received an electrical shock from the energized recloser. The work occurred on a warm, dry night, and the employee was being trained under the supervision of a more experienced crew member. No coordination or briefing was conducted between Employee #1's crew and another three-person crew working nearby on 34 kV overhead lines to confirm hazard isolation procedures. Employee #1 sustained burns from the electrical shock and was transported to a hospital for admission and treatment.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 2
29 CFR 1910.269(u)(6)(i) · Electric power generation, transmission, and distribution
Other-than-serious$13,653$13,653Nov 17, 2021Final
Citation 1, item 3
29 CFR 1910.269(m)(3)(i) · Electric power generation, transmission, and distribution
Serious$13,653$13,653Nov 17, 2021Final

Inspection 344194220 OPENED JUL 31, 2019Closed

Referral · Partial · Safety · 200 employees at the site · Closed Dec 21, 2020

8420 N. University Street, Peoria, IL 61615 · Electric Power Distribution · OSHA's record · Phone and website on Google Maps

Incident on Jul 29, 2019: Employee incurs shock and burns from energized bushing

At 12:45 p.m. on July 29, 2019, an employee was preparing to remove an electrical lead from a bushing on a portable substation. The employer had added a maintenance breaker which allowed maintenance personnel to supply power to a motor that moved a tap changer. The maintenance breaker allowed an extension cord, used to maintain batteries and supply power to a heater, to back-feed electricity through the transformers and up to the bushing that the employee was touching. The maintenance breaker was not operated in a manner to control the energy to the equipment. The employee incurred an electrical shock and burns to his back and hands which required hospitalization.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1a
29 CFR 1910.269(m)(3)(ii) · Electric power generation, transmission, and distribution
Serious$11,934$11,934Dec 9, 2019Final

Inspection 344128327 OPENED JUL 2, 2019Closed

Monitoring · Partial · Safety · 5 employees at the site · Closed Sep 5, 2019

300 Liberty St, Peoria, IL 61602 · Electric Power Distribution · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

Inspection 343829495 OPENED MAR 7, 2019Closed

Monitoring · Partial · Safety · 13 employees at the site · Closed Apr 4, 2019

3007 Hillcrest Drive, Eldorado, IL 62930 · Electric Power Generation · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

Inspection 341921062 OPENED NOV 17, 2016Closed

Fatality or catastrophe · No inspection · Health · 10 employees at the site · Closed Apr 18, 2017

50 N 1st Ave, Canton, IL 61520 · Natural Gas Distribution · OSHA's record · Phone and website on Google Maps

Incident on Nov 17, 2016 (fatal): Employee is killed during gas explosion

At 5:45 p.m. on November 17, 2016, an employee was isolating a 1 inch gas line leak and a build-up of gas had accumulated in the basement of a building. The gas ignited and the building exploded. The employee received blunt force trauma to the head and chest from building material remnants.

No citations from this inspection.

Inspection 341535920 OPENED JUN 9, 2016Closed

Referral · Partial · Safety · 4 employees at the site · Closed Sep 9, 2016

419 N West Street, Carlinville, IL 62626 · Natural Gas Distribution · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

2 older inspections

Inspection 341055010 OPENED NOV 13, 2015Closed

Referral · Partial · Safety · 56 employees at the site · Closed Feb 16, 2016

306 Hind Lake, Collinsville, IL 62234 · Electric Power Distribution · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

Inspection 340009562 OPENED OCT 15, 2014Closed

Complaint · Partial · Safety · 100 employees at the site · Closed Oct 15, 2014

Evergreen Square, Peoria, IL 61614 · Electric Power Distribution · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

Injury and illness logs

From the Form 300A summaries employers file with OSHA each year. Rate = recordable cases per 100 full-time workers.

In 2025, the Decatur site logged 0 recordable injuries or illnesses among about 178 workers: 0.0 per 100 full-time workers, against a median of 1.0 for its industry.

Site and yearWorkersCasesDays-away casesRateIndustry median
AMEREN ILLINOIS - IL Sub Maint & Ops
Decatur · 2025
178 000.01.0
Ameren Illinois - DDC
Collinsville · 2025
103 101.00.0
AMEREN ILLINOIS - IL Admin Mgmt & Clerical
Peoria · 2025
84 000.00.0
AMEREN ILLINOIS - Gas Tech - Operations
Decatur · 2025
69 000.01.2
AMEREN ILLINOIS - IL Fleet Svcs
Collinsville · 2025
61 101.63.1
AMEREN SERVICES - Credit and Collections
Collinsville · 2025
61 000.00.0
AMEREN ILLINOIS - IL Relay & Ops
Decatur · 2025
60 000.01.0
AMEREN SERVICES - Customer Accounts
Collinsville · 2025
59 000.00.0

Included with any plan: 176 more yearly logs from these sites, back to 2016, with each site's average rate over its latest three years. Already a subscriber? Sign in.

See plans

Severe injury reports

Employers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 6 reports on file.

Sep 27, 2023, Decatur: Hospitalization · fractures · pelvis

An employee was performing work on a utility pole when the pole broke, causing the employee to fall to the ground along with the pole. The employee sustained a fractured pelvis and a knee injury.

Jul 23, 2021, Cambria: Hospitalization · electrical burns, unspecified · upper and lower limb(s)

A substation employee was removing bolts from a recloser bushing. The employee's hand made contact with an energized wire, causing electrical burns to the employee's hand and leg.

Jul 29, 2019, Peoria: Hospitalization · electrical burns, unspecified · nonclassifiable

An employee was working on a portable sub-station with a battery and transformer when the employee suffered an electrical shock, burns, and a fall that required hospitalization.

May 18, 2018, Peoria: Hospitalization · fractures · arm(s), unspecified

An employee was climbing out of an open air electrical vault. As the employee reached to gain access out of the vault, the manhole grate door became dislodged and fell onto the employee's right arm, fracturing it.

Aug 15, 2017, Peoria: Hospitalization · fractures · lower leg(s)

On August 15, 2017, at approximately 1:30 p.m., an employee tripped over a computer mouse cord and fell, fracturing her left tibia. She was hospitalized.

Jul 25, 2017, Decatur: Hospitalization · fractures · hip(s)

On July 25, 2017, an employee was walking around and inspecting a portable sub station when the employee fell and fractured the right hip, requiring hospitalization.

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.269 · Electric power generation, transmission, and distribution

29 CFR 1910.269(m)(3)(i)

(3) Deenergizing lines and equipment. (i) The employee that the employer designates pursuant to paragraph (m)(2) of this section as being in charge of the clearance shall make a request of the system operator to deenergize the particular section of line or equipment. The designated employee becomes the employee in charge (as this term is used in paragraph (m)(3) of this section) and is responsible for the clearance.

29 CFR 1910.269(m)(3)(ii)

(ii) The employer shall ensure that all switches, disconnectors, jumpers, taps, and other means through which known sources of electric energy may be supplied to the particular lines and equipment to be deenergized are open. The employer shall render such means inoperable, unless its design does not so permit, and then ensure that such means are tagged to indicate that employees are at work.

29 CFR 1910.269(u)(6)(i)

(6) Substation entry. (i) Upon entering an attended substation, each employee, other than employees regularly working in the station, shall report his or her presence to the employee in charge of substation activities to receive information on special system conditions affecting employee safety.

Other electric power distribution employers in Illinois

Alert subscribers get notified of each newly cited employer in Illinois the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.