Inspection 348440405 OPENED AUG 15, 2025Closed
3420 Court St., Pekin, IL 61554 · Electric Power Distribution · OSHA's record · Phone and website on Google Maps
No citations from this inspection.
Ameren Illinois Company has 10 OSHA inspections on record in Illinois, the first in 2014.
OSHA's last visit started on Aug 15, 2025 as part of a related case, in Pekin.
Across those inspections OSHA issued 3 citation items: 2 serious and 1 other-than-serious.
OSHA proposed $39,240 in penalties and the amount has not been reduced.
Most often, OSHA cited 1910.269, electric power generation, transmission, and distribution (3 items).
For context, across all utility employers the median penalty per cited inspection since 2015 is $0. Ameren Illinois Company averages $19,620 over 2 cited inspections in that time.
1 inspection on this page followed a fatal incident.
Ameren Illinois Company also files yearly injury logs with OSHA, summarized below.
It reported 6 severe injuries to OSHA since 2015.
Illinois · latest 90 days of OSHA records
414employers cited
Get notified the morning OSHA posts each new citation in Illinois: the employer, the site address, the rules broken and the penalty.
See who gets cited nextLatest cited in Illinois
Checking a subcontractor, a client or your own company? Watch Ameren Illinois Company and get notified the morning OSHA posts a new citation for it.
Watch this company3420 Court St., Pekin, IL 61554 · Electric Power Distribution · OSHA's record · Phone and website on Google Maps
No citations from this inspection.
4580 East Lost Bridge Road, Decatur, IL 62521 · Electric Bulk Power Transmission and Control · OSHA's record · Phone and website on Google Maps
No citations from this inspection.
1103 South Maple Street, Cambria, IL 62915 · Electric Bulk Power Transmission and Control · OSHA's record · Phone and website on Google Maps
Incident on Jul 23, 2021: Employee is electrically shocked while removing lines from r
At 11:00 p.m. on July 23, 2021, Employee #1, working as part of a two-person crew, was attempting to remove a bolt securing the middle phase line on a 12 kV McGraw Edison Automatic Recloser Type "W" (serial Number 6005) inside the fenced electrical substation, approximately 50 feet by 50 feet. While applying an electrical drill, Employee #1 received an electrical shock from the energized recloser. The work occurred on a warm, dry night, and the employee was being trained under the supervision of a more experienced crew member. No coordination or briefing was conducted between Employee #1's crew and another three-person crew working nearby on 34 kV overhead lines to confirm hazard isolation procedures. Employee #1 sustained burns from the electrical shock and was transported to a hospital for admission and treatment.
| Citation and rule | Type | Proposed | Current | Issued | Status |
|---|---|---|---|---|---|
| Citation 1, item 2 29 CFR 1910.269(u)(6)(i) · Electric power generation, transmission, and distribution |
Other-than-serious | $13,653 | $13,653 | Nov 17, 2021 | Final |
| Citation 1, item 3 29 CFR 1910.269(m)(3)(i) · Electric power generation, transmission, and distribution |
Serious | $13,653 | $13,653 | Nov 17, 2021 | Final |
8420 N. University Street, Peoria, IL 61615 · Electric Power Distribution · OSHA's record · Phone and website on Google Maps
Incident on Jul 29, 2019: Employee incurs shock and burns from energized bushing
At 12:45 p.m. on July 29, 2019, an employee was preparing to remove an electrical lead from a bushing on a portable substation. The employer had added a maintenance breaker which allowed maintenance personnel to supply power to a motor that moved a tap changer. The maintenance breaker allowed an extension cord, used to maintain batteries and supply power to a heater, to back-feed electricity through the transformers and up to the bushing that the employee was touching. The maintenance breaker was not operated in a manner to control the energy to the equipment. The employee incurred an electrical shock and burns to his back and hands which required hospitalization.
| Citation and rule | Type | Proposed | Current | Issued | Status |
|---|---|---|---|---|---|
| Citation 1, item 1a 29 CFR 1910.269(m)(3)(ii) · Electric power generation, transmission, and distribution |
Serious | $11,934 | $11,934 | Dec 9, 2019 | Final |
300 Liberty St, Peoria, IL 61602 · Electric Power Distribution · OSHA's record · Phone and website on Google Maps
No citations from this inspection.
3007 Hillcrest Drive, Eldorado, IL 62930 · Electric Power Generation · OSHA's record · Phone and website on Google Maps
No citations from this inspection.
50 N 1st Ave, Canton, IL 61520 · Natural Gas Distribution · OSHA's record · Phone and website on Google Maps
Incident on Nov 17, 2016 (fatal): Employee is killed during gas explosion
At 5:45 p.m. on November 17, 2016, an employee was isolating a 1 inch gas line leak and a build-up of gas had accumulated in the basement of a building. The gas ignited and the building exploded. The employee received blunt force trauma to the head and chest from building material remnants.
No citations from this inspection.
419 N West Street, Carlinville, IL 62626 · Natural Gas Distribution · OSHA's record · Phone and website on Google Maps
No citations from this inspection.
306 Hind Lake, Collinsville, IL 62234 · Electric Power Distribution · OSHA's record · Phone and website on Google Maps
No citations from this inspection.
Evergreen Square, Peoria, IL 61614 · Electric Power Distribution · OSHA's record · Phone and website on Google Maps
No citations from this inspection.
From the Form 300A summaries employers file with OSHA each year. Rate = recordable cases per 100 full-time workers.
In 2025, the Decatur site logged 0 recordable injuries or illnesses among about 178 workers: 0.0 per 100 full-time workers, against a median of 1.0 for its industry.
| Site and year | Workers | Cases | Days-away cases | Rate | Industry median |
|---|---|---|---|---|---|
| AMEREN ILLINOIS - IL Sub Maint & Ops Decatur · 2025 | 178 | 0 | 0 | 0.0 | 1.0 |
| Ameren Illinois - DDC Collinsville · 2025 | 103 | 1 | 0 | 1.0 | 0.0 |
| AMEREN ILLINOIS - IL Admin Mgmt & Clerical Peoria · 2025 | 84 | 0 | 0 | 0.0 | 0.0 |
| AMEREN ILLINOIS - Gas Tech - Operations Decatur · 2025 | 69 | 0 | 0 | 0.0 | 1.2 |
| AMEREN ILLINOIS - IL Fleet Svcs Collinsville · 2025 | 61 | 1 | 0 | 1.6 | 3.1 |
| AMEREN SERVICES - Credit and Collections Collinsville · 2025 | 61 | 0 | 0 | 0.0 | 0.0 |
| AMEREN ILLINOIS - IL Relay & Ops Decatur · 2025 | 60 | 0 | 0 | 0.0 | 1.0 |
| AMEREN SERVICES - Customer Accounts Collinsville · 2025 | 59 | 0 | 0 | 0.0 | 0.0 |
Included with any plan: 176 more yearly logs from these sites, back to 2016, with each site's average rate over its latest three years. Already a subscriber? Sign in.
See plansEmployers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 6 reports on file.
Sep 27, 2023, Decatur: Hospitalization · fractures · pelvis
An employee was performing work on a utility pole when the pole broke, causing the employee to fall to the ground along with the pole. The employee sustained a fractured pelvis and a knee injury.
Jul 23, 2021, Cambria: Hospitalization · electrical burns, unspecified · upper and lower limb(s)
A substation employee was removing bolts from a recloser bushing. The employee's hand made contact with an energized wire, causing electrical burns to the employee's hand and leg.
Jul 29, 2019, Peoria: Hospitalization · electrical burns, unspecified · nonclassifiable
An employee was working on a portable sub-station with a battery and transformer when the employee suffered an electrical shock, burns, and a fall that required hospitalization.
May 18, 2018, Peoria: Hospitalization · fractures · arm(s), unspecified
An employee was climbing out of an open air electrical vault. As the employee reached to gain access out of the vault, the manhole grate door became dislodged and fell onto the employee's right arm, fracturing it.
Aug 15, 2017, Peoria: Hospitalization · fractures · lower leg(s)
On August 15, 2017, at approximately 1:30 p.m., an employee tripped over a computer mouse cord and fell, fracturing her left tibia. She was hospitalized.
Jul 25, 2017, Decatur: Hospitalization · fractures · hip(s)
On July 25, 2017, an employee was walking around and inspecting a portable sub station when the employee fell and fractured the right hip, requiring hospitalization.
Current text from the Code of Federal Regulations. Some citations were issued under older wording.
29 CFR 1910.269(m)(3)(i)
(3) Deenergizing lines and equipment. (i) The employee that the employer designates pursuant to paragraph (m)(2) of this section as being in charge of the clearance shall make a request of the system operator to deenergize the particular section of line or equipment. The designated employee becomes the employee in charge (as this term is used in paragraph (m)(3) of this section) and is responsible for the clearance.
29 CFR 1910.269(m)(3)(ii)
(ii) The employer shall ensure that all switches, disconnectors, jumpers, taps, and other means through which known sources of electric energy may be supplied to the particular lines and equipment to be deenergized are open. The employer shall render such means inoperable, unless its design does not so permit, and then ensure that such means are tagged to indicate that employees are at work.
29 CFR 1910.269(u)(6)(i)
(6) Substation entry. (i) Upon entering an attended substation, each employee, other than employees regularly working in the station, shall report his or her presence to the employee in charge of substation activities to receive information on special system conditions affecting employee safety.
Alert subscribers get notified of each newly cited employer in Illinois the morning it is posted. See the alert plans.
Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.