Ampro, Inc.: OSHA inspections and violations

Kissimmee, Florida · Electrical Contractors and Other Wiring Installation Contractors · NAICS 238210

1inspections
4citation items
$32,483current penalties
Nov 19, 2021last inspection

OSHA inspectors have visited Ampro, Inc. in Florida one time.

It opened on Nov 19, 2021 on a referral, in Kissimmee.

In all, OSHA issued 4 citation items: 4 serious.

The penalties, $32,483 in total, stand where OSHA first set them.

The rule cited most here is 1910.333 (working near live electrical parts), 3 times.

Among construction employers, the typical cited inspection since 2015 ends with a $3,078 penalty. Ampro, Inc. averages $32,483 across 1 cited inspection.

It reported 1 severe injury to OSHA since 2015.

Ampro, Inc.: OSHA citation items per year, 2021 to 2021
Citation items per year, by inspection date.

Want to know if OSHA cites Ampro, Inc. again? Add it to a watchlist and we will email you the morning the citation shows up.

Watch this company

Inspection history

Inspection 345648646 OPENED NOV 19, 2021Closed

Referral · Partial · Safety · 45 employees at the site · Closed Jul 21, 2022

1347 E. Vine Street, Kissimmee, FL 34744 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.333(a)(1) · Working near live electrical parts
Serious$10,151$11,000Feb 25, 2022Final
Citation 1, item 2a
29 CFR 1910.333(b)(2)(iii)(a) · Working near live electrical parts
Serious$10,151$11,000Feb 25, 2022Final
Citation 1, item 2b
29 CFR 1910.333(b)(2)(iv)(b) · Working near live electrical parts
Serious$0$0Feb 25, 2022Final
Citation 1, item 4
29 CFR 1910.335(a)(2)(i) · Safeguards for personnel protection
Serious$10,151$10,483Feb 25, 2022Final

Severe injury reports

Employers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 1 report on file.

Nov 11, 2021, Kissimmee: Hospitalization · electrocutions, electric shocks · body systems

An employee and co-workers were replacing the existing HID parking lot fixtures with new LED fixtures. During the process of removing the existing fixtures, the lighting circuits were energized by a photocell. The employee attempted to strip wiring to make the electrical connections for the new fixtures when they were electrocuted, resulting in hospitalization.

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.333 · Working near live electrical parts

29 CFR 1910.333(a)(1)

(1) Deenergized parts. Live parts to which an employee may be exposed shall be deenergized before the employee works on or near them, unless the employer can demonstrate that deenergizing introduces additional or increased hazards or is infeasible due to equipment design or operational limitations. Live parts that operate at less than 50 volts to ground need not be deenergized if there will be no increased exposure to electrical burns or to explosion due to electric arcs.

29 CFR 1910.333(b)(2)(iii)(a)

(iii) Application of locks and tags. (A) A lock and a tag shall be placed on each disconnecting means used to deenergize circuits and equipment on which work is to be performed, except as provided in paragraphs (b)(2)(iii)(C) and (b)(2)(iii)(E) of this section. The lock shall be attached so as to prevent persons from operating the disconnecting means unless they resort to undue force or the use of tools.

29 CFR 1910.333(b)(2)(iv)(b)

(B) A qualified person shall use test equipment to test the circuit elements and electrical parts of equipment to which employees will be exposed and shall verify that the circuit elements and equipment parts are deenergized. The test shall also determine if any energized condition exists as a result of inadvertently induced voltage or unrelated voltage backfeed even though specific parts of the circuit have been deenergized and presumed to be safe. If the circuit to be tested is over 600 volts, nominal, the test equipment shall be checked for proper operation immediately before and immediately after this test.

29 CFR 1910.335 · Safeguards for personnel protection

Other electrical contractors and other wiring installation contractors employers in Florida

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.