OSHA SearchOSHA records by employer

Apex Oil Company, Inc.: OSHA inspections and violations

Wilmington, North Carolina · Petroleum Bulk Stations and Terminals · NAICS 424710

1inspections
2citation items
$1,500current penalties
May 18, 2015last inspection

Apex Oil Company, Inc. has one OSHA inspection on record in North Carolina.

OSHA opened it on May 18, 2015 on a referral, in Wilmington.

From that inspection OSHA issued 2 citation items: 2 serious.

OSHA proposed $1,500 in penalties and the amount has not been reduced.

Most often, OSHA cited 1910.106, flammable liquids (2 items).

For context, across all wholesale employers the median penalty per cited inspection since 2015 is $3,424. Apex Oil Company, Inc. averages $1,500 over 1 cited inspection in that time.

Apex Oil Company, Inc.: OSHA citation items per year, 2015 to 2015
Citation items per year, by inspection date.

North Carolina · latest 90 days of OSHA records

228employers cited

Get notified the morning OSHA posts each new citation in North Carolina: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in North Carolina

Checking a subcontractor, a client or your own company? Watch Apex Oil Company, Inc. and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 317988590 OPENED MAY 18, 2015Closed

Referral · Partial · Safety · 10 employees at the site · Closed Jun 18, 2015

3314 River Road, Wilmington, NC 28412 · Petroleum Bulk Stations and Terminals · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1a
29 CFR 1910.106(f)(3)(vi) · Flammable liquids
Serious$1,500$1,500Jun 10, 2015Closed
Citation 1, item 1b
29 CFR 1910.106(f)(4)(ix) · Flammable liquids
Serious$0$0Jun 10, 2015Closed

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.106 · Flammable liquids

29 CFR 1910.106(f)(3)(vi)

(vi) Container filling facilities. Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), shall not be dispensed into containers unless the nozzle and container are electrically interconnected. Where the metallic floorplate on which the container stands while filling is electrically connected to the fill stem or where the fill stem is bonded to the container during filling operations by means of a bond wire, the provisions of this section shall be deemed to have been complied with.

29 CFR 1910.106(f)(4)(ix)

(ix) Fire protection. Suitable portable fire extinguishers with a rating of not less than 12-BC shall be located within 75 feet of those portions of the facility where fires are likely to occur, such as hose connections, pumps, and separator tanks.

Other petroleum bulk stations and terminals employers in North Carolina

Alert subscribers get notified of each newly cited employer in North Carolina the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.