OSHA SearchOSHA records by employer

Arkansas Electric Cooperatives: OSHA inspections and violations

Stillwater, Oklahoma · Power and Communication Line and Related Structures Construction · NAICS 237130

1inspections
3citation items
$21,000current penalties
Jan 15, 2016last inspection

Arkansas Electric Cooperatives has one OSHA inspection on record in Oklahoma.

OSHA opened it on Jan 15, 2016 after a fatality or catastrophe, in Stillwater.

From that inspection OSHA issued 3 citation items: 3 serious.

OSHA proposed $21,000 in penalties and the amount has not been reduced.

Most often, OSHA cited 1926.960, working on or near exposed energized parts (3 items).

For context, across all construction employers the median penalty per cited inspection since 2015 is $3,080. Arkansas Electric Cooperatives averages $21,000 over 1 cited inspection in that time.

1 inspection on this page followed a fatal incident.

Arkansas Electric Cooperatives: OSHA citation items per year, 2016 to 2016
Citation items per year, by inspection date.

Oklahoma · latest 90 days of OSHA records

52employers cited

Get notified the morning OSHA posts each new citation in Oklahoma: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Oklahoma

Checking a subcontractor, a client or your own company? Watch Arkansas Electric Cooperatives and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 341186773 OPENED JAN 15, 2016Closed

Fatality or catastrophe · Partial · Safety · 387 employees at the site · Closed May 19, 2016

Fairgrounds Rd & E 32nd St, Stillwater, OK 74074 · Power and Communication Line and Related Structures Construction · OSHA's record · Phone and website on Google Maps

Incident on Jan 14, 2016 (fatal): Employee is killed when electrocuted

At 5:30 p.m. on January 14, 2016, an employee who was a lineman was hanging fuses and barrels onto an electrical cutout. The employee contacted a live electrical line and sustained an electrical shock that killed him.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1926.960(c)(1)(iii) · Working on or near exposed energized parts
Serious$7,000$7,000Mar 24, 2016Final
Citation 1, item 2
29 CFR 1926.960(c)(2)(ii)(b) · Working on or near exposed energized parts
Serious$7,000$7,000Mar 24, 2016Final
Citation 1, item 3
29 CFR 1926.960(h) · Working on or near exposed energized parts
Serious$7,000$7,000Mar 24, 2016Final

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1926.960 · Working on or near exposed energized parts

29 CFR 1926.960(c)(1)(iii)

(iii) The employer shall ensure that no employee approaches or takes any conductive object closer to exposed energized parts than the employer's established minimum approach distance, unless:

29 CFR 1926.960(c)(2)(ii)(b)

(B) Does not remove the rubber insulating gloves and sleeves until he or she is in a position where he or she cannot reach into the minimum approach distance, established by the employer under paragraph (c)(1) of this section.

29 CFR 1926.960(h)

(h) Fuse handling. When an employee must install or remove fuses with one or both terminals energized at more than 300 volts, or with exposed parts energized at more than 50 volts, the employer shall ensure that the employee uses tools or gloves rated for the voltage. When an employee installs or removes expulsion-type fuses with one or both terminals energized at more than 300 volts, the employer shall ensure that the employee wears eye protection meeting the requirements of subpart E of this part, uses a tool rated for the voltage, and is clear of the exhaust path of the fuse barrel.