OSHA SearchOSHA records by employer

B&B Designed Systems, Inc.: OSHA inspections and violations

Meadville, Pennsylvania · Electrical Contractors and Other Wiring Installation Contractors · NAICS 238210

1inspections
5citation items
$10,000current penalties
Oct 14, 2020last inspection

OSHA inspectors have visited B&B Designed Systems, Inc. in Pennsylvania one time.

It opened on Oct 14, 2020 on a referral, in Meadville.

In all, OSHA issued 5 citation items: 5 serious.

The proposed penalties came to $16,384; today they stand at $10,000, 39% less.

The rule cited most here is 1926.416 (electrical safety in construction), 2 times.

Among construction employers, the typical cited inspection since 2015 ends with a $3,080 penalty. B&B Designed Systems, Inc. averages $10,000 across 1 cited inspection.

It reported 1 severe injury to OSHA since 2015.

B&B Designed Systems, Inc.: OSHA citation items per year, 2020 to 2020
Citation items per year, by inspection date.

Pennsylvania · latest 90 days of OSHA records

287employers cited

4 of them in the same industry

Get notified the morning OSHA posts each new citation in Pennsylvania: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Pennsylvania

Checking a subcontractor, a client or your own company? Watch B&B Designed Systems, Inc. and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 344974076 OPENED OCT 14, 2020Closed

Referral · Partial · Safety · 3 employees at the site · Closed May 21, 2021

18746 Mill Street, Meadville, PA 16335 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Incident on Oct 9, 2020: Employee sustains burns to arms, face and neck in arc flash

At 9:26 a.m. on October 9, 2020, an employee working as an electrician for an electrical contractor was working on panel CXPN-99 in a manufacturing plant. This was the last day of the project. The employee was attempting to land and terminate a ground wire onto a ground bus for a make-up air unit (MAU). The units needing ground wire installations were MAU #3 and MAU #4. The electrical panel was energized and was not locked out at panel CXPN95 prior to the start of the work operations. Panel CXPN95 supplied the power to CXPN-99. CXPN-99 was also powering MAU #9, which at time was on-line. Furthermore, arc flash protection was not being used at the time of the accident. A second ground wire touched the energized hot bus (feeder lug) within the electrical panel. The contact was struck by the arc flash. The employee was hospitalized to treat 2nd and 3rd degree burns to the inside of his left arm and left hand, 2nd degree burns to the outside of his right arm and right hand, and 1st degree burns to his face and neck.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1a
29 CFR 1926.416(a)(1) · Electrical safety in construction
Serious$9,557$5,000Mar 18, 2021Final
Citation 1, item 1b
29 CFR 1926.417(b) · Lockout and tagging of circuits
Serious$0$0Mar 18, 2021Final
Citation 1, item 1c
29 CFR 1926.95(a) · Criteria for personal protective equipment
Serious$0$0Mar 18, 2021Final
Citation 1, item 2a
29 CFR 1926.416(a)(3) · Electrical safety in construction
Serious$6,827$5,000Mar 18, 2021Final
Citation 1, item 2b
29 CFR 1926.850(c) · Preparatory operations
Serious$0$0Mar 18, 2021Final

Severe injury reports

Employers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 1 report on file.

Oct 9, 2020, Meadville: Hospitalization · electrical burns, unspecified · multiple body parts, n.e.c.

Employees were finishing one ground termination in a three-phase, 480 volt panel. The ground touched the feeder lug and the panel, which caused a short and an arc flash. One employee was hospitalized with burns to the face, hands, and forearms.

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1926.416 · Electrical safety in construction

29 CFR 1926.416(a)(1)

(a) Protection of employees. (1) No employer shall permit an employee to work in such proximity to any part of an electric power circuit that the employee could contact the electric power circuit in the course of work, unless the employee is protected against electric shock by deenergizing the circuit and grounding it or by guarding it effectively by insulation or other means.

29 CFR 1926.416(a)(3)

(3) Before work is begun the employer shall ascertain by inquiry or direct observation, or by instruments, whether any part of an energized electric power circuit, exposed or concealed, is so located that the performance of the work may bring any person, tool, or machine into physical or electrical contact with the electric power circuit. The employer shall post and maintain proper warning signs where such a circuit exists. The employer shall advise employees of the location of such lines, the hazards involved, and the protective measures to be taken.

29 CFR 1926.417 · Lockout and tagging of circuits

29 CFR 1926.417(b)

(b) Equipment and circuits. Equipment or circuits that are deenergized shall be rendered inoperative and shall have tags attached at all points where such equipment or circuits can be energized.

29 CFR 1926.850 · Preparatory operations

29 CFR 1926.95 · Criteria for personal protective equipment

Other electrical contractors and other wiring installation contractors employers in Pennsylvania

Alert subscribers get notified of each newly cited employer in Pennsylvania the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.