Inspection 344974076 OPENED OCT 14, 2020Closed
18746 Mill Street, Meadville, PA 16335 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps
Incident on Oct 9, 2020: Employee sustains burns to arms, face and neck in arc flash
At 9:26 a.m. on October 9, 2020, an employee working as an electrician for an electrical contractor was working on panel CXPN-99 in a manufacturing plant. This was the last day of the project. The employee was attempting to land and terminate a ground wire onto a ground bus for a make-up air unit (MAU). The units needing ground wire installations were MAU #3 and MAU #4. The electrical panel was energized and was not locked out at panel CXPN95 prior to the start of the work operations. Panel CXPN95 supplied the power to CXPN-99. CXPN-99 was also powering MAU #9, which at time was on-line. Furthermore, arc flash protection was not being used at the time of the accident. A second ground wire touched the energized hot bus (feeder lug) within the electrical panel. The contact was struck by the arc flash. The employee was hospitalized to treat 2nd and 3rd degree burns to the inside of his left arm and left hand, 2nd degree burns to the outside of his right arm and right hand, and 1st degree burns to his face and neck.
| Citation and rule | Type | Proposed | Current | Issued | Status |
|---|---|---|---|---|---|
| Citation 1, item 1a 29 CFR 1926.416(a)(1) · Electrical safety in construction |
Serious | $9,557 | $5,000 | Mar 18, 2021 | Final |
| Citation 1, item 1b 29 CFR 1926.417(b) · Lockout and tagging of circuits |
Serious | $0 | $0 | Mar 18, 2021 | Final |
| Citation 1, item 1c 29 CFR 1926.95(a) · Criteria for personal protective equipment |
Serious | $0 | $0 | Mar 18, 2021 | Final |
| Citation 1, item 2a 29 CFR 1926.416(a)(3) · Electrical safety in construction |
Serious | $6,827 | $5,000 | Mar 18, 2021 | Final |
| Citation 1, item 2b 29 CFR 1926.850(c) · Preparatory operations |
Serious | $0 | $0 | Mar 18, 2021 | Final |