OSHA SearchOSHA records by employer

Brooklyn Municipal Utilities: OSHA inspections and violations

Brooklyn, Iowa · Electric Bulk Power Transmission and Control · NAICS 221121

1inspections
4citation items
$29,926current penalties
Aug 11, 2020last inspection

Brooklyn Municipal Utilities has one OSHA inspection on record in Iowa.

OSHA opened it on Aug 11, 2020 after a fatality or catastrophe, in Brooklyn.

From that inspection OSHA issued 4 citation items: 4 serious.

OSHA proposed $29,926 in penalties and the amount has not been reduced.

Most often, OSHA cited 1910.269, electric power generation, transmission, and distribution (4 items).

For context, across all utility employers the median penalty per cited inspection since 2015 is $0. Brooklyn Municipal Utilities averages $29,926 over 1 cited inspection in that time.

1 inspection on this page followed a fatal incident.

Brooklyn Municipal Utilities: OSHA citation items per year, 2020 to 2020
Citation items per year, by inspection date.

Iowa · latest 90 days of OSHA records

68employers cited

Get notified the morning OSHA posts each new citation in Iowa: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Iowa

Checking a subcontractor, a client or your own company? Watch Brooklyn Municipal Utilities and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 344877337 OPENED AUG 11, 2020Closed

Fatality or catastrophe · Partial · Safety · Local government · 5 employees at the site · Closed Dec 21, 2020

801 Boundry St, Brooklyn, IA 52211 · Electric Bulk Power Transmission and Control · OSHA's record · Phone and website on Google Maps

Incident on Aug 10, 2020 (fatal): Utility worker is electrocuted while repairing 2,400-volt pr

At 6:05 p.m. on August 10, 2020, an employee was working for an electric power utility. He was working on a primary line that had been damaged in a storm. A tree had fallen on the line and broken it. The employee was splicing the ends. The line was energized at 2,400 volts. The employee was measuring the length of the cable needed. When he held an end of the damaged conductor in each hand, his body completed the circuit. He suffered an electric shock from direct contact with an overhead line. He was electrocuted.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.269(c)(1)(ii) · Electric power generation, transmission, and distribution
Serious$2,651$2,651Nov 10, 2020Final
Citation 1, item 2
29 CFR 1910.269(l)(3)(i) · Electric power generation, transmission, and distribution
Serious$2,651$2,651Nov 10, 2020Final
Citation 1, item 3
29 CFR 1910.269(l)(3)(iii)(a) · Electric power generation, transmission, and distribution
Serious$1,894$1,894Nov 10, 2020Final
Citation 2, item 1
29 CFR 1910.269(d)(2)(i) · Electric power generation, transmission, and distribution
Serious$22,730$22,730Nov 10, 2020Final

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.269 · Electric power generation, transmission, and distribution

29 CFR 1910.269(c)(1)(ii)

(ii) The employer shall ensure that the employee in charge conducts a job briefing that meets paragraphs (c)(2), (c)(3), and (c)(4) of this section with the employees involved before they start each job.

29 CFR 1910.269(d)(2)(i)

(2) General. (i) The employer shall establish a program consisting of energy control procedures, employee training, and periodic inspections to ensure that, before any employee performs any servicing or maintenance on a machine or equipment where the unexpected energizing, start up, or release of stored energy could occur and cause injury, the machine or equipment is isolated from the energy source and rendered inoperative.

29 CFR 1910.269(l)(3)(i)

(3) Minimum approach distances. (i) The employer shall establish minimum approach distances no less than the distances computed by Table R-3 for ac systems or Table R-8 for dc systems.