Buckeye Rural Electric Cooperative Inc. has one OSHA inspection on record in Ohio.
OSHA opened it on Dec 23, 2022 after a fatality or catastrophe, in Pedro.
From that inspection OSHA issued 4 citation items: 4 serious.
OSHA proposed $42,188 in penalties and the amount has not been reduced.
Most often, OSHA cited 1910.269, electric power generation, transmission, and distribution (4 items).
For context, across all utility employers the median penalty per cited inspection since 2015 is $0. Buckeye Rural Electric Cooperative Inc. averages $42,188 over 1 cited inspection in that time.
1 inspection on this page followed a fatal incident.
Inspection 346407919 OPENED DEC 23, 2022Closed
Fatality or catastrophe · Partial · Safety · 47 employees at the site · Closed Mar 27, 2025
Pole 6d4y33-8-1, Private Rd 1275, Pedro, OH 45659 · Electric Power Distribution · OSHA's record · Phone and website on Google Maps
Incident on Dec 23, 2022 (fatal): Employee is electrocuted while repairing downed power line
At 10:16 a.m. on December 23, 2022, an apprentice lineman was making repairs to a downed power line. Prior to making the line repair, the disconnect switches supplying 7,200 volts were not rendered open and tagged, the lines were not tested to verify the absence of voltage, and protective ground jumpers were not installed on the primary conductor and neutral. The employee contacted the downed power line and was electrocuted.
| Citation and rule | Type | Proposed | Current | Issued | Status |
|---|
| Citation 1, item 1 |
Serious | $10,938 | $10,938 | Apr 18, 2023 | Final |
| Citation 1, item 2 |
Serious | $15,625 | $15,625 | Apr 18, 2023 | Final |
| Citation 1, item 3a |
Serious | $15,625 | $15,625 | Apr 18, 2023 | Final |
| Citation 1, item 3b |
Serious | $0 | $0 | Apr 18, 2023 | Final |
Current text from the Code of Federal Regulations. Some citations were issued under older wording.
29 CFR 1910.269 · Electric power generation, transmission, and distribution
29 CFR 1910.269(l)(3)(iii)(a)
(A) The employee is insulated from the energized part (rubber insulating gloves or rubber insulating gloves and sleeves worn in accordance with paragraph (l)(4) of this section constitutes insulation of the employee from the energized part upon which the employee is working provided that the employee has control of the part in a manner sufficient to prevent exposure to uninsulated portions of the employee's body), or
29 CFR 1910.269(m)(3)(ii)
(ii) The employer shall ensure that all switches, disconnectors, jumpers, taps, and other means through which known sources of electric energy may be supplied to the particular lines and equipment to be deenergized are open. The employer shall render such means inoperable, unless its design does not so permit, and then ensure that such means are tagged to indicate that employees are at work.
29 CFR 1910.269(m)(3)(vii)
(vii) The employer shall ensure the installation of protective grounds as required by paragraph (n) of this section.
Alert subscribers get notified of each newly cited employer in Ohio the morning it is posted. See the alert plans.
Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.