OSHA SearchOSHA records by employer

Cochran Electric, Inc: OSHA inspections and violations

Granville, Ohio · Electrical Contractors and Other Wiring Installation Contractors · NAICS 238210

2inspections
6citation items
$12,535current penalties
Apr 19, 2018last inspection

OSHA has inspected Cochran Electric, Inc 2 times in Ohio since 2017.

The latest one began on Apr 19, 2018 on a referral, in Columbus.

Those inspections ended with 6 citation items: 1 serious and 5 other-than-serious.

Penalties were first proposed at $19,144 and now stand at $12,535, 35% lower after settlements or reviews.

Working near live electrical parts comes up most often in these citations: 4 items under 1910.333.

How that compares: the median penalty per cited inspection for construction employers since 2015 is $3,080, and Cochran Electric, Inc averages $6,268 (2 cited inspections).

It reported 1 severe injury to OSHA since 2015.

Cochran Electric, Inc: OSHA citation items per year, 2017 to 2018
Citation items per year, by inspection date.

Ohio · latest 90 days of OSHA records

267employers cited

2 of them in the same industry

Get notified the morning OSHA posts each new citation in Ohio: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Ohio

Checking a subcontractor, a client or your own company? Watch Cochran Electric, Inc and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 343099495 OPENED APR 19, 2018Closed

Referral · Partial · Safety · 16 employees at the site · Closed Mar 10, 2020

845 Kaderly Drive, Columbus, OH 43228 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Incident on Apr 14, 2018: Electrician is burned in switchboard arc flash

At 1:20 p.m. on April 14, 2018, Employee #1 and his coworker, electricians employed by an electrical services company, were opening up a primary electrical switchboard enclosure of 13,200 volts of alternating current (VAC). Employee #1 reached into the switch and made contact with two energized phases. An arc flash/blast occurred. Employee #1 was thrown against an adjacent electrical switchboard. Emergency services were called, and Employee #1 was transported to the hospital. He was admitted and treated for first and second degree burns across the chest, a third degree exit wound at the right bicep, and a laceration to the head.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1a
29 CFR 1910.335(a)(1)(i) · Safeguards for personnel protection
Other-than-serious$5,174$5,000Jul 17, 2018Final
Citation 1, item 2a
29 CFR 1910.333(a)(1) · Working near live electrical parts
Other-than-serious$5,174$5,000Jul 17, 2018Final
Citation 1, item 2b
29 CFR 1910.333(b)(2)(ii)(a) · Working near live electrical parts
Other-than-serious$0$0Jul 17, 2018Final
Citation 1, item 2c
29 CFR 1910.333(b)(2)(iii)(a) · Working near live electrical parts
Other-than-serious$0$0Jul 17, 2018Final
Citation 1, item 3
29 CFR 1910.333(b)(2)(iv)(b) · Working near live electrical parts
Other-than-serious$5,174$0Jul 17, 2018Final

Inspection 342715224 OPENED OCT 19, 2017Closed

Planned · Partial · Safety · 14 employees at the site · Closed Dec 18, 2017

Founders Lane Kendal Drive, Granville, OH 43023 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1926.453(b)(2)(v) · Aerial lifts
Serious$3,622$2,535Nov 21, 2017Final

Severe injury reports

Employers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 1 report on file.

Apr 14, 2018, Columbus: Hospitalization · electrical burns, unspecified · arm(s), unspecified

An employee was cleaning and maintaining switch gears when an arc flash occurred resulting in burns to the employee's right arm.

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.333 · Working near live electrical parts

29 CFR 1910.333(a)(1)

(1) Deenergized parts. Live parts to which an employee may be exposed shall be deenergized before the employee works on or near them, unless the employer can demonstrate that deenergizing introduces additional or increased hazards or is infeasible due to equipment design or operational limitations. Live parts that operate at less than 50 volts to ground need not be deenergized if there will be no increased exposure to electrical burns or to explosion due to electric arcs.

29 CFR 1910.333(b)(2)(ii)(a)

(ii) Deenergizing equipment. (A) Safe procedures for deenergizing circuits and equipment shall be determined before circuits or equipment are deenergized.

29 CFR 1910.333(b)(2)(iii)(a)

(iii) Application of locks and tags. (A) A lock and a tag shall be placed on each disconnecting means used to deenergize circuits and equipment on which work is to be performed, except as provided in paragraphs (b)(2)(iii)(C) and (b)(2)(iii)(E) of this section. The lock shall be attached so as to prevent persons from operating the disconnecting means unless they resort to undue force or the use of tools.

29 CFR 1910.335 · Safeguards for personnel protection

29 CFR 1926.453 · Aerial lifts

Other electrical contractors and other wiring installation contractors employers in Ohio

Alert subscribers get notified of each newly cited employer in Ohio the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.