OSHA SearchOSHA records by employer

Cold, Inc.: OSHA inspections and violations

Round Rock, Texas · Refrigeration Equipment and Supplies Merchant Wholesalers · NAICS 423740

1inspections
1citation items
$4,351current penalties
Jul 18, 2022last inspection

OSHA inspectors have visited Cold, Inc. in Texas one time.

It opened on Jul 18, 2022 after a fatality or catastrophe, in Round Rock.

In all, OSHA issued 1 citation item: 1 serious.

The penalties, $4,351 in total, stand where OSHA first set them.

Among wholesale employers, the typical cited inspection since 2015 ends with a $3,427 penalty. Cold, Inc. averages $4,351 across 1 cited inspection.

1 inspection on this page followed a fatal incident.

Cold, Inc.: OSHA citation items per year, 2022 to 2022
Citation items per year, by inspection date.

Want to know if OSHA cites Cold, Inc. again? Add it to a watchlist and we will email you the morning the citation shows up.

Watch this company

Inspection history

Inspection 346085731 OPENED JUL 18, 2022Closed

Fatality or catastrophe · Partial · Safety · 2 employees at the site · Closed Aug 20, 2024

130 Sundance Prwy Unit 300, Round Rock, TX 78681 · Refrigeration Equipment and Supplies Merchant Wholesalers · OSHA's record · Phone and website on Google Maps

Incident on Jul 18, 2022 (fatal): Employee is electrocuted and killed while replacing ice mach

At 1:45 p.m. on July 18, 2022, an employee was preparing to replace an ice machine at a retail store. The employee searched for the electrical panel to de-energize the ice machine but was unable to locate it. The employee was employed by a refrigeration equipment company and did not work at the retail store. The employee asked a supervisor at the store to help find the electrical panel but the supervisor was unable to help him. The employee decided to replace the ice machine without de-energizing it since he could not locate the electrical panel, so he attempted to disconnect the fixed wired 220 volt power cord. The employee was killed when he received an electrical shock from the power cord.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.333(a)(1) · Working near live electrical parts
Serious$4,351$4,351Jan 6, 2023Final

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.333 · Working near live electrical parts

29 CFR 1910.333(a)(1)

(1) Deenergized parts. Live parts to which an employee may be exposed shall be deenergized before the employee works on or near them, unless the employer can demonstrate that deenergizing introduces additional or increased hazards or is infeasible due to equipment design or operational limitations. Live parts that operate at less than 50 volts to ground need not be deenergized if there will be no increased exposure to electrical burns or to explosion due to electric arcs.

Other refrigeration equipment and supplies merchant wholesalers employers in Texas

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.