OSHA SearchOSHA records by employer

Current Electric Service, Inc.: OSHA inspections and violations

Bonita Springs, Florida · Electrical Contractors and Other Wiring Installation Contractors · NAICS 238210

2inspections
5citation items
$34,825current penalties
Jul 25, 2023last inspection

Since 2007, OSHA inspectors have visited Current Electric Service, Inc. in Florida 2 times.

The most recent inspection opened on Jul 25, 2023 after a fatality or catastrophe, in Fort Myers Beach.

In all, OSHA issued 5 citation items: 5 serious.

The proposed penalties came to $34,975; today they stand at $34,825, 0% less.

The rule cited most here is 1926.416 (electrical safety in construction), 2 times.

Among construction employers, the typical cited inspection since 2015 ends with a $3,080 penalty. Current Electric Service, Inc. averages $34,375 across 1 cited inspection.

1 inspection on this page followed a fatal incident.

Current Electric Service, Inc.: OSHA citation items per year, 2007 to 2023
Citation items per year, by inspection date.

Florida · latest 90 days of OSHA records

326employers cited

5 of them in the same industry

Get notified the morning OSHA posts each new citation in Florida: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Florida

Checking a subcontractor, a client or your own company? Watch Current Electric Service, Inc. and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 346863624 OPENED JUL 25, 2023Closed

Fatality or catastrophe · Complete · Safety · 12 employees at the site · Closed Mar 27, 2024

2000 Estero Blvd Diamond Head Beach Resort, Fort Myers Beach, FL 33931 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Incident on Jul 25, 2023 (fatal): Employee is killed via electrocution

At 12:45 p.m. on July 25, 2023, an employee was laying on the grass in the prone position, while using a handheld uninsulated cutting plier to remove/strip the insulation from the end of an energized electrical wire, which was located in an existing below grade electrical junction box. The employee, who was not wearing PPE/electrically insulated gloves, was electrocuted and was subsequently pronounced dead at the scene.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1926.95(a) · Criteria for personal protective equipment
Serious$15,625$15,625Jan 11, 2024Final
Citation 1, item 2
29 CFR 1926.416(a)(1) · Electrical safety in construction
Serious$6,250$6,250Jan 11, 2024Final
Citation 1, item 3
29 CFR 1926.416(a)(3) · Electrical safety in construction
Serious$6,250$6,250Jan 11, 2024Final
Citation 1, item 4
29 CFR 1926.417(a) · Lockout and tagging of circuits
Serious$6,250$6,250Jan 11, 2024Final

Inspection 311551360 OPENED OCT 30, 2007Closed

Planned · Partial · Safety · 20 employees at the site · Closed Nov 23, 2007

Dealership-s. Tamiami Trail, Bonita Springs, FL 33928 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1926.453(b)(2)(v) · Aerial lifts
Serious$600$450Nov 8, 2007Closed

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1926.416 · Electrical safety in construction

29 CFR 1926.416(a)(1)

(a) Protection of employees. (1) No employer shall permit an employee to work in such proximity to any part of an electric power circuit that the employee could contact the electric power circuit in the course of work, unless the employee is protected against electric shock by deenergizing the circuit and grounding it or by guarding it effectively by insulation or other means.

29 CFR 1926.416(a)(3)

(3) Before work is begun the employer shall ascertain by inquiry or direct observation, or by instruments, whether any part of an energized electric power circuit, exposed or concealed, is so located that the performance of the work may bring any person, tool, or machine into physical or electrical contact with the electric power circuit. The employer shall post and maintain proper warning signs where such a circuit exists. The employer shall advise employees of the location of such lines, the hazards involved, and the protective measures to be taken.

29 CFR 1926.417 · Lockout and tagging of circuits

29 CFR 1926.417(a)

(a) Controls. Controls that are to be deactivated during the course of work on energized or deenergized equipment or circuits shall be tagged.

29 CFR 1926.453 · Aerial lifts

29 CFR 1926.95 · Criteria for personal protective equipment

Other electrical contractors and other wiring installation contractors employers in Florida

Alert subscribers get notified of each newly cited employer in Florida the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.