OSHA SearchOSHA records by employer

E-Mc Electrical Services: OSHA inspections and violations

Arlington, Texas · Electrical Contractors and Other Wiring Installation Contractors · NAICS 238210

1inspections
4citation items
$6,464current penalties
Jan 20, 2022last inspection

OSHA inspectors have visited E-Mc Electrical Services in Texas one time.

It opened on Jan 20, 2022 on a referral, in Arlington.

In all, OSHA issued 4 citation items: 4 serious.

The proposed penalties came to $10,773; today they stand at $6,464, 40% less.

The rule cited most here is 1910.333 (working near live electrical parts), 4 times.

Among construction employers, the typical cited inspection since 2015 ends with a $3,079 penalty. E-Mc Electrical Services averages $6,464 across 1 cited inspection.

It reported 1 severe injury to OSHA since 2015.

E-Mc Electrical Services: OSHA citation items per year, 2022 to 2022
Citation items per year, by inspection date.

Want to know if OSHA cites E-Mc Electrical Services again? Add it to a watchlist and we will email you the morning the citation shows up.

Watch this company

Inspection history

Inspection 345741391 OPENED JAN 20, 2022Closed

Referral · Partial · Safety · 21 employees at the site · Closed Mar 15, 2022

2004 East Randol Mill Road, Arlington, TX 76011 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Incident on Jan 18, 2022: Employee working near energized electrical equipment suffers

At approximately 3:00pm on January 18, 2022, Employee #1 was working near energized electric equipment and circuits. Employee #1 was using a metal tool which made contact with an energized part, causing an arc flash. Employee #1 was transported to the hospital, admitted and treated for burns to both arms, hands and multiple fingers.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.333(a) · Working near live electrical parts
Serious$2,486$1,492Feb 22, 2022Final
Citation 1, item 2a
29 CFR 1910.333(a)(1) · Working near live electrical parts
Serious$5,801$3,481Feb 22, 2022Final
Citation 1, item 2b
29 CFR 1910.333(a)(2) · Working near live electrical parts
Serious$0$0Feb 22, 2022Final
Citation 1, item 3
29 CFR 1910.333(b)(1) · Working near live electrical parts
Serious$2,486$1,492Feb 22, 2022Final

Severe injury reports

Employers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 1 report on file.

Jan 18, 2022, Arlington: Hospitalization · electrical burns, unspecified · multiple body parts, n.e.c.

An employee was using a metal retrieval tool to dislodge a fiberglass tool trapped in an electrical conduit. The metal tool contacted live a electrical part, and an arc flash burned the employee's hand and face.

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.333 · Working near live electrical parts

29 CFR 1910.333(a)

(a) General. Safety-related work practices shall be employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work is performed near or on equipment or circuits which are or may be energized. The specific safety-related work practices shall be consistent with the nature and extent of the associated electrical hazards.

29 CFR 1910.333(a)(1)

(1) Deenergized parts. Live parts to which an employee may be exposed shall be deenergized before the employee works on or near them, unless the employer can demonstrate that deenergizing introduces additional or increased hazards or is infeasible due to equipment design or operational limitations. Live parts that operate at less than 50 volts to ground need not be deenergized if there will be no increased exposure to electrical burns or to explosion due to electric arcs.

29 CFR 1910.333(a)(2)

(2) Energized parts. If the exposed live parts are not deenergized (i.e., for reasons of increased or additional hazards or infeasibility), other safety-related work practices shall be used to protect employees who may be exposed to the electrical hazards involved. Such work practices shall protect employees against contact with energized circuit parts directly with any part of their body or indirectly through some other conductive object. The work practices that are used shall be suitable for the conditions under which the work is to be performed and for the voltage level of the exposed electric conductors or circuit parts. Specific work practice requirements are detailed in paragraph (c) of this section.

Other electrical contractors and other wiring installation contractors employers in Texas

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.