OSHA SearchOSHA records by employer

Electrical Reliability Services, Inc.: OSHA inspections and violations

Bradenton, Florida · Electrical Contractors and Other Wiring Installation Contractors · NAICS 238210

1inspections
1citation items
$15,625current penalties
Aug 1, 2023last inspection

OSHA inspectors have visited Electrical Reliability Services, Inc. in Florida one time.

It opened on Aug 1, 2023 on a referral, in Bradenton.

In all, OSHA issued 1 citation item: 1 other-than-serious.

The penalties, $15,625 in total, stand where OSHA first set them.

Among construction employers, the typical cited inspection since 2015 ends with a $3,079 penalty. Electrical Reliability Services, Inc. averages $15,625 across 1 cited inspection.

It reported 1 severe injury to OSHA since 2015.

Electrical Reliability Services, Inc.: OSHA citation items per year, 2023 to 2023
Citation items per year, by inspection date.

Want to know if OSHA cites Electrical Reliability Services, Inc. again? Add it to a watchlist and we will email you the morning the citation shows up.

Watch this company

Inspection history

Inspection 346874480 OPENED AUG 1, 2023Closed

Referral · Partial · Safety · 8 employees at the site · Closed Sep 24, 2025

1001 13th Ave E, Bradenton, FL 34208 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.333(b)(2)(iv)(b) · Working near live electrical parts
Other-than-serious$15,625$15,625Sep 28, 2023Final

Severe injury reports

Employers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 1 report on file.

Jul 23, 2023, Bradenton: Hospitalization · electrical burns, unspecified · hand(s) and arm(s), unspecified

An employee was performing electrical testing on a 5-kV electrical switch when an arc flash occurred. The employee sustained burns to the hands and arms.

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.333 · Working near live electrical parts

29 CFR 1910.333(b)(2)(iv)(b)

(B) A qualified person shall use test equipment to test the circuit elements and electrical parts of equipment to which employees will be exposed and shall verify that the circuit elements and equipment parts are deenergized. The test shall also determine if any energized condition exists as a result of inadvertently induced voltage or unrelated voltage backfeed even though specific parts of the circuit have been deenergized and presumed to be safe. If the circuit to be tested is over 600 volts, nominal, the test equipment shall be checked for proper operation immediately before and immediately after this test.

Other electrical contractors and other wiring installation contractors employers in Florida

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.