Elliott Electric, Inc.: OSHA inspections and violations
Lockport, Illinois · Electrical Contractors and Other Wiring Installation Contractors · NAICS 238210
3inspections
4citation items
$14,774current penalties
Sep 8, 2020last inspection
OSHA has inspected Elliott Electric, Inc. 3 times in Illinois since 1990.
The latest one began on Sep 8, 2020 after a fatality or catastrophe, in Minooka.
Those inspections ended with 4 citation items: 4 serious.
Penalties were first proposed at $14,774 and still stand at $14,774.
Ground-fault protection on job sites comes up most often in these citations: 2 items under 1926.404.
How that compares: the median penalty per cited inspection for construction employers since 2015 is $3,080, and Elliott Electric, Inc. averages $13,494 (1 cited inspection).
1 inspection on this page followed a fatal incident.
Elliott Electric, Inc. also files yearly injury logs with OSHA, summarized below.
Citation items per year, by inspection date.
Illinois · latest 90 days of OSHA records
416employers cited
Get notified the morning OSHA posts each new citation in Illinois: the employer, the site address, the rules broken and the penalty.
Incident on Sep 4, 2020 (fatal): Employee receives electrical shock and dies while terminatin
At 2:15 p.m. on September 4, 2020, an employee was working in a 480/277 volt distribution switchgear cabinet that was energized and partially trimmed out with electrical circuits. As some point, while terminating a ground wire for a 60-amp automatic transfer switch, the employee made contact with an energized buss bar and received an electrical shock. The employee was taken by ambulance to a local hospital, where the employee was pronounced dead with the cause determined to be electrocution.
From the Form 300A summaries employers file with OSHA each year. Rate = recordable cases per 100 full-time workers.
In 2025, the Coal City site logged 0 recordable injuries or illnesses among about 33 workers: 0.0 per 100 full-time workers, against a median of 1.8 for its industry.
Site and year
Workers
Cases
Days-away cases
Rate
Industry median
Elliott Electric Inc.
Coal City · 2025
33
0
0
0.0
1.8
Included with any plan: 3 more yearly logs from these sites, back to 2022, with each site's average rate over its latest three years. Already a subscriber? Sign in.
(b) Branch circuits—(1) Ground-fault protection—(i) General. The employer shall use either ground fault circuit interrupters as specified in paragraph (b)(1)(ii) of this section or an assured equipment grounding conductor program as specified in paragraph (b)(1)(iii) of this section to protect employees on construction sites. These requirements are in addition to any other requirements for equipment grounding conductors.
29 CFR 1926.404(f)(6)
(6) Grounding path. The path to ground from circuits, equipment, and enclosures shall be permanent and continuous.
(a) Protection of employees. (1) No employer shall permit an employee to work in such proximity to any part of an electric power circuit that the employee could contact the electric power circuit in the course of work, unless the employee is protected against electric shock by deenergizing the circuit and grounding it or by guarding it effectively by insulation or other means.
Alert subscribers get notified of each newly cited employer in Illinois the morning it is posted. See the alert plans.
Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.