OSHA SearchOSHA records by employer

Entact, LLC: OSHA inspections and violations

Lockport, Illinois · Site Preparation Contractors · NAICS 238910

2inspections
2citation items
$14,676current penalties
Nov 29, 2021last inspection

Entact, LLC has 2 OSHA inspections on record in Illinois, the first in 2004.

OSHA's last visit started on Nov 29, 2021 on a referral, in Lawrenceville.

Across those inspections OSHA issued 2 citation items: 2 other-than-serious.

OSHA proposed $17,612 in penalties. After settlements and reviews the total is $14,676, down 17%.

Most often, OSHA cited 1910.269, electric power generation, transmission, and distribution (2 items).

For context, across all construction employers the median penalty per cited inspection since 2015 is $3,079. Entact, LLC averages $14,676 over 1 cited inspection in that time.

Entact, LLC also files yearly injury logs with OSHA, summarized below.

It reported 1 severe injury to OSHA since 2015.

Entact, LLC: OSHA citation items per year, 2004 to 2021
Citation items per year, by inspection date.

Want to know if OSHA cites Entact, LLC again? Add it to a watchlist and we will email you the morning the citation shows up.

Watch this company

Inspection history

Inspection 345658793 OPENED NOV 29, 2021Closed

Referral · Partial · Safety · 6 employees at the site · Closed Feb 12, 2024

1 Illinois St., Lawrenceville, IL 62439 · Remediation Services · OSHA's record · Phone and website on Google Maps

Incident on Nov 17, 2021: Employee suffers burns from energized utility line

At 7:55 a.m. on November 17, 2021, an employee was repositioning orange plastic fencing markers on the line from an aerial lift basket within one foot of an electric utility line. After engaging an air brake on the line approximately 430 feet away, a coworker verified that the brake was engaged, and a multi-hasp lock and tag were placed on the air brake control. However a voltage detector was not used to verify that the line was de-energized. As the employee threw the fencing on to the line, an arc occurred between the line and the employee. A jumper wire on the utility side of the switch had moved out of position and made direct contact with the switch, bypassing the air gap created by the ground switch. Under the bypass condition, the line had approximately 10 kV of electricity. The employee was hospitalized for treatment of burns to right hand, with hole under middle finger through palm, burns to left hand, exit hole on left forearm.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.269(l)(1)(i) · Electric power generation, transmission, and distribution
Other-than-serious$8,806$5,870Apr 21, 2022Final
Citation 1, item 3
29 CFR 1910.269(n)(2) · Electric power generation, transmission, and distribution
Other-than-serious$8,806$8,806Apr 21, 2022Final

Inspection 307373944 OPENED OCT 12, 2004Closed

Complaint · Partial · Health · 40 employees at the site · Closed Oct 25, 2004

301 West 2nd Steet, Lockport, IL 60441 · Site Preparation Contractors · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

Injury and illness logs

From the Form 300A summaries employers file with OSHA each year. Rate = recordable cases per 100 full-time workers.

In 2018, the Lockport site logged 0 recordable injuries or illnesses among about 20 workers: 0.0 per 100 full-time workers, against a median of 1.0 for its industry.

Site and yearWorkersCasesDays-away casesRateIndustry median
Lockport site
Lockport · 2018
20 000.01.0
Lawrenceville site
Lawrenceville · 2018
18 000.01.0

Severe injury reports

Employers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 1 report on file.

Nov 18, 2021, Lawrenceville: Hospitalization · electrical burns, unspecified · hand(s), unspecified

An employee was rearranging markers on a 1,200-volt power line. A mechanical failure in the wire caused the lockout/tagout to fail. The employee sustained burns to both hands and was hospitalized.

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.269 · Electric power generation, transmission, and distribution

29 CFR 1910.269(l)(1)(i)

(1) General. (i) Only qualified employees may work on or with exposed energized lines or parts of equipment.

29 CFR 1910.269(n)(2)

(2) General. For any employee to work transmission and distribution lines or equipment as deenergized, the employer shall ensure that the lines or equipment are deenergized under the provisions of paragraph (m) of this section and shall ensure proper grounding of the lines or equipment as specified in paragraphs (n)(3) through (n)(8) of this section. However, if the employer can demonstrate that installation of a ground is impracticable or that the conditions resulting from the installation of a ground would present greater hazards to employees than working without grounds, the lines and equipment may be treated as deenergized provided that the employer establishes that all of the following conditions apply:

Other site preparation contractors employers in Illinois