OSHA SearchOSHA records by employer

Ericson Electric Inc: OSHA inspections and violations

Junction City, Oregon · Electrical Contractors and Other Wiring Installation Contractors · NAICS 238210

1inspections
7citation items
$200current penalties
Aug 31, 2022last inspection

OSHA has inspected Ericson Electric Inc once in Oregon.

The inspection began on Aug 31, 2022 as a planned inspection, in Junction City.

That inspection ended with 7 citation items: 3 serious and 4 other-than-serious.

Penalties were first proposed at $200 and still stand at $200.

Electrical wiring methods comes up most often in these citations: 3 items under 1910.305.

How that compares: the median penalty per cited inspection for construction employers since 2015 is $3,080, and Ericson Electric Inc averages $200 (1 cited inspection).

Ericson Electric Inc: OSHA citation items per year, 2022 to 2022
Citation items per year, by inspection date.

Oregon · latest 90 days of OSHA records

386employers cited

7 of them in the same industry

Get notified the morning OSHA posts each new citation in Oregon: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Oregon

Checking a subcontractor, a client or your own company? Watch Ericson Electric Inc and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 346189053 OPENED AUG 31, 2022Closed

Planned · Complete · Safety · 6 employees at the site · Closed Apr 19, 2023

94710 Highway 99 E, Junction City, OR 97448 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1a
29 CFR OAR 437-002-0041(8)(E)-1
Serious$100$100Oct 20, 2022Final
Citation 1, item 1b
29 CFR OAR 437-002-0041(4)(C)-3
Serious$0$0Oct 20, 2022Final
Citation 1, item 2
29 CFR 1910.305(j)(1)(i) · Electrical wiring methods
Serious$100$100Oct 20, 2022Final
Citation 2, item 3
29 CFR OAR 437-002-0022(3)(B)
Other-than-serious$0$0Oct 20, 2022Final
Citation 2, item 4
29 CFR 1910.305(b)(2)(i) · Electrical wiring methods
Other-than-serious$0$0Oct 20, 2022Final
Citation 2, item 5
29 CFR 1910.334(a)(1) · Using electrical equipment
Other-than-serious$0$0Oct 20, 2022Final
Citation 2, item 6
29 CFR 1910.305(c)(4) · Electrical wiring methods
Other-than-serious$0$0Oct 20, 2022Final

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.305 · Electrical wiring methods

29 CFR 1910.305(b)(2)(i)

(2) Covers and canopies. (i) All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear.

29 CFR 1910.305(c)(4)

(4) Faceplates for flush-mounted snap switches. Snap switches mounted in boxes shall have faceplates installed so as to completely cover the opening and seat against the finished surface.

29 CFR 1910.305(j)(1)(i)

(j) Equipment for general use—(1) Lighting fixtures, lampholders, lamps, and receptacles. (i) Fixtures, lampholders, lamps, rosettes, and receptacles may have no live parts normally exposed to employee contact. However, rosettes and cleat-type lampholders and receptacles located at least 2.44 m (8.0 ft) above the floor may have exposed terminals.

29 CFR 1910.334 · Using electrical equipment

Other electrical contractors and other wiring installation contractors employers in Oregon

Alert subscribers get notified of each newly cited employer in Oregon the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.