OSHA SearchOSHA records by employer

Gladieux Processing LLC: OSHA inspections and violations

Huntington, Indiana · Petroleum Refineries · NAICS 324110

1inspections
6citation items
$1,925current penalties
Jun 5, 2018last inspection

Gladieux Processing LLC has one OSHA inspection on record in Indiana.

OSHA opened it on Jun 5, 2018 on a referral, in Huntington.

From that inspection OSHA issued 6 citation items: 6 serious.

OSHA proposed $11,550 in penalties. After settlements and reviews the total is $1,925, down 83%.

Most often, OSHA cited 1910.106, flammable liquids (6 items).

For context, across all manufacturing employers the median penalty per cited inspection since 2015 is $4,500. Gladieux Processing LLC averages $1,925 over 1 cited inspection in that time.

Gladieux Processing LLC: OSHA citation items per year, 2018 to 2018
Citation items per year, by inspection date.

Want to know if OSHA cites Gladieux Processing LLC again? Add it to a watchlist and we will email you the morning the citation shows up.

Watch this company

Inspection history

Inspection 343240701 OPENED JUN 5, 2018Closed

Referral · Partial · Safety · 19 employees at the site · Closed Aug 27, 2018

4761 N Us 24 East, Huntington, IN 46750 · Petroleum Refineries · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.106(e)(3)(v)(a) · Flammable liquids
Serious$1,925$0Jul 24, 2018Final
Citation 1, item 1a
29 CFR 1910.106(e)(3)(v)(a) · Flammable liquids
Serious$1,925$1,925Jul 24, 2018Final
Citation 1, item 1b
29 CFR 1910.106(e)(6)(i) · Flammable liquids
Serious$1,925$0Jul 24, 2018Final
Citation 1, item 1c
29 CFR 1910.106(e)(6)(ii) · Flammable liquids
Serious$1,925$0Jul 24, 2018Final
Citation 1, item 2
29 CFR 1910.106(e)(6)(i) · Flammable liquids
Serious$1,925$0Jul 24, 2018Final
Citation 1, item 3
29 CFR 1910.106(e)(6)(ii) · Flammable liquids
Serious$1,925$0Jul 24, 2018Final

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.106 · Flammable liquids

29 CFR 1910.106(e)(3)(v)(a)

(v) Ventilation—(a) Areas as defined in paragraph (e)(3)(i) of this section using Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), shall be ventilated at a rate of not less than 1 cubic foot per minute per square foot of solid floor area. This shall be accomplished by natural or mechanical ventilation with discharge or exhaust to a safe location outside of the building. Provision shall be made for introduction of makeup air in such a manner as not to short circuit the ventilation. Ventilation shall be arranged to include all floor areas or pits where flammable vapors may collect.

29 CFR 1910.106(e)(6)(i)

(6) Sources of ignition—(i) General. Adequate precautions shall be taken to prevent the ignition of flammable vapors. Sources of ignition include but are not limited to open flames; lightning; smoking; cutting and welding; hot surfaces; frictional heat; static, electrical, and mechanical sparks; spontaneous ignition, including heat-producing chemical reactions; and radiant heat.

29 CFR 1910.106(e)(6)(ii)

(ii) Grounding. Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), shall not be dispensed into containers unless the nozzle and container are electrically interconnected. Where the metallic floorplate on which the container stands while filling is electrically connected to the fill stem or where the fill stem is bonded to the container during filling operations by means of a bond wire, the provisions of this section shall be deemed to have been complied with.

Other petroleum refineries employers in Indiana

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.