Since 2005, OSHA inspectors have visited Great Lakes Energy Cooperative in Michigan 4 times.
The most recent inspection opened on Sep 9, 2021 after a fatality or catastrophe, in Baldwin and is still open.
In all, OSHA issued 7 citation items: 4 serious and 3 other-than-serious.
The proposed penalties came to $23,050; today they stand at $21,980, 5% less.
The rule cited most here is 1910.269 (electric power generation, transmission, and distribution), 3 times.
Among construction employers, the typical cited inspection since 2015 ends with a $3,080 penalty. Great Lakes Energy Cooperative averages $10,740 across 2 cited inspections.
1 inspection on this page followed a fatal incident.
Inspection 345522296 OPENED SEP 9, 2021Open
Fatality or catastrophe · Partial · Safety · 55 employees at the site · Open
2143 W Lakes Colony Dr, Baldwin, MI 49304 · Power and Communication Line and Related Structures Construction · OSHA's record · Phone and website on Google Maps
Incident on Sep 8, 2021 (fatal): Employee is electrocuted in contact with electrical line
At 4:00 p.m. on September 8, 2021, an employee worked to hoist a broken electrical line into place on a pole and sleeve it. While working, the employee made contact with the live electrical line and was killed by electrocution.
| Citation and rule | Type | Proposed | Current | Issued | Status |
|---|
| Citation 1, item 1 |
Serious | $7,000 | $7,000 | Feb 4, 2022 | Final |
| Citation 1, item 3 |
Serious | $7,000 | $7,000 | Feb 4, 2022 | Final |
| Citation 1, item 4 |
Serious | $7,000 | $7,000 | Feb 4, 2022 | Final |
Current text from the Code of Federal Regulations. Some citations were issued under older wording.
29 CFR 1910.269 · Electric power generation, transmission, and distribution
29 CFR 1910.269(l)(3)(iii)
(iii) The employer shall ensure that no employee approaches or takes any conductive object closer to exposed energized parts than the employer's established minimum approach distance, unless:
29 CFR 1910.269(m)(3)(vi)
(vi) After the applicable requirements in paragraphs (m)(3)(i) through (m)(3)(v) of this section have been followed and the system operator gives a clearance to the employee in charge, the employer shall ensure that the lines and equipment are deenergized by testing the lines and equipment to be worked with a device designed to detect voltage.
29 CFR 1910.269(m)(3)(vii)
(vii) The employer shall ensure the installation of protective grounds as required by paragraph (n) of this section.
Alert subscribers get notified of each newly cited employer in Michigan the morning it is posted. See the alert plans.