Innomotics, LLC.: OSHA inspections and violations

Chicago, Illinois · Electrical Contractors and Other Wiring Installation Contractors · NAICS 238210

1inspections
4citation items
$35,000current penalties
Apr 4, 2024last inspection

Innomotics, LLC. has one OSHA inspection on record in Illinois.

OSHA opened it on Apr 4, 2024 after a fatality or catastrophe, in Chicago.

From that inspection OSHA issued 4 citation items: 1 serious and 3 other-than-serious.

OSHA proposed $27,655 in penalties and the amount has not been reduced.

Most often, OSHA cited 1926.405, job-site wiring (3 items).

For context, across all construction employers the median penalty per cited inspection since 2015 is $3,078. Innomotics, LLC. averages $35,000 over 1 cited inspection in that time.

1 inspection on this page followed a fatal incident.

Innomotics, LLC.: OSHA citation items per year, 2024 to 2024
Citation items per year, by inspection date.

Want to know if OSHA cites Innomotics, LLC. again? Add it to a watchlist and we will email you the morning the citation shows up.

Watch this company

Inspection history

Inspection 347394918 OPENED APR 4, 2024Closed

Fatality or catastrophe · Partial · Safety · 2 employees at the site · Closed Nov 13, 2025

1015 S. Central Park Ave., Chicago, IL 60644 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Incident on Apr 4, 2024 (fatal): Employee dies from electrocution while back feeding vfd

At 9:00 a.m. on April 2, 2024, an employee working as a field service technician for an electrical contractor was working at a city water plant. The employee was back feeding a variable frequency drive (VFD) using 480 volts to reform cell capacitors. The work environment had branch circuit cables laid on the floor and across passageways, conductors installed without strain relief and run through open cabinet doors that not protected from abrasion and splices in cables running 480 volts. The employee contacted an energized 480-volt, 30-amp, 3-phase power source to the electrical equipment while back feeding the VFD. At 10:00 a.m., the employee was pronounced dead on site by the county coroner.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1a
29 CFR 1926.405(a)(2)(ii)(b) · Job-site wiring
Other-than-serious$11,524$9,500Sep 11, 2024Final
Citation 1, item 1b
29 CFR 1926.405(b)(1) · Job-site wiring
Other-than-serious$0$0Sep 11, 2024Final
Citation 1, item 3c
29 CFR 1926.416(a)(3) · Electrical safety in construction
Serious$0$16,000Sep 11, 2024Final
Citation 2, item 1
29 CFR 1926.405(g)(2)(iii) · Job-site wiring
Other-than-serious$16,131$9,500Sep 11, 2024Final

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1926.405 · Job-site wiring

29 CFR 1926.405(a)(2)(ii)(b)

(B) Branch circuits shall originate in a power outlet or panelboard. Conductors shall be run as multiconductor cord or cable assemblies or open conductors, or shall be run in raceways. All conductors shall be protected by overcurrent devices at their ampacity. Runs of open conductors shall be located where the conductors will not be subject to physical damage, and the conductors shall be fastened at intervals not exceeding 10 feet (3.05 m). No branch-circuit conductors shall be laid on the floor. Each branch circuit that supplies receptacles or fixed equipment shall contain a separate equipment grounding conductor if the branch circuit is run as open conductors.

29 CFR 1926.405(b)(1)

(b) Cabinets, boxes, and fittings—(1) Conductors entering boxes, cabinets, or fittings. Conductors entering boxes, cabinets, or fittings shall be protected from abrasion, and openings through which conductors enter shall be effectively closed. Unused openings in cabinets, boxes, and fittings shall also be effectively closed.

29 CFR 1926.405(g)(2)(iii)

(iii) Splices. Flexible cords shall be used only in continuous lengths without splice or tap. Hard service flexible cords No. 12 or larger may be repaired if spliced so that the splice retains the insulation, outer sheath properties, and usage characteristics of the cord being spliced.

29 CFR 1926.416 · Electrical safety in construction

Other electrical contractors and other wiring installation contractors employers in Illinois

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.