OSHA SearchOSHA records by employer

Jacobs Field Services, North America: OSHA inspections and violations

Columbus, Nebraska · Electrical Contractors and Other Wiring Installation Contractors · NAICS 238210

2inspections
1citation items
$11,408current penalties
Feb 2, 2018last inspection

OSHA has inspected Jacobs Field Services, North America 2 times in Nebraska since 2017.

The latest one began on Feb 2, 2018 after a complaint, in Columbus.

Those inspections ended with 1 citation item: 1 serious.

Penalties were first proposed at $11,408 and still stand at $11,408.

How that compares: the median penalty per cited inspection for construction employers since 2015 is $3,080, and Jacobs Field Services, North America averages $11,408 (1 cited inspection).

Jacobs Field Services, North America also files yearly injury logs with OSHA, summarized below.

It reported 1 severe injury to OSHA since 2015.

Jacobs Field Services, North America: OSHA citation items per year, 2017 to 2018
Citation items per year, by inspection date.

Nebraska · latest 90 days of OSHA records

30employers cited

Get notified the morning OSHA posts each new citation in Nebraska: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Nebraska

Checking a subcontractor, a client or your own company? Watch Jacobs Field Services, North America and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 342926987 OPENED FEB 2, 2018Closed

Complaint · Partial · Health · 75 employees at the site · Closed Mar 23, 2018

3000 8th St., Columbus, NE 68601 · Other Building Equipment Contractors · OSHA's record · Phone and website on Google Maps

Incident on Oct 13, 2017: Employees inhale unknown fumes and lungs are irritated

At 9:30 a.m. on October 13, 2017, Employee #1, #2 and #3, employed by a construction company, were working on a multiemployer project at a wastewater treatment plant. Employee #1 was grinding an I-beam that was propped up on a steel skid pan. An unknown powdery substance in the skid pan began to smolder. All three employees, after inhaling the fumes, began to experience respiratory problems. Emergency services were called, and the employees were transported to the hospital. Employee #1 was hospitalized and treated for lung irritation. Employees #2 and #3 were treated and released. The subsequent investigation showed that the skid pan, which had been used by multiple contractors, likely contained a waste product that contained sulfur.

No citations from this inspection.

Inspection 342118841 OPENED FEB 16, 2017Closed

Referral · Partial · Safety · 5,200 employees at the site · Closed Feb 22, 2023

3000 8th St., Columbus, NE 68601 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Incident on Feb 8, 2017: Employee performing electrical work is burned by arc flash

At 1:00 p.m. on February 8, 2017, Employee #1, employed by a construction-related services company, was performing electrical work. He was terminating a ground wire onto a mechanical lug on the lower half of a 480-volt, 200-amp disconnect. When he loosened the mechanical ground lug, the ground wire came into contact with an energized A Phase at the top of the disconnect, which was not fully insulated. This caused an arc flash, and Employee #1 was burned. Emergency services were called, and Employee #1 was transported to the hospital. He was admitted and treated for burns to his face and left hand. face and left hand.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.335(a)(1)(i) · Safeguards for personnel protection
Serious$11,408$11,408Aug 3, 2017Final

Injury and illness logs

From the Form 300A summaries employers file with OSHA each year. Rate = recordable cases per 100 full-time workers.

In 2019, the Columbus site logged 0 recordable injuries or illnesses among about 70 workers: 0.0 per 100 full-time workers, against a median of 1.0 for its industry.

Site and yearWorkersCasesDays-away casesRateIndustry median
Jacobs Field Services North America at ADM Columbus
Columbus · 2019
70 000.01.0
JFSNA at ADM Columbus
Columbus · 2018
73 000.00.6

Included with any plan: 2 more yearly logs from these sites, back to 2016, with each site's average rate over its latest three years. Already a subscriber? Sign in.

See plans

Severe injury reports

Employers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 1 report on file.

Feb 8, 2017, Columbus: Hospitalization · electrical burns, unspecified · multiple body parts, n.e.c.

An employee was terminating a ground wire onto a mechanical lug on the lower half of a 480-volt, 200-amp disconnect. When he loosened the mechanical ground lug, the ground wire came into contact with an energized A-phase, which was not fully insulated, at the top of the disconnect. An arc flash then occurred and burned the employee's face and left hand.

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.335 · Safeguards for personnel protection

29 CFR 1910.335(a)(1)(i)

(a) Use of protective equipment—(1) Personal protective equipment. (i) Employees working in areas where there are potential electrical hazards shall be provided with, and shall use, electrical protective equipment that is appropriate for the specific parts of the body to be protected and for the work to be performed.

Other electrical contractors and other wiring installation contractors employers in Nebraska

Alert subscribers get notified of each newly cited employer in Nebraska the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.