OSHA SearchOSHA records by employer

Jordan High Voltage Inc: OSHA inspections and violations

Hallandale, Florida · Electrical Contractors and Other Wiring Installation Contractors · NAICS 238210

2inspections
4citation items
$19,649current penalties
Aug 8, 2019last inspection

Jordan High Voltage Inc has 2 OSHA inspections on record in Florida, the first in 2018.

OSHA's last visit started on Aug 8, 2019 on a referral, in Sunny Isles Beach, and the case has not closed yet.

Across those inspections OSHA issued 4 citation items: 3 serious and 1 other-than-serious.

OSHA proposed $19,649 in penalties and the amount has not been reduced.

Most often, OSHA cited 1926.416, electrical safety in construction (2 items).

For context, across all construction employers the median penalty per cited inspection since 2015 is $3,080. Jordan High Voltage Inc averages $19,649 over 1 cited inspection in that time.

1 inspection on this page followed a fatal incident.

It reported 1 severe injury to OSHA since 2015.

Jordan High Voltage Inc: OSHA citation items per year, 2018 to 2019
Citation items per year, by inspection date.

Florida · latest 90 days of OSHA records

321employers cited

4 of them in the same industry

Get notified the morning OSHA posts each new citation in Florida: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Florida

Checking a subcontractor, a client or your own company? Watch Jordan High Voltage Inc and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 344225982 OPENED AUG 8, 2019Open

Referral · Partial · Safety · 2 employees at the site · Open

400 Kings Point Dr., Sunny Isles Beach, FL 33160 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Incident on Aug 5, 2019: Employee receives electric shock and arc flash burns

At 10:00 a.m. on August 5, 2019, an employee was working as an electrician for a contractor that installed electrical and other wiring. He was working in a residential condominium's electrical vault. He was installing a cable from two new transformers to a main cabinet. He had not deenergized the main electrical switch. The main cabinet electrical switch was energized at approximately 7.6 kV, according to the firm's president. The employee was working near an RA switch. He was manipulating the cable, getting ready to connect it later. The employee lost control of the cable and grabbed it, but it inadvertently touched the still energized cabinet top. An electric arc flash resulted. In addition to being exposed to the arc flash, the employee received an electric shock from being in direct contact with the energized cable. He suffered burns. He was hospitalized for two or more days. The employee was wearing or using an MSA protective hard hat, safety glasses, a 7005-4 yellow switch stick, type I class 2 Salisbury electrical gloves rated at 17,000 volts with leather protective gloves over the Salisbury gloves, and a flame-resistant shirt. His employer had not provided him with steel toed safety shoes with an EH rating, per the employer's footwear policy, at no cost.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1a
29 CFR 1926.21(b)(2) · Construction safety training
Serious$9,446$9,446Feb 3, 2020Contested
Citation 1, item 1b
29 CFR 1926.416(a)(3) · Electrical safety in construction
Serious$0$0Feb 3, 2020Contested
Citation 1, item 2
29 CFR 1926.416(a)(1) · Electrical safety in construction
Serious$9,446$9,446Feb 3, 2020Contested
Citation 2, item 1
29 CFR 1926.95(d)(1) · Criteria for personal protective equipment
Other-than-serious$757$757Feb 3, 2020Contested

Inspection 343333332 OPENED JUL 25, 2018Closed

Fatality or catastrophe · Complete · Safety · 3 employees at the site · Closed Mar 7, 2019

1865 South Ocean Drive, Hallandale, FL 33008 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Incident on Jul 25, 2018 (fatal): Employee with cardio arterial disease dies at work

At 2:57 p.m. on July 25, 2018, an employee was replacing a transformer inside the eighth floor electrical vault room. A loud explosion occurred, which was heard by nearby coworkers. The employee was then observed staggering towards the door of the vault room and collapsed. A coworker performed CPR on the employee and he was taken to a nearby hospital where he later died.

No citations from this inspection.

Severe injury reports

Employers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 1 report on file.

Aug 5, 2019, Sunny Isles Beach: Hospitalization · electrical burns, unspecified · upper and lower limb(s)

An employee was working on a 7.6 kV electrical switch gear panel to add a new cable. The employee was electrocuted and sustained burns to both feet and the right hand.

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1926.21 · Construction safety training

29 CFR 1926.21(b)(2)

(2) The employer shall instruct each employee in the recognition and avoidance of unsafe conditions and the regulations applicable to his work environment to control or eliminate any hazards or other exposure to illness or injury.

29 CFR 1926.416 · Electrical safety in construction

29 CFR 1926.416(a)(1)

(a) Protection of employees. (1) No employer shall permit an employee to work in such proximity to any part of an electric power circuit that the employee could contact the electric power circuit in the course of work, unless the employee is protected against electric shock by deenergizing the circuit and grounding it or by guarding it effectively by insulation or other means.

29 CFR 1926.416(a)(3)

(3) Before work is begun the employer shall ascertain by inquiry or direct observation, or by instruments, whether any part of an energized electric power circuit, exposed or concealed, is so located that the performance of the work may bring any person, tool, or machine into physical or electrical contact with the electric power circuit. The employer shall post and maintain proper warning signs where such a circuit exists. The employer shall advise employees of the location of such lines, the hazards involved, and the protective measures to be taken.

29 CFR 1926.95 · Criteria for personal protective equipment

Other electrical contractors and other wiring installation contractors employers in Florida

Alert subscribers get notified of each newly cited employer in Florida the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.