Las Vegas Electric, Inc. has 10 OSHA inspections on record in Nevada, the first in 1982.
OSHA's last visit started on Jun 15, 2020 on a referral, in Las Vegas.
Across those inspections OSHA issued 19 citation items: 6 serious and 13 other-than-serious.
OSHA proposed $15,461 in penalties. After settlements and reviews the total is $6,685, down 57%.
Most often, OSHA cited 6180.5420, (3 items).
For context, across all construction employers the median penalty per cited inspection since 2015 is $3,080. Las Vegas Electric, Inc. averages $1,000 over 1 cited inspection in that time.
1 inspection on this page followed a fatal incident.
Las Vegas Electric, Inc. also files yearly injury logs with OSHA, summarized below.
Inspection 344788575 OPENED JUN 15, 2020Closed
Referral · Partial · Health · 55 employees at the site · Closed Jul 7, 2020
Intersection Of North Hualapai Way And West Farm Road, Las Vegas, NV 89166 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps
No citations from this inspection.
Incident on Jun 28, 1992 (fatal): Electric shock - direct contact with energized parts
AN ELECTRICIAN WAS PULLING AN ELECTRICAL SERVICE INTO A 2000-AMPERE, 480-VOLT MA IN SERVICE PANELBOARD. THE EMPLOYER SCHEDULED THE WORK ON A SUNDAY BECAUSE THE F ACILITY WAS A FOOD STORAGE AND PROCESSING PLANT, WHICH WOULD BE LEAST AFFECTED B Y A POWER OUTAGE ON A NON-WORKDAY. THE COMPANY'S SENIOR OFFICER, WHO WAS ASSISTI NG AS WELL AS SUPERVISING, ATTEMPTED TO DEENERGIZE THE SYSTEM BY OPENING THE MAI N DISCONNECT. THIS ACTION, HOWEVER, ONLY DEENERGIZED THE LOAD SIDE OF THE CIRCUI T, AND THE SERVICE ENTRANCE CONDUCTORS WERE STILL ENERGIZED. THE SUPERVISOR INST RUCTED THE CREW TO TEST THE CIRCUITS BEFORE BEGINNING WORK. ANOTHER EMPLOYEE OPE NED A SUB-PANEL, TESTED IT, AND FOUND IT TO BE DEENERGIZED. HE RELAYED THIS INFO RMATION TO THE OTHER CREW MEMBERS. SOON AFTER THIS, THE SUPERVISOR AND ANOTHER E MPLOYEE NOTICED THE ELECTRICIAN SLUMPED OVER AT HIS WORK AREA (THE MAIN PANELBOA RD). THE ELECTRICIAN WAS BLEEDING FROM HIS HEAD AND WAS NOT BREATHING. HE DIED O F ELECTROCUTION A SHORT TIME LATER. AFTER THE ACCIDENT, A CHECK FOUND AN ENERGIZ ED LINE WITHIN THE ELECTRICIAN'S WORK AREA. IT WAS THE 480-VOLT (277-VOLT-TO-GRO UND) SERVICE ENTRANCE CONDUCTORS FOR THE MAIN CIRCUIT BREAKER, AND IT ORIGINATED AT THE ELECTRIC UTILITY'S TRANSFORMER. THE TERMINAL LUGS AND BUSES TO WHICH THE SE CONDUCTORS WERE CONNECTED WERE ALSO ENERGIZED.
| Citation and rule | Type | Proposed | Current | Issued | Status |
|---|
| Citation 1, item 1 |
Serious | $1,500 | $750 | Aug 14, 1992 | Closed |
From the Form 300A summaries employers file with OSHA each year. Rate = recordable cases per 100 full-time workers.
In 2025, the Las Vegas site logged 5 recordable injuries or illnesses among about 68 workers: 7.0 per 100 full-time workers, against a median of 1.8 for its industry. Those cases cost 22 days away from work.
Current text from the Code of Federal Regulations. Some citations were issued under older wording.
Alert subscribers get notified of each newly cited employer in Nevada the morning it is posted. See the alert plans.
Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.