OSHA SearchOSHA records by employer

Libra Electric Company: OSHA inspections and violations

Oklahoma City, Oklahoma · Electrical Contractors and Other Wiring Installation Contractors · NAICS 238210

7inspections
8citation items
$26,153current penalties
May 16, 2023last inspection

OSHA has inspected Libra Electric Company 7 times in Oklahoma since 1990.

The latest one began on May 16, 2023 after a fatality or catastrophe, in Tulsa.

Those inspections ended with 8 citation items: 5 serious and 3 other-than-serious.

Penalties were first proposed at $32,650 and now stand at $26,153, 20% lower after settlements or reviews.

Electrical safety in construction comes up most often in these citations: 4 items under 1926.416.

How that compares: the median penalty per cited inspection for construction employers since 2015 is $3,080, and Libra Electric Company averages $13,076 (2 cited inspections).

1 inspection on this page followed a fatal incident.

Libra Electric Company also files yearly injury logs with OSHA, summarized below.

The Wage and Hour Division has 1 case on it since 2015, with $0 in back wages owed to workers.

Libra Electric Company: OSHA citation items per year, 1990 to 2023
Citation items per year, by inspection date.

Oklahoma · latest 90 days of OSHA records

53employers cited

2 of them in the same industry

Get notified the morning OSHA posts each new citation in Oklahoma: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Oklahoma

Checking a subcontractor, a client or your own company? Watch Libra Electric Company and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 346709769 OPENED MAY 16, 2023Closed

Fatality or catastrophe · Partial · Safety · 50 employees at the site · Closed Dec 22, 2023

8605 S. Elwood Ave On Taxiway L (lima) Between Runway 19r/01l And 19l/01r, Tulsa, OK 74132 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Incident on May 15, 2023 (fatal): Employee is killed by electrocution

At 3:15 p.m. on May 15, 2023, an employee was servicing a taxiway light. The employee cleared the contacts of a tester and preceded to perform the isolation work. The employee did not perform a second test to determine if the 5kV wire was live. The employee started to remove the electrical tape at the end of the electrical connection to the taxiway light that was connected to a series circuit. As the employee began to disconnect the connectors, the employee contacted the live male end of the series circuit and was electrocuted. The employee was killed.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1a
29 CFR 1926.416(a)(1) · Electrical safety in construction
Other-than-serious$10,938$6,563Nov 8, 2023Final
Citation 1, item 1b
29 CFR 1926.416(a)(3) · Electrical safety in construction
Serious$0$0Nov 8, 2023Final
Citation 1, item 2b
29 CFR 1926.417(b) · Lockout and tagging of circuits
Serious$0$6,563Nov 8, 2023Final
Citation 1, item 3
29 CFR 1926.95(a) · Criteria for personal protective equipment
Other-than-serious$10,938$6,563Nov 8, 2023Final

Inspection 342577160 OPENED AUG 15, 2017Closed

Planned · Partial · Health · 50 employees at the site · Closed Jan 10, 2018

7110 W. Reno Avenue, Oklahoma City, OK 73127 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1a
29 CFR 1926.416(a)(1) · Electrical safety in construction
Serious$5,387$3,232Dec 11, 2017Final
Citation 1, item 1b
29 CFR 1926.416(a)(3) · Electrical safety in construction
Serious$0$0Dec 11, 2017Final
Citation 1, item 2
29 CFR 1926.453(b)(2)(v) · Aerial lifts
Serious$5,387$3,232Dec 11, 2017Final

Inspection 311003156 OPENED JAN 28, 2008Closed

Unprogrammed other · Complete · Safety · 4 employees at the site · Closed Feb 27, 2008

3500 South Jenkins, Norman, OK 73072 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

Inspection 306643081 OPENED FEB 24, 2004Closed

Unprogrammed other · Partial · Safety · 5 employees at the site · Closed Feb 24, 2004

307 W Brooks, Norman, OK 73019 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

Inspection 301878146 OPENED AUG 7, 1998Closed

Planned · Complete · Safety · 2 employees at the site · Closed Feb 2, 1999

5905 North Classen, Oklahoma City, OK 73118 · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1926.403(g) · Electrical equipment on job sites
Other-than-serious$0$0Oct 5, 1998Closed

Inspection 300472768 OPENED SEP 20, 1996Closed

Unprogrammed other · Complete · Safety · 13 employees at the site · Closed Nov 14, 1996

100 North University, Edmond, OK 73034 · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

Inspection 106651821 OPENED FEB 27, 1990Closed

Planned · Complete · Safety · 6 employees at the site · Closed Apr 23, 1990

Altus Air Force Base, Altus, OK 73521 · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

Injury and illness logs

From the Form 300A summaries employers file with OSHA each year. Rate = recordable cases per 100 full-time workers.

In 2023, the Oklahoma City site logged 2 recordable injuries or illnesses among about 48 workers: 4.2 per 100 full-time workers, against a median of 1.8 for its industry. Those cases cost 1 days away from work.

Site and yearWorkersCasesDays-away casesRateIndustry median
Libra Electric Company
Oklahoma City · 2023
48 214.21.8

Included with any plan: 7 more yearly logs from these sites, back to 2016, with each site's average rate over its latest three years. Already a subscriber? Sign in.

See plans

Wage and hour cases

Cases by the Labor Department's Wage and Hour Division since 2015: unpaid minimum wage or overtime, child labor, family leave and more.

Period reviewedViolationsWorkers owedBack wagesPenalties
May 4, 2015 to May 3, 2017
Oklahoma City
20$0$0

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1926.403 · Electrical equipment on job sites

29 CFR 1926.403(g)

(g) Marking. Electrical equipment shall not be used unless the manufacturer's name, trademark, or other descriptive marking by which the organization responsible for the product may be identified is placed on the equipment and unless other markings are provided giving voltage, current, wattage, or other ratings as necessary. The marking shall be of sufficient durability to withstand the environment involved.

29 CFR 1926.416 · Electrical safety in construction

29 CFR 1926.416(a)(1)

(a) Protection of employees. (1) No employer shall permit an employee to work in such proximity to any part of an electric power circuit that the employee could contact the electric power circuit in the course of work, unless the employee is protected against electric shock by deenergizing the circuit and grounding it or by guarding it effectively by insulation or other means.

29 CFR 1926.416(a)(3)

(3) Before work is begun the employer shall ascertain by inquiry or direct observation, or by instruments, whether any part of an energized electric power circuit, exposed or concealed, is so located that the performance of the work may bring any person, tool, or machine into physical or electrical contact with the electric power circuit. The employer shall post and maintain proper warning signs where such a circuit exists. The employer shall advise employees of the location of such lines, the hazards involved, and the protective measures to be taken.

29 CFR 1926.417 · Lockout and tagging of circuits

29 CFR 1926.453 · Aerial lifts

29 CFR 1926.95 · Criteria for personal protective equipment

Other electrical contractors and other wiring installation contractors employers in Oklahoma

Alert subscribers get notified of each newly cited employer in Oklahoma the morning it is posted. See the alert plans.