OSHA SearchOSHA records by employer

Meany Inc.: OSHA inspections and violations

Riverside, Illinois · Electrical Contractors and Other Wiring Installation Contractors · NAICS 238210

3inspections
3citation items
$21,142current penalties
Jul 22, 2019last inspection

OSHA has inspected Meany Inc. 3 times in Illinois since 2012.

The latest one began on Jul 22, 2019 after a fatality or catastrophe, in Chicago Heights.

Those inspections ended with 3 citation items: 3 serious.

Penalties were first proposed at $27,214 and now stand at $21,142, 22% lower after settlements or reviews.

How that compares: the median penalty per cited inspection for construction employers since 2015 is $3,080, and Meany Inc. averages $9,346 (2 cited inspections).

1 inspection on this page followed a fatal incident.

Meany Inc.: OSHA citation items per year, 2012 to 2019
Citation items per year, by inspection date.

Illinois · latest 90 days of OSHA records

413employers cited

Get notified the morning OSHA posts each new citation in Illinois: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Illinois

Checking a subcontractor, a client or your own company? Watch Meany Inc. and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 344170758 OPENED JUL 22, 2019Closed

Fatality or catastrophe · Complete · Safety · 14 employees at the site · Closed Jan 23, 2020

101 W. 10th St., Chicago Heights, IL 60411 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Incident on Jul 20, 2019 (fatal): Employee contacts energized circuit and is electrocuted

At 12:45 p.m. on July 20, 2019, Employee #1 and two coworkers, employed by an electrical services company, were installing wiring and Acuity Brands BLT/BLC LED Luminaire lights in a school classroom. Employee #1, an electrician, was working from an 8-foot fiberglass ladder and checking an installed light that had shorted out. Coworker #1, the crew foreman, went to turn off the breaker that supplied power to the classroom. Before the power stopped transmitting to the room, Employee #1 made contact with an energized circuit, sustained an electrical shock, and fell from the ladder. Employee #1 was transported to the hospital, where he was pronounced dead from electrocution.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1926.416(a)(1) · Electrical safety in construction
Serious$13,260$13,260Nov 26, 2019Final

Inspection 342713559 OPENED OCT 19, 2017Closed

Unprogrammed related · Partial · Safety · 37 employees at the site · Closed Jan 4, 2018

556 St. James Gate, Bolingbrook, IL 60440 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1926.501(b)(1) · Fall protection in construction
Serious$9,054$5,432Dec 5, 2017Final

Inspection 334943388 OPENED JUN 25, 2012Closed

Unprogrammed other · Partial · Safety · 5 employees at the site · Closed Oct 25, 2012

Riverside School District 96, Riverside, IL 60546 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1926.403(i)(2)(i) · Electrical equipment on job sites
Serious$4,900$2,450Sep 25, 2012Final

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1926.403 · Electrical equipment on job sites

29 CFR 1926.403(i)(2)(i)

(2) Guarding of live parts. (i) Except as required or permitted elsewhere in this subpart, live parts of electric equipment operating at 50 volts or more shall be guarded against accidental contact by cabinets or other forms of enclosures, or by any of the following means:

29 CFR 1926.416 · Electrical safety in construction

29 CFR 1926.416(a)(1)

(a) Protection of employees. (1) No employer shall permit an employee to work in such proximity to any part of an electric power circuit that the employee could contact the electric power circuit in the course of work, unless the employee is protected against electric shock by deenergizing the circuit and grounding it or by guarding it effectively by insulation or other means.

29 CFR 1926.501 · Fall protection in construction

29 CFR 1926.501(b)(1)

(b)(1) Unprotected sides and edges. Each employee on a walking/working surface (horizontal and vertical surface) with an unprotected side or edge which is 6 feet (1.8 m) or more above a lower level shall be protected from falling by the use of guardrail systems, safety net systems, or personal fall arrest systems.

Other electrical contractors and other wiring installation contractors employers in Illinois

Alert subscribers get notified of each newly cited employer in Illinois the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.