OSHA SearchOSHA records by employer

Mille Lacs Energy Cooperative: OSHA inspections and violations

Onamia, Minnesota · Electric Power Distribution · NAICS 221122

1inspections
4citation items
$5,040current penalties
Mar 17, 2022last inspection

Mille Lacs Energy Cooperative has one OSHA inspection on record in Minnesota.

OSHA opened it on Mar 17, 2022 as a planned inspection, in Onamia.

From that inspection OSHA issued 4 citation items: 2 serious and 2 other-than-serious.

OSHA proposed $8,400 in penalties. After settlements and reviews the total is $5,040, down 40%.

Most often, OSHA cited 1910.269, electric power generation, transmission, and distribution (4 items).

For context, across all utility employers the median penalty per cited inspection since 2015 is $0. Mille Lacs Energy Cooperative averages $5,040 over 1 cited inspection in that time.

Mille Lacs Energy Cooperative: OSHA citation items per year, 2022 to 2022
Citation items per year, by inspection date.

Minnesota · latest 90 days of OSHA records

364employers cited

Get notified the morning OSHA posts each new citation in Minnesota: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Minnesota

Checking a subcontractor, a client or your own company? Watch Mille Lacs Energy Cooperative and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 345846067 OPENED MAR 17, 2022Closed

Planned · Partial · Safety · 2 employees at the site · Closed May 31, 2023

17278 Ataage Drive, Onamia, MN 56359 · Electric Power Distribution · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.269(l)(8)(v) · Electric power generation, transmission, and distribution
Other-than-serious$2,100$1,260Aug 3, 2022Final
Citation 1, item 2
29 CFR 1910.269(m)(3)(ii) · Electric power generation, transmission, and distribution
Serious$2,100$1,260Aug 3, 2022Final
Citation 1, item 3
29 CFR 1910.269(n)(3) · Electric power generation, transmission, and distribution
Serious$2,100$1,260Aug 3, 2022Final
Citation 1, item 4
29 CFR 1910.269(u)(5)(i) · Electric power generation, transmission, and distribution
Other-than-serious$2,100$1,260Aug 3, 2022Final

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.269 · Electric power generation, transmission, and distribution

29 CFR 1910.269(l)(8)(v)

(v) The employer shall ensure that each employee exposed to hazards from electric arcs wears protective clothing and other protective equipment with an arc rating greater than or equal to the heat energy estimated under paragraph (l)(8)(ii) of this section whenever that estimate exceeds 2.0 cal/cm 2. This protective equipment shall cover the employee's entire body, except as follows:

29 CFR 1910.269(m)(3)(ii)

(ii) The employer shall ensure that all switches, disconnectors, jumpers, taps, and other means through which known sources of electric energy may be supplied to the particular lines and equipment to be deenergized are open. The employer shall render such means inoperable, unless its design does not so permit, and then ensure that such means are tagged to indicate that employees are at work.

29 CFR 1910.269(n)(3)

(3) Equipotential zone. Temporary protective grounds shall be placed at such locations and arranged in such a manner that the employer can demonstrate will prevent each employee from being exposed to hazardous differences in electric potential.

Other electric power distribution employers in Minnesota

Alert subscribers get notified of each newly cited employer in Minnesota the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.