OSHA SearchOSHA records by employer

National Grid Electric Services LLC: OSHA inspections and violations

Feura Bush, New York · Electric Power Distribution · NAICS 221122

2inspections
3citation items
$36,333current penalties
May 1, 2019last inspection

OSHA has inspected National Grid Electric Services LLC 2 times in New York since 2018.

The latest one began on May 1, 2019 on a referral, in Elizaville.

Those inspections ended with 3 citation items: 2 serious and 1 other-than-serious.

Penalties were first proposed at $30,029 and still stand at $36,333.

Electric power generation, transmission, and distribution comes up most often in these citations: 3 items under 1910.269.

How that compares: the median penalty per cited inspection for utility employers since 2015 is $0, and National Grid Electric Services LLC averages $18,166 (2 cited inspections).

National Grid Electric Services LLC: OSHA citation items per year, 2018 to 2019
Citation items per year, by inspection date.

New York · latest 90 days of OSHA records

361employers cited

2 of them in the same industry

Get notified the morning OSHA posts each new citation in New York: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in New York

Checking a subcontractor, a client or your own company? Watch National Grid Electric Services LLC and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 343972337 OPENED MAY 1, 2019Closed

Referral · Partial · Safety · 10,000 employees at the site · Closed Dec 31, 2020

1699 County Rte 8, Elizaville, NY 12523 · Electric Power Distribution · OSHA's record · Phone and website on Google Maps

Incident on Apr 24, 2019: Employee receives shock after touching energized power line

At 2:30 p.m. on April 24, 2019, an employee was working for a utility that distributed electric power. The employer was removing and replacing a 65 foot (19.8 meter) H-frame wooden pole structure in the middle of an apple orchard. The pole carried a 115 kV transmission line. In an effort to work around the apple trees, the employer decided to work within the clear areas between the trees, instead of performing line clearance and removing some trees. The employer had the right-of-way and could have removed trees to provide room to remove and replace the structure without any obstructions. The employee was working as a ground worker. He was on the ground with coworkers aligning poles to be boomed up and installed. Among them was the chief lineman, who was working nearby on the pole truck. The boom truck was operating near low-hanging lines. The lines had been deenergized and grounded. Because the trees made clearance an issue and obstructed the view of the workers, the employee had to hold the outside conductor out of the way of the boom truck. The boom truck operator could then lift a pole between the tree rows. The employee took hold of the line to move it out of the way. He touched it with his bare hands. He was not wearing rubber insulating gloves. Although the line had been grounded and was believed to be deenergized, there was an induced voltage on the line. It had become energized. The employee received a near-fatal electric shock. He lost consciousness, and he suffered burns on his right thumb and right buttock, the entry and exit points for the electric current. He was hospitalized for two or more days.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 2
29 CFR 1910.269(a)(4) · Electric power generation, transmission, and distribution
Other-than-serious$13,260$6,630Jun 25, 2019Final
Citation 1, item 3
29 CFR 1910.269(c)(4)(ii)(a) · Electric power generation, transmission, and distribution
Serious$5,683$5,683Jun 25, 2019Final

Inspection 343623534 OPENED NOV 28, 2018Closed

Referral · Partial · Safety · 1,000 employees at the site · Closed Nov 4, 2020

481 Unionville Feura Bush Road, Feura Bush, NY 12067 · Electric Power Distribution · OSHA's record · Phone and website on Google Maps

Incident on Nov 21, 2018: Employee sustains electric shock while performing repairs wi

At 11:30 a.m. on November 21, 2018, an employee had opened an electrical cabinet to determine what parts may be needed to finish repair work. The equipment was energized at 13.2kV and the employee received an electric shock to his left index finger. The employee was hospitalized.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 2
29 CFR 1910.269(u)(5)(ii) · Electric power generation, transmission, and distribution
Serious$11,086$24,020Jan 4, 2019Final

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.269 · Electric power generation, transmission, and distribution

29 CFR 1910.269(a)(4)

(4) Existing characteristics and conditions. Existing characteristics and conditions of electric lines and equipment that are related to the safety of the work to be performed shall be determined before work on or near the lines or equipment is started. Such characteristics and conditions include, but are not limited to:

29 CFR 1910.269(c)(4)(ii)(a)

(A) If the work is complicated or particularly hazardous, or

29 CFR 1910.269(u)(5)(ii)

(5) Guarding of energized parts. (i) The employer shall provide guards around all live parts operating at more than 150 volts to ground without an insulating covering unless the location of the live parts gives sufficient clearance (horizontal, vertical, or both) to minimize the possibility of accidental employee contact.