OSHA SearchOSHA records by employer

Nations Electric, Inc.: OSHA inspections and violations

Atlanta, Georgia · Lessors of Nonresidential Buildings (except Miniwarehouses) · NAICS 531120

2inspections
3citation items
$8,071current penalties
Jan 25, 2019last inspection

Since 2018, OSHA inspectors have visited Nations Electric, Inc. in Georgia 2 times.

The most recent inspection opened on Jan 25, 2019 to follow up on an earlier case, in Douglasville.

In all, OSHA issued 3 citation items: 2 serious and 1 other-than-serious.

The penalties, $8,071 in total, stand where OSHA first set them.

Among real estate and rental employers, the typical cited inspection since 2015 ends with a $1,864 penalty. Nations Electric, Inc. averages $8,071 across 1 cited inspection.

It reported 1 severe injury to OSHA since 2015.

The Wage and Hour Division has 1 case on it since 2015, with $38,911 in back wages owed to workers.

Nations Electric, Inc.: OSHA citation items per year, 2018 to 2019
Citation items per year, by inspection date.

Georgia · latest 90 days of OSHA records

146employers cited

Get notified the morning OSHA posts each new citation in Georgia: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Georgia

Checking a subcontractor, a client or your own company? Watch Nations Electric, Inc. and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 343743027 OPENED JAN 25, 2019Closed

Follow-up · Partial · Safety · 3 employees at the site · Closed Apr 8, 2019

5915 Azalea Ridge Drive, Douglasville, GA 30135 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

Inspection 343055208 OPENED MAR 23, 2018Closed

Referral · Partial · Safety · 7 employees at the site · Closed Jul 23, 2019

285 Centennial Olympic Park: Children's Tower, Atlanta, GA 30313 · Lessors of Nonresidential Buildings (except Miniwarehouses) · OSHA's record · Phone and website on Google Maps

Incident on Mar 15, 2018: Employee is working on an electrical distribution panel and

At 2:00 p.m. on March 15, 2018, an employee was setting up to install breakers in a live 480V distribution panel at the switch gear area for an office build-out. The employee made contact with the bus bars when a screw driver fell inside the electrical panel and he suffered first, second, and third degree burns to his arm and face from an arc flash. The employee was hospitalized. hospitalized.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.333(a)(1) · Working near live electrical parts
Serious$3,880$3,880Sep 14, 2018Final
Citation 1, item 2
29 CFR 1910.335(a)(1)(i) · Safeguards for personnel protection
Serious$3,880$3,880Sep 14, 2018Final
Citation 2, item 1
29 CFR 1903.19(d)(1) · Proving cited hazards were fixed
Other-than-serious$311$311Jan 2, 2019Final

Severe injury reports

Employers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 1 report on file.

Mar 15, 2018, Atlanta: Hospitalization · third or fourth degree electrical burns · multiple body parts, n.e.c.

An employee was getting ready to put an insert inside a distribution panel when an arc flash occurred. He sustained first, second, and third degree burns to the face, legs, arm, and stomach.

Wage and hour cases

Cases by the Labor Department's Wage and Hour Division since 2015: unpaid minimum wage or overtime, child labor, family leave and more.

Period reviewedViolationsWorkers owedBack wagesPenalties
Aug 17, 2013 to Aug 15, 2015
Douglasville
149$38,911$0

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1903.19 · Proving cited hazards were fixed

29 CFR 1903.19(d)(1)

(d) Abatement documentation. (1) The employer must submit to the Agency, along with the information on abatement certification required by paragraph (c)(3) of this section, documents demonstrating that abatement is complete for each willful or repeat violation and for any serious violation for which the Agency indicates in the citation that such abatement documentation is required.

29 CFR 1910.333 · Working near live electrical parts

29 CFR 1910.333(a)(1)

(1) Deenergized parts. Live parts to which an employee may be exposed shall be deenergized before the employee works on or near them, unless the employer can demonstrate that deenergizing introduces additional or increased hazards or is infeasible due to equipment design or operational limitations. Live parts that operate at less than 50 volts to ground need not be deenergized if there will be no increased exposure to electrical burns or to explosion due to electric arcs.

29 CFR 1910.335 · Safeguards for personnel protection

29 CFR 1910.335(a)(1)(i)

(a) Use of protective equipment—(1) Personal protective equipment. (i) Employees working in areas where there are potential electrical hazards shall be provided with, and shall use, electrical protective equipment that is appropriate for the specific parts of the body to be protected and for the work to be performed.

Other lessors of nonresidential buildings (except miniwarehouses) employers in Georgia

Alert subscribers get notified of each newly cited employer in Georgia the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.