Inspection 343743027 OPENED JAN 25, 2019Closed
5915 Azalea Ridge Drive, Douglasville, GA 30135 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps
No citations from this inspection.
Since 2018, OSHA inspectors have visited Nations Electric, Inc. in Georgia 2 times.
The most recent inspection opened on Jan 25, 2019 to follow up on an earlier case, in Douglasville.
In all, OSHA issued 3 citation items: 2 serious and 1 other-than-serious.
The penalties, $8,071 in total, stand where OSHA first set them.
Among real estate and rental employers, the typical cited inspection since 2015 ends with a $1,864 penalty. Nations Electric, Inc. averages $8,071 across 1 cited inspection.
It reported 1 severe injury to OSHA since 2015.
The Wage and Hour Division has 1 case on it since 2015, with $38,911 in back wages owed to workers.
Georgia · latest 90 days of OSHA records
146employers cited
Get notified the morning OSHA posts each new citation in Georgia: the employer, the site address, the rules broken and the penalty.
See who gets cited nextLatest cited in Georgia
Checking a subcontractor, a client or your own company? Watch Nations Electric, Inc. and get notified the morning OSHA posts a new citation for it.
Watch this company5915 Azalea Ridge Drive, Douglasville, GA 30135 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps
No citations from this inspection.
285 Centennial Olympic Park: Children's Tower, Atlanta, GA 30313 · Lessors of Nonresidential Buildings (except Miniwarehouses) · OSHA's record · Phone and website on Google Maps
Incident on Mar 15, 2018: Employee is working on an electrical distribution panel and
At 2:00 p.m. on March 15, 2018, an employee was setting up to install breakers in a live 480V distribution panel at the switch gear area for an office build-out. The employee made contact with the bus bars when a screw driver fell inside the electrical panel and he suffered first, second, and third degree burns to his arm and face from an arc flash. The employee was hospitalized. hospitalized.
| Citation and rule | Type | Proposed | Current | Issued | Status |
|---|---|---|---|---|---|
| Citation 1, item 1 29 CFR 1910.333(a)(1) · Working near live electrical parts |
Serious | $3,880 | $3,880 | Sep 14, 2018 | Final |
| Citation 1, item 2 29 CFR 1910.335(a)(1)(i) · Safeguards for personnel protection |
Serious | $3,880 | $3,880 | Sep 14, 2018 | Final |
| Citation 2, item 1 29 CFR 1903.19(d)(1) · Proving cited hazards were fixed |
Other-than-serious | $311 | $311 | Jan 2, 2019 | Final |
Employers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 1 report on file.
Mar 15, 2018, Atlanta: Hospitalization · third or fourth degree electrical burns · multiple body parts, n.e.c.
An employee was getting ready to put an insert inside a distribution panel when an arc flash occurred. He sustained first, second, and third degree burns to the face, legs, arm, and stomach.
Cases by the Labor Department's Wage and Hour Division since 2015: unpaid minimum wage or overtime, child labor, family leave and more.
| Period reviewed | Violations | Workers owed | Back wages | Penalties |
|---|---|---|---|---|
| Aug 17, 2013 to Aug 15, 2015 Douglasville | 14 | 9 | $38,911 | $0 |
Current text from the Code of Federal Regulations. Some citations were issued under older wording.
29 CFR 1903.19(d)(1)
(d) Abatement documentation. (1) The employer must submit to the Agency, along with the information on abatement certification required by paragraph (c)(3) of this section, documents demonstrating that abatement is complete for each willful or repeat violation and for any serious violation for which the Agency indicates in the citation that such abatement documentation is required.
29 CFR 1910.333(a)(1)
(1) Deenergized parts. Live parts to which an employee may be exposed shall be deenergized before the employee works on or near them, unless the employer can demonstrate that deenergizing introduces additional or increased hazards or is infeasible due to equipment design or operational limitations. Live parts that operate at less than 50 volts to ground need not be deenergized if there will be no increased exposure to electrical burns or to explosion due to electric arcs.
29 CFR 1910.335(a)(1)(i)
(a) Use of protective equipment—(1) Personal protective equipment. (i) Employees working in areas where there are potential electrical hazards shall be provided with, and shall use, electrical protective equipment that is appropriate for the specific parts of the body to be protected and for the work to be performed.
Alert subscribers get notified of each newly cited employer in Georgia the morning it is posted. See the alert plans.
Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.