Next Generation Solutions, Inc: OSHA inspections and violations

Norfolk, Virginia · Commercial and Institutional Building Construction · NAICS 236220

1inspections
6citation items
$3,500current penalties
Aug 18, 2015last inspection

OSHA inspectors have visited Next Generation Solutions, Inc in Virginia one time.

It opened on Aug 18, 2015 after a fatality or catastrophe, in Norfolk.

In all, OSHA issued 6 citation items: 5 serious and 1 other-than-serious.

The proposed penalties came to $29,050; today they stand at $3,500, 88% less.

The rule cited most here is 1926.416 (electrical safety in construction), 2 times.

Among construction employers, the typical cited inspection since 2015 ends with a $3,080 penalty. Next Generation Solutions, Inc averages $3,500 across 1 cited inspection.

1 inspection on this page followed a fatal incident.

Next Generation Solutions, Inc: OSHA citation items per year, 2015 to 2015
Citation items per year, by inspection date.

Virginia · latest 90 days of OSHA records

249employers cited

22 of them in the same industry

Get notified the morning OSHA posts each new citation in Virginia: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Virginia

Checking a subcontractor, a client or your own company? Watch Next Generation Solutions, Inc and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 340856723 OPENED AUG 18, 2015Closed

Fatality or catastrophe · Complete · Safety · 2 employees at the site · Closed Mar 15, 2016

Tesla Charging Station, Janaf Shopping Center 5900 E. Virginia Beach Blvd, Norfolk, VA 23502 · Commercial and Institutional Building Construction · OSHA's record · Phone and website on Google Maps

Incident on Aug 18, 2015 (fatal): Employee contacts an energized bus bar and is electrocuted

At 10:23 a.m. on August 18, 2015, an employee was installing duct sealant into conduit inside an energized switch gear. The employee used his hands to press in and compact sealant around conductor protruding out of PVC conduit. The employee's head made contact with an energized bus bar and he was electrocuted. He sustained electrical burns to forehead, abdomen, back, arms, and hand. and hand.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1a
29 CFR 1926.95(a) · Criteria for personal protective equipment
Serious$7,000$3,500Feb 12, 2016Final
Citation 1, item 1b
29 CFR 1926.100(a) · Hard hats in construction
Serious$7,000$0Feb 12, 2016Final
Citation 1, item 1c
29 CFR 1926.416(a)(1) · Electrical safety in construction
Serious$7,000$0Feb 12, 2016Final
Citation 1, item 1d
29 CFR 1926.416(a)(3) · Electrical safety in construction
Serious$7,000$0Feb 12, 2016Final
Citation 1, item 1e
29 CFR 1926.417(b) · Lockout and tagging of circuits
Serious$1,050$0Feb 12, 2016Final
Citation 2, item 1
29 CFR 1926.403(h) · Electrical equipment on job sites
Other-than-serious$0$0Feb 12, 2016Final

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1926.100 · Hard hats in construction

29 CFR 1926.100(a)

(a) Employees working in areas where there is a possible danger of head injury from impact, or from falling or flying objects, or from electrical shock and burns, shall be protected by protective helmets.

29 CFR 1926.403 · Electrical equipment on job sites

29 CFR 1926.403(h)

(h) Identification of disconnecting means and circuits. Each disconnecting means required by this subpart for motors and appliances shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident. Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident. These markings shall be of sufficient durability to withstand the environment involved.

29 CFR 1926.416 · Electrical safety in construction

29 CFR 1926.416(a)(1)

(a) Protection of employees. (1) No employer shall permit an employee to work in such proximity to any part of an electric power circuit that the employee could contact the electric power circuit in the course of work, unless the employee is protected against electric shock by deenergizing the circuit and grounding it or by guarding it effectively by insulation or other means.

29 CFR 1926.417 · Lockout and tagging of circuits

29 CFR 1926.95 · Criteria for personal protective equipment