Inspection 340856723 OPENED AUG 18, 2015Closed
Tesla Charging Station, Janaf Shopping Center 5900 E. Virginia Beach Blvd, Norfolk, VA 23502 · Commercial and Institutional Building Construction · OSHA's record · Phone and website on Google Maps
Incident on Aug 18, 2015 (fatal): Employee contacts an energized bus bar and is electrocuted
At 10:23 a.m. on August 18, 2015, an employee was installing duct sealant into conduit inside an energized switch gear. The employee used his hands to press in and compact sealant around conductor protruding out of PVC conduit. The employee's head made contact with an energized bus bar and he was electrocuted. He sustained electrical burns to forehead, abdomen, back, arms, and hand. and hand.
| Citation and rule | Type | Proposed | Current | Issued | Status |
|---|---|---|---|---|---|
| Citation 1, item 1a 29 CFR 1926.95(a) · Criteria for personal protective equipment |
Serious | $7,000 | $3,500 | Feb 12, 2016 | Final |
| Citation 1, item 1b 29 CFR 1926.100(a) · Hard hats in construction |
Serious | $7,000 | $0 | Feb 12, 2016 | Final |
| Citation 1, item 1c 29 CFR 1926.416(a)(1) · Electrical safety in construction |
Serious | $7,000 | $0 | Feb 12, 2016 | Final |
| Citation 1, item 1d 29 CFR 1926.416(a)(3) · Electrical safety in construction |
Serious | $7,000 | $0 | Feb 12, 2016 | Final |
| Citation 1, item 1e 29 CFR 1926.417(b) · Lockout and tagging of circuits |
Serious | $1,050 | $0 | Feb 12, 2016 | Final |
| Citation 2, item 1 29 CFR 1926.403(h) · Electrical equipment on job sites |
Other-than-serious | $0 | $0 | Feb 12, 2016 | Final |