Inspection 340889955 OPENED SEP 1, 2015Closed
100 Bidwell Road, South Windsor, CT 06074 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps
Incident on Sep 1, 2015 (fatal): Employee is electrocuted while removing recessed light
At approximately 11:30 a.m. on September 1, 2015, an employee was removing 12-2 metal clad (MC) wire from a 2-ft by 4-ft recessed light. The employee turned off the wrong 20 amp circuit breaker at the panel. The circuit was connected to a four way light switch. The employee assumed the circuit was de-energized because it did not test positive for an electric current. An unknown person in another part of the facility turned on the light at a different location which energized the 277 volt/20 amp circuits. The employee received electric shock from an energized, 277 volt /20amp, recessed lighting circuit and was killed. circuit and was killed.
| Citation and rule | Type | Proposed | Current | Issued | Status |
|---|---|---|---|---|---|
| Citation 1, item 1b 29 CFR 1926.403(h) · Electrical equipment on job sites |
Serious | $0 | $2,800 | Nov 5, 2015 | Final |