OSHA SearchOSHA records by employer

Northern Lights Electrical, LLC: OSHA inspections and violations

South Windsor, Connecticut · Electrical Contractors and Other Wiring Installation Contractors · NAICS 238210

1inspections
1citation items
$2,800current penalties
Sep 1, 2015last inspection

OSHA inspectors have visited Northern Lights Electrical, LLC in Connecticut one time.

It opened on Sep 1, 2015 after a fatality or catastrophe, in South Windsor.

In all, OSHA issued 1 citation item: 1 serious.

No penalty came with these citations.

Among construction employers, the typical cited inspection since 2015 ends with a $3,080 penalty. Northern Lights Electrical, LLC averages $2,800 across 1 cited inspection.

1 inspection on this page followed a fatal incident.

Northern Lights Electrical, LLC: OSHA citation items per year, 2015 to 2015
Citation items per year, by inspection date.

Connecticut · latest 90 days of OSHA records

83employers cited

Get notified the morning OSHA posts each new citation in Connecticut: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Connecticut

Checking a subcontractor, a client or your own company? Watch Northern Lights Electrical, LLC and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 340889955 OPENED SEP 1, 2015Closed

Fatality or catastrophe · Partial · Safety · 5 employees at the site · Closed Apr 12, 2016

100 Bidwell Road, South Windsor, CT 06074 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Incident on Sep 1, 2015 (fatal): Employee is electrocuted while removing recessed light

At approximately 11:30 a.m. on September 1, 2015, an employee was removing 12-2 metal clad (MC) wire from a 2-ft by 4-ft recessed light. The employee turned off the wrong 20 amp circuit breaker at the panel. The circuit was connected to a four way light switch. The employee assumed the circuit was de-energized because it did not test positive for an electric current. An unknown person in another part of the facility turned on the light at a different location which energized the 277 volt/20 amp circuits. The employee received electric shock from an energized, 277 volt /20amp, recessed lighting circuit and was killed. circuit and was killed.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1b
29 CFR 1926.403(h) · Electrical equipment on job sites
Serious$0$2,800Nov 5, 2015Final

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1926.403 · Electrical equipment on job sites

29 CFR 1926.403(h)

(h) Identification of disconnecting means and circuits. Each disconnecting means required by this subpart for motors and appliances shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident. Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident. These markings shall be of sufficient durability to withstand the environment involved.

Other electrical contractors and other wiring installation contractors employers in Connecticut