Inspection 342519824 OPENED AUG 3, 2017Closed
1500 East Woodrow Wilson Dr., Jackson, MS 39201 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps
Incident on Jul 28, 2017: Worker installing circuit breaker is burned in arc flash
At 10:22 a.m. on July 28, 2017, Employee #1, employed by a construction company, was performing electrical work at a multiemployer construction site, a medical building. He was installing a new circuit breaker in an existing, live, 480-volt circuit breaker panel. Three straps, each with one screw, were required to install the breaker. Employee #1 had installed two straps and was working on the last strap when he dropped the screw. The screw struck live parts, causing an arc flash. Employee #1 was burned in the flash. Emergency services were called, and Employee #1 was transported to the hospital. He was admitted and treated for burns to his face, arms, and chest. The subsequent investigation determined that Employee #1 had not been wearing eye and face protection or arc flash protection.
| Citation and rule | Type | Proposed | Current | Issued | Status |
|---|---|---|---|---|---|
| Citation 1, item 1a 29 CFR 1926.102(a)(1) · Eye and face protection in construction |
Other-than-serious | $8,873 | $8,873 | Jan 4, 2018 | Final |
| Citation 1, item 1b 29 CFR 1926.416(a)(1) · Electrical safety in construction |
Other-than-serious | $0 | $0 | Jan 4, 2018 | Final |