Inspection 316720770 OPENED NOV 20, 2012Closed
Accident · Partial · Health · Local government · 25 employees at the site · Closed Jan 29, 2013
900 W. Pioneer Ave., Porterville, CA 93257 · Administration of Education Programs · OSHA's record · Phone and website on Google Maps
Incident on Nov 20, 2012: Refrigerant leak sends 16 school workers to hospital
On November 29, 2012, Employee #1, a 27-year-old male, Employee #2, a 26-year-ol d male, Employee #3, a 44-year-old female Employee #4, a 45-year-old female, Emp loyee #5, a 53-year-old female, Employee #6, a 54-year-old female, Employee #7, a 41-year-old male, Employee #8, a 57-year-old male, Employee #9, a 65-year-old female, Employee #10, a 59 -year-old female, Employee #11, a 41-year-old female, Employee #12, a 51-year-old female, Employee #13, a 54-year-old female, Employe e #14, a 49-year-old female, Employee #15, a 42-year-old female and Employee # 1 6, a 45-year-old female with Porterville Unified School District were involved i n a catastrophic event causing the sixteen employees to be transported to three medical facilities after the release of three hundred pounds of R-507 refrigeran t was released into Porterville Unified School District's Central Kitchen. The r elease occurred in the kitchen 47,000 cu. ft. cold room when the facility was no t occupied. At first, Employee's entering the cold room did not detect or notice anything wrong, however as the refrigerant migrated from the cold room into the warmer cooking area, it expanded and filled the kitchen. Employee's in these wa rmer areas were able to detect a sweet smell and then began experiencing upper r espiratory and eye irritations, which triggered an evacuation of the facility. T he refrigerant release was found to be the failure of the air handler's evaporat or coil that was abraded by an electrical conduit rubbing against it. During the installation of the air handler a hold-down clip that secures the conduit was n ot installed and the defect occurred under a cover that normally would not be re moved for normal maintenance.
No citations from this inspection.