OSHA SearchOSHA records by employer

Powertown Line Construction LLC: OSHA inspections and violations

Naples, Florida · Electrical Contractors and Other Wiring Installation Contractors · NAICS 238210

2inspections
4citation items
$17,112current penalties
Dec 20, 2023last inspection

Powertown Line Construction LLC has 2 OSHA inspections on record in Florida, the first in 2016.

OSHA's last visit started on Dec 20, 2023 on a referral, in Clearwater.

Across those inspections OSHA issued 4 citation items: 4 serious.

OSHA proposed $34,224 in penalties. After settlements and reviews the total is $17,112, down 50%.

Most often, OSHA cited 1926.960, working on or near exposed energized parts (4 items).

For context, across all construction employers the median penalty per cited inspection since 2015 is $3,080. Powertown Line Construction LLC averages $17,112 over 1 cited inspection in that time.

It reported 2 severe injuries to OSHA since 2015.

Powertown Line Construction LLC: OSHA citation items per year, 2016 to 2023
Citation items per year, by inspection date.

Florida · latest 90 days of OSHA records

320employers cited

4 of them in the same industry

Get notified the morning OSHA posts each new citation in Florida: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Florida

Checking a subcontractor, a client or your own company? Watch Powertown Line Construction LLC and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 347174393 OPENED DEC 20, 2023Closed

Referral · Partial · Safety · 4 employees at the site · Closed Jan 25, 2024

2244 Riverside Dr. N, Clearwater, FL 33762 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

Inspection 341956993 OPENED DEC 7, 2016Closed

Referral · Partial · Safety · 8 employees at the site · Closed Jan 25, 2018

5700 27th Place, Naples, FL 34117 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1926.960(c)(1)(iii)(b) · Working on or near exposed energized parts
Serious$11,408$5,704May 30, 2017Final
Citation 1, item 2a
29 CFR 1926.960(c)(2)(i)(b) · Working on or near exposed energized parts
Serious$11,408$5,704May 30, 2017Final
Citation 1, item 2b
29 CFR 1926.960(d)(1) · Working on or near exposed energized parts
Serious$0$0May 30, 2017Final
Citation 1, item 3
29 CFR 1926.960(g)(2) · Working on or near exposed energized parts
Serious$11,408$5,704May 30, 2017Final

Severe injury reports

Employers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 2 reports on file.

Dec 18, 2023, Clearwater: Hospitalization · electrical burns, unspecified · multiple face locations

An employee was connecting a utility transformer for underground service to a home. The employee's impact drill went across two connection bars with 240 volts of potential, creating an arc flash. The employee sustained burns to the face and eyes due to the arc flash and molten aluminum.

Dec 5, 2016, Naples: Hospitalization · third or fourth degree electrical burns · multiple body parts, n.e.c.

An employee was installing rubber protection (hoses and blankets) on a 13.2-KV powerline when an arc flash occurred, causing second and third degree burns to his upper right back and left upper leg.

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1926.960 · Working on or near exposed energized parts

29 CFR 1926.960(c)(1)(iii)(b)

(B) The energized part is insulated from the employee and from any other conductive object at a different potential, or

29 CFR 1926.960(c)(2)(i)(b)

(B) When installing insulation for purposes of paragraph (c)(2)(i)(A) of this section, the employee installs the insulation from a position that does not expose his or her upper arm to contact with other energized parts.

29 CFR 1926.960(d)(1)

(d) Working position—(1) Working from below. The employer shall ensure that each employee, to the extent that other safety-related conditions at the worksite permit, works in a position from which a slip or shock will not bring the employee's body into contact with exposed, uninsulated parts energized at a potential different from the employee's.

Other electrical contractors and other wiring installation contractors employers in Florida

Alert subscribers get notified of each newly cited employer in Florida the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.