Inspection 348658436 OPENED DEC 22, 2025Closed
400 South Prairie Avenue, Waukesha, WI 53186 · Service Establishment Equipment and Supplies Merchant Wholesalers · OSHA's record · Phone and website on Google Maps
No citations from this inspection.
Since 2024, OSHA inspectors have visited Prolec-GE Waukesha, Inc. in Wisconsin 3 times.
The most recent inspection opened on Dec 22, 2025 on a referral, in Waukesha.
In all, OSHA issued 5 citation items: 4 serious and 1 other-than-serious.
The proposed penalties came to $46,700; today they stand at $36,650, 22% less.
The rule cited most here is 1910.333 (working near live electrical parts), 3 times.
Among wholesale employers, the typical cited inspection since 2015 ends with a $3,422 penalty. Prolec-GE Waukesha, Inc. averages $36,650 across 1 cited inspection.
1 inspection on this page followed a fatal incident.
Prolec-GE Waukesha, Inc. also files yearly injury logs with OSHA, summarized below.
Wisconsin · latest 90 days of OSHA records
216employers cited
Get notified the morning OSHA posts each new citation in Wisconsin: the employer, the site address, the rules broken and the penalty.
See who gets cited nextLatest cited in Wisconsin
Checking a subcontractor, a client or your own company? Watch Prolec-GE Waukesha, Inc. and get notified the morning OSHA posts a new citation for it.
Watch this company400 South Prairie Avenue, Waukesha, WI 53186 · Service Establishment Equipment and Supplies Merchant Wholesalers · OSHA's record · Phone and website on Google Maps
No citations from this inspection.
400 South Prairie Avenue, Waukesha, WI 53186 · Service Establishment Equipment and Supplies Merchant Wholesalers · OSHA's record · Phone and website on Google Maps
No citations from this inspection.
400 South Prairie Avenue, Waukesha, WI 53186 · Service Establishment Equipment and Supplies Merchant Wholesalers · OSHA's record · Phone and website on Google Maps
Incident on Dec 7, 2024 (fatal): Employee dies from electrocution after arc flash
At 2:30 p.m. on December 7, 2024, Employee #1, a test technician at Prolec-GE Waukesha, Inc., was working alone in the transformer manufacturing test area. Using a scissor lift, the employee elevated approximately 15 feet to the top of a newly built high-voltage electrical transformer to disconnect three-phase power by removing power leads as part of teardown after an electrical test. The electrical circuit had not been effectively deenergized or verified as deenergized visually or with testing equipment prior to the work. While loosening a nut securing one of the power leads, an arc flash occurred, causing electrical current to pass through the employee. The employee was thrown onto the surface of the transformer top, sustaining burn and electrical shock injuries resulting in electrocution. The electrical power involved was approximately 8,000 volts.
| Citation and rule | Type | Proposed | Current | Issued | Status |
|---|---|---|---|---|---|
| Citation 1, item 1 29 CFR 1910.28(b)(1)(i) · Fall protection in general industry |
Other-than-serious | $10,050 | $10,050 | May 16, 2025 | Final |
| Citation 1, item 2a 29 CFR 1910.333(b)(2)(iv)(a) · Working near live electrical parts |
Serious | $16,550 | $16,550 | May 16, 2025 | Final |
| Citation 1, item 2b 29 CFR 1910.333(b)(2)(iv)(b) · Working near live electrical parts |
Serious | $0 | $0 | May 16, 2025 | Final |
| Citation 1, item 2c 29 CFR 1910.333(a)(1) · Working near live electrical parts |
Serious | $10,050 | $0 | May 16, 2025 | Final |
| Citation 1, item 3 29 CFR 1910.305(a)(2)(x) · Electrical wiring methods |
Serious | $10,050 | $10,050 | May 16, 2025 | Final |
From the Form 300A summaries employers file with OSHA each year. Rate = recordable cases per 100 full-time workers.
In 2025, the Waukesha site logged 21 recordable injuries or illnesses among about 774 workers: 2.8 per 100 full-time workers, against a median of 1.4 for its industry. Those cases cost 252 days away from work.
| Site and year | Workers | Cases | Days-away cases | Rate | Industry median |
|---|---|---|---|---|---|
| Prolec-GE Waukesha, Inc. Waukesha · 2025 | 774 | 21 | 5 | 2.8 | 1.4 |
Included with any plan: 3 more yearly logs from these sites, back to 2022, with each site's average rate over its latest three years. Already a subscriber? Sign in.
See plansCurrent text from the Code of Federal Regulations. Some citations were issued under older wording.
29 CFR 1910.28(b)(1)(i)
(b) Protection from fall hazards—(1) Unprotected sides and edges. (i) Except as provided elsewhere in this section, the employer must ensure that each employee on a walking-working surface with an unprotected side or edge that is 4 feet (1.2 m) or more above a lower level is protected from falling by one or more of the following:
29 CFR 1910.305(a)(2)(x)
(x) Flexible cords and cables shall be protected from accidental damage, as might be caused, for example, by sharp corners, projections, and doorways or other pinch points.
29 CFR 1910.333(a)(1)
(1) Deenergized parts. Live parts to which an employee may be exposed shall be deenergized before the employee works on or near them, unless the employer can demonstrate that deenergizing introduces additional or increased hazards or is infeasible due to equipment design or operational limitations. Live parts that operate at less than 50 volts to ground need not be deenergized if there will be no increased exposure to electrical burns or to explosion due to electric arcs.
Alert subscribers get notified of each newly cited employer in Wisconsin the morning it is posted. See the alert plans.
Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.