OSHA SearchOSHA records by employer

Quality Liquid Feeds, Inc.: OSHA inspections and violations

Dunlap, Iowa · Farm Supplies Merchant Wholesalers · NAICS 424910

2inspections
3citation items
$4,186current penalties
Jan 22, 2024last inspection

Quality Liquid Feeds, Inc. has 2 OSHA inspections on record in Iowa, the first in 2022.

OSHA's last visit started on Jan 22, 2024 after a complaint, in Dunlap.

Across those inspections OSHA issued 3 citation items: 3 serious.

OSHA proposed $8,372 in penalties. After settlements and reviews the total is $4,186, down 50%.

Most often, OSHA cited 1910.303, electrical equipment, general requirements (2 items).

For context, across all wholesale employers the median penalty per cited inspection since 2015 is $3,425. Quality Liquid Feeds, Inc. averages $4,186 over 1 cited inspection in that time.

1 inspection on this page followed a fatal incident.

Quality Liquid Feeds, Inc. also files yearly injury logs with OSHA, summarized below.

Quality Liquid Feeds, Inc.: OSHA citation items per year, 2022 to 2024
Citation items per year, by inspection date.

Iowa · latest 90 days of OSHA records

63employers cited

Get notified the morning OSHA posts each new citation in Iowa: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Iowa

Checking a subcontractor, a client or your own company? Watch Quality Liquid Feeds, Inc. and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 347222291 OPENED JAN 22, 2024Closed

Complaint · Partial · Safety · 22 employees at the site · Closed May 28, 2024

107 Remsen Street, Dunlap, IA 51529 · Farm Supplies Merchant Wholesalers · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1a
29 CFR 1910.303(b)(6) · Electrical equipment, general requirements
Serious$8,372$4,186Apr 25, 2024Final
Citation 1, item 1b
29 CFR 1910.305(e)(1) · Electrical wiring methods
Serious$0$0Apr 25, 2024Final
Citation 1, item 1c
29 CFR 1910.303(f)(3) · Electrical equipment, general requirements
Serious$0$0Apr 25, 2024Final

Inspection 346199672 OPENED SEP 7, 2022Closed

Fatality or catastrophe · Partial · Health · 28 employees at the site · Closed Feb 24, 2023

107 Remsen Street, Dunlap, IA 51529 · Farm Supplies Merchant Wholesalers · OSHA's record · Phone and website on Google Maps

Incident on Sep 2, 2022 (fatal): Employee dies from heart attack

At 4:30 p.m. on September 2, 2022, an employee was in the loading area on top of a nearly empty tanker truck's trailer. The employee was using a hose to wash out residual ground lime, i.e., Calcium Carbonate (CaCO3). A few minutes after talking to two coworkers, the employee was discovered unresponsive and without a pulse on the tanker platform by one of the coworkers in the loading area. The coworker initiated CPR and called 911. The employee was transported to the hospital, where he was pronounced dead as a result of a heart attack caused by coronary disease.

No citations from this inspection.

Injury and illness logs

From the Form 300A summaries employers file with OSHA each year. Rate = recordable cases per 100 full-time workers.

In 2025, the Dunlap site logged 2 recordable injuries or illnesses among about 26 workers: 9.3 per 100 full-time workers, against a median of 2.6 for its industry.

Site and yearWorkersCasesDays-away casesRateIndustry median
Quality Liquid Feeds Inc. - Dunlap
Dunlap · 2025
26 209.32.6
Quality Liquid Feeds, Inc Dunlap
Dunlap · 2019
16 115.72.6

Included with any plan: 3 more yearly logs from these sites, back to 2016, with each site's average rate over its latest three years. Already a subscriber? Sign in.

See plans

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.303 · Electrical equipment, general requirements

29 CFR 1910.303(b)(6)

(6) Deteriorating agents. Unless identified for use in the operating environment, no conductors or equipment shall be located in damp or wet locations; where exposed to gases, fumes, vapors, liquids, or other agents that have a deteriorating effect on the conductors or equipment; or where exposed to excessive temperatures.

29 CFR 1910.303(f)(3)

(3) Durability of markings. The markings required by paragraphs (f)(1) and (f)(2) of this section shall be of sufficient durability to withstand the environment involved.

29 CFR 1910.305 · Electrical wiring methods

29 CFR 1910.305(e)(1)

(e) Enclosures for damp or wet locations—(1) Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures. Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations shall be installed so as to prevent moisture or water from entering and accumulating within the enclosures and shall be mounted so there is at least 6.35-mm (0.25-in.) airspace between the enclosure and the wall or other supporting surface. However, nonmetallic enclosures may be installed without the airspace on a concrete, masonry, tile, or similar surface. The enclosures shall be weatherproof in wet locations.

Other farm supplies merchant wholesalers employers in Iowa

Alert subscribers get notified of each newly cited employer in Iowa the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.