OSHA SearchOSHA records by employer

Redline Electrical Services, LP: OSHA inspections and violations

Andrews, Texas · Electrical Contractors and Other Wiring Installation Contractors · NAICS 238210

2inspections
4citation items
$28,000current penalties
Jun 3, 2025last inspection

Redline Electrical Services, LP has 2 OSHA inspections on record in Texas, the first in 2022.

OSHA's last visit started on Jun 3, 2025 after a fatality or catastrophe, in Andrews.

Across those inspections OSHA issued 4 citation items: 4 serious.

OSHA proposed $38,556 in penalties. After settlements and reviews the total is $28,000, down 27%.

Most often, OSHA cited 1910.335, safeguards for personnel protection (2 items).

For context, across all construction employers the median penalty per cited inspection since 2015 is $3,080. Redline Electrical Services, LP averages $14,000 over 2 cited inspections in that time.

Redline Electrical Services, LP also files yearly injury logs with OSHA, summarized below.

It reported 1 severe injury to OSHA since 2015.

Redline Electrical Services, LP: OSHA citation items per year, 2022 to 2025
Citation items per year, by inspection date.

Texas · latest 90 days of OSHA records

391employers cited

7 of them in the same industry

Get notified the morning OSHA posts each new citation in Texas: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Texas

Checking a subcontractor, a client or your own company? Watch Redline Electrical Services, LP and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 348294737 OPENED JUN 3, 2025Closed

Fatality or catastrophe · Partial · Safety · 8 employees at the site · Closed Feb 27, 2026

32.2813.5, -102.5119.2, Andrews, TX 79714 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1 Serious$13,902$8,000Nov 21, 2025Final

Inspection 346019789 OPENED JUN 15, 2022Closed

Referral · Partial · Safety · 42 employees at the site · Closed Nov 28, 2022

31? 57.17.7 N/104? 02.13.2 W Well Hughins 1 H, Andrews, TX 79714 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.335(a)(2)(i) · Safeguards for personnel protection
Serious$8,629$7,000Oct 12, 2022Final
Citation 1, item 2
29 CFR 1910.333(a)(1) · Working near live electrical parts
Serious$8,629$7,000Oct 12, 2022Final
Citation 1, item 3
29 CFR 1910.335(a)(2)(ii) · Safeguards for personnel protection
Serious$7,396$6,000Oct 12, 2022Final

Injury and illness logs

From the Form 300A summaries employers file with OSHA each year. Rate = recordable cases per 100 full-time workers.

In 2022, the Andrews site logged 1 recordable injury or illness among about 45 workers: 1.6 per 100 full-time workers, against a median of 1.8 for its industry. Those cases cost 90 days away from work.

Site and yearWorkersCasesDays-away casesRateIndustry median
redline electrical services lp
Andrews · 2022
45 111.61.8

Severe injury reports

Employers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 1 report on file.

Jun 11, 2022, Andrews: Hospitalization · electrical burns, unspecified · hand(s) and arm(s), n.e.c.

An employee was troubleshooting an electrical problem at a well site. The employee touched an electrical panel with an impact wrench when an electrical arc occurred, resulting in burns to the employee's right hand and forearm.

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.333 · Working near live electrical parts

29 CFR 1910.333(a)(1)

(1) Deenergized parts. Live parts to which an employee may be exposed shall be deenergized before the employee works on or near them, unless the employer can demonstrate that deenergizing introduces additional or increased hazards or is infeasible due to equipment design or operational limitations. Live parts that operate at less than 50 volts to ground need not be deenergized if there will be no increased exposure to electrical burns or to explosion due to electric arcs.

29 CFR 1910.335 · Safeguards for personnel protection

29 CFR 1910.335(a)(2)(i)

(2) General protective equipment and tools. (i) When working near exposed energized conductors or circuit parts, each employee shall use insulated tools or handling equipment if the tools or handling equipment might make contact with such conductors or parts. If the insulating capability of insulated tools or handling equipment is subject to damage, the insulating material shall be protected.

29 CFR 1910.335(a)(2)(ii)

(ii) Protective shields, protective barriers, or insulating materials shall be used to protect each employee from shock, burns, or other electrically related injuries while that employee is working near exposed energized parts which might be accidentally contacted or where dangerous electric heating or arcing might occur. When normally enclosed live parts are exposed for maintenance or repair, they shall be guarded to protect unqualified persons from contact with the live parts.

29 CFR 1926.600 · Equipment

Other electrical contractors and other wiring installation contractors employers in Texas

Alert subscribers get notified of each newly cited employer in Texas the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.