OSHA SearchOSHA records by employer

Retail Power, Inc.: OSHA inspections and violations

Bethlehem, Georgia · Electrical Contractors and Other Wiring Installation Contractors · NAICS 238210

4inspections
7citation items
$27,215current penalties
Nov 16, 2017last inspection

Retail Power, Inc. has 4 OSHA inspections on record in Georgia, the first in 2012.

OSHA's last visit started on Nov 16, 2017 on a referral, in Milledgeville.

Across those inspections OSHA issued 7 citation items: 7 serious.

OSHA proposed $43,092 in penalties. After settlements and reviews the total is $27,215, down 37%.

Most often, OSHA cited 1926.404, ground-fault protection on job sites (2 items).

For context, across all construction employers the median penalty per cited inspection since 2015 is $3,080. Retail Power, Inc. averages $21,295 over 1 cited inspection in that time.

It reported 1 severe injury to OSHA since 2015.

Retail Power, Inc.: OSHA citation items per year, 2012 to 2017
Citation items per year, by inspection date.

Georgia · latest 90 days of OSHA records

145employers cited

2 of them in the same industry

Get notified the morning OSHA posts each new citation in Georgia: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Georgia

Checking a subcontractor, a client or your own company? Watch Retail Power, Inc. and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 342778180 OPENED NOV 16, 2017Closed

Referral · Partial · Safety · 4 employees at the site · Closed Jul 6, 2018

1970 N. Columbia St., Milledgeville, GA 31061 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Incident on Nov 9, 2017: Employee installing lighting is shocked and burned

At 12:00 p.m. on November 9, 2017, Employee #1, employed by an electrical services company, was installing lighting at a multiemployer construction project, a commercial building. As he was working on energized wires, he sustained a shock and burns to his hands. Emergency services were called, and Employee #1 was transported to the hospital, admitted, and treated for the electric shock and burns.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1926.21(b)(2) · Construction safety training
Serious$8,873$5,324Dec 29, 2017Final
Citation 1, item 2
29 CFR 1926.95(a) · Criteria for personal protective equipment
Serious$8,873$5,324Dec 29, 2017Final
Citation 1, item 3
29 CFR 1926.416(a)(1) · Electrical safety in construction
Serious$8,873$5,324Dec 29, 2017Final
Citation 1, item 4
29 CFR 1926.417(b) · Lockout and tagging of circuits
Serious$8,873$5,324Dec 29, 2017Final

Inspection 341447043 OPENED APR 20, 2016Closed

Unprogrammed related · Partial · Safety · 2 employees at the site · Closed Jun 11, 2016

1150 Dawsonville Highway, Gainesville, GA 30501 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

Inspection 334230232 OPENED APR 26, 2012Closed

Unprogrammed other · Complete · Safety · 4 employees at the site · Closed Aug 12, 2013

4959 Bill Gardner Pkwy, Locust Grove, GA 30248 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1926.403(e) · Electrical equipment on job sites
Serious$1,700$1,700Jun 13, 2012Final
Citation 1, item 2
29 CFR 1926.404(b)(1)(ii) · Ground-fault protection on job sites
Serious$1,700$1,700Jun 13, 2012Final

Inspection 315742767 OPENED MAR 27, 2012Closed

Unprogrammed other · Complete · Safety · 25 employees at the site · Closed Sep 4, 2012

916 Loganville Highway, Bethlehem, GA 30620 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1926.404(f)(6) · Ground-fault protection on job sites
Serious$4,200$2,520Apr 27, 2012Closed

Severe injury reports

Employers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 1 report on file.

Nov 9, 2017, Milledgeville: Hospitalization · third or fourth degree electrical burns · hand(s), unspecified

An employee was identifying whips to ensure they were not hot and then ohming them out. When he tested the last one, electricity jumped across his hands, causing third degree burns that required hospitalization.

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1926.21 · Construction safety training

29 CFR 1926.21(b)(2)

(2) The employer shall instruct each employee in the recognition and avoidance of unsafe conditions and the regulations applicable to his work environment to control or eliminate any hazards or other exposure to illness or injury.

29 CFR 1926.403 · Electrical equipment on job sites

29 CFR 1926.403(e)

(e) Splices. Conductors shall be spliced or joined with splicing devices designed for the use or by brazing, welding, or soldering with a fusible metal or alloy. Soldered splices shall first be so spliced or joined as to be mechanically and electrically secure without solder and then soldered. All splices and joints and the free ends of conductors shall be covered with an insulation equivalent to that of the conductors or with an insulating device designed for the purpose.

29 CFR 1926.404 · Ground-fault protection on job sites

29 CFR 1926.404(b)(1)(ii)

(ii) Ground-fault circuit interrupters. All 120-volt, single-phase, 15- and 20-ampere receptacle outlets on construction sites, which are not a part of the permanent wiring of the building or structure and which are in use by employees, shall have approved ground-fault circuit interrupters for personnel protection. Receptacles on a two-wire, single-phase portable or vehicle-mounted generator rated not more than 5kW, where the circuit conductors of the generator are insulated from the generator frame and all other grounded surfaces, need not be protected with ground-fault circuit interrupters.

29 CFR 1926.416 · Electrical safety in construction

29 CFR 1926.417 · Lockout and tagging of circuits

29 CFR 1926.95 · Criteria for personal protective equipment

Other electrical contractors and other wiring installation contractors employers in Georgia

Alert subscribers get notified of each newly cited employer in Georgia the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.