Inspection 347536609 OPENED JUN 7, 2024Closed
1818 N. Westmoreland Road, Dallas, TX 75212 · Plumbing, Heating, and Air-Conditioning Contractors · OSHA's record · Phone and website on Google Maps
Incident on Jun 6, 2024 (fatal): Employee is electrocuted while installing chiller system
At 1:40 p.m. on June 6, 2024, Employee #1, employed by a company installing a temporary cooling chiller system, was working on electrical connections. The employee was running 50-foot cables (4-AWG) from the rooftop to connect to the electrical panel and the chiller's disconnect on the ground. While working underneath the chiller equipment, the employee was electrocuted when the power to the equipment was energized, and the frame of the equipment was not grounded. The employee was found unresponsive and pronounced dead at the scene.
| Citation and rule | Type | Proposed | Current | Issued | Status |
|---|---|---|---|---|---|
| Citation 1, item 1a 29 CFR 1926.21(b)(2) · Construction safety training |
Other-than-serious | $11,292 | $11,292 | Dec 5, 2024 | Final |
| Citation 1, item 1b 29 CFR 1926.95(a) · Criteria for personal protective equipment |
Other-than-serious | $11,292 | $0 | Dec 5, 2024 | Final |
| Citation 1, item 3a 29 CFR 1926.404(f)(1)(iv) · Ground-fault protection on job sites |
Serious | $11,292 | $11,292 | Dec 5, 2024 | Final |
| Citation 1, item 3b 29 CFR 1926.417(b) · Lockout and tagging of circuits |
Serious | $11,292 | $0 | Dec 5, 2024 | Final |