OSHA SearchOSHA records by employer

Russ Electric a Siemens Buisness: OSHA inspections and violations

Colorado Springs, Colorado · Electric Power Distribution · NAICS 221122

1inspections
3citation items
$26,988current penalties
Sep 4, 2020last inspection

OSHA has inspected Russ Electric a Siemens Buisness once in Colorado.

The inspection began on Sep 4, 2020 on a referral, in Colorado Springs.

That inspection ended with 3 citation items: 3 other-than-serious.

Penalties were first proposed at $26,988 and still stand at $26,988.

Electric power generation, transmission, and distribution comes up most often in these citations: 3 items under 1910.269.

How that compares: the median penalty per cited inspection for utility employers since 2015 is $0, and Russ Electric a Siemens Buisness averages $26,988 (1 cited inspection).

Russ Electric a Siemens Buisness: OSHA citation items per year, 2020 to 2020
Citation items per year, by inspection date.

Colorado · latest 90 days of OSHA records

138employers cited

Get notified the morning OSHA posts each new citation in Colorado: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Colorado

Checking a subcontractor, a client or your own company? Watch Russ Electric a Siemens Buisness and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 344925169 OPENED SEP 4, 2020Closed

Referral · Partial · Safety · 2 employees at the site · Closed Apr 30, 2021

650 Sybilla Lane, Colorado Springs, CO 80921 · Electric Power Distribution · OSHA's record · Phone and website on Google Maps

Incident on Sep 2, 2020: Employee suffers electric shock

At 1:30 p.m. on September 2, 2020, an employee was cleaning electrical connectors, when he experienced electric shock. He was hospitalized.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.269(a)(2)(iv) · Electric power generation, transmission, and distribution
Other-than-serious$13,494$13,494Dec 28, 2020Final
Citation 1, item 2a
29 CFR 1910.269(m)(3)(ii) · Electric power generation, transmission, and distribution
Other-than-serious$13,494$13,494Dec 28, 2020Final
Citation 1, item 2c
29 CFR 1910.269(l)(8)(v) · Electric power generation, transmission, and distribution
Other-than-serious$0$0Dec 28, 2020Final

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.269 · Electric power generation, transmission, and distribution

29 CFR 1910.269(a)(2)(iv)

(iv) The employer shall determine, through regular supervision and through inspections conducted on at least an annual basis, that each employee is complying with the safety-related work practices required by this section.

29 CFR 1910.269(l)(8)(v)

(v) The employer shall ensure that each employee exposed to hazards from electric arcs wears protective clothing and other protective equipment with an arc rating greater than or equal to the heat energy estimated under paragraph (l)(8)(ii) of this section whenever that estimate exceeds 2.0 cal/cm 2. This protective equipment shall cover the employee's entire body, except as follows:

29 CFR 1910.269(m)(3)(ii)

(ii) The employer shall ensure that all switches, disconnectors, jumpers, taps, and other means through which known sources of electric energy may be supplied to the particular lines and equipment to be deenergized are open. The employer shall render such means inoperable, unless its design does not so permit, and then ensure that such means are tagged to indicate that employees are at work.