OSHA SearchOSHA records by employer

Seco Industrial Maintenance & Controls, Inc.: OSHA inspections and violations

Humble, Texas · Electrical Contractors and Other Wiring Installation Contractors · NAICS 238210

2inspections
4citation items
$5,590current penalties
Jun 3, 2015last inspection

OSHA has inspected Seco Industrial Maintenance & Controls, Inc. 2 times in Texas since 2003.

The latest one began on Jun 3, 2015 on a referral, in Houston.

Those inspections ended with 4 citation items: 4 serious.

Penalties were first proposed at $7,300 and now stand at $5,590, 23% lower after settlements or reviews.

Working near live electrical parts comes up most often in these citations: 3 items under 1910.333.

How that compares: the median penalty per cited inspection for construction employers since 2015 is $3,080, and Seco Industrial Maintenance & Controls, Inc. averages $2,240 (1 cited inspection).

1 inspection on this page followed a fatal incident.

Seco Industrial Maintenance & Controls, Inc. also files yearly injury logs with OSHA, summarized below.

It reported 1 severe injury to OSHA since 2015.

Seco Industrial Maintenance & Controls, Inc.: OSHA citation items per year, 2003 to 2015
Citation items per year, by inspection date.

Texas · latest 90 days of OSHA records

394employers cited

10 of them in the same industry

Get notified the morning OSHA posts each new citation in Texas: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Texas

Checking a subcontractor, a client or your own company? Watch Seco Industrial Maintenance & Controls, Inc. and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 340674720 OPENED JUN 3, 2015Closed

Referral · Complete · Safety · 23 employees at the site · Closed Feb 22, 2016

8615 Golden Spike, Houston, TX 77086 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1926.416(a)(3) · Electrical safety in construction
Serious$2,800$2,240Aug 11, 2015Final

Inspection 306565938 OPENED OCT 27, 2003Closed

Accident · Partial · Safety · 24 employees at the site · Closed Oct 15, 2004

14506 Smith Road, Humble, TX 77396 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Incident on Oct 24, 2003 (fatal): Employee electrocuted replacing part in pump feeder box

On October 24, 2003, Employee #1, an electrician, was replacing a CT part in a w astewater pump feeder box. He contacted 4,160 volt energized parts and was elect rocuted. The feeder box had fluctuating amps, and the stabs did not separate whe n the handles were activated. Employee #1 also did not verify the feeder box was de-energized or that the stabs had separated before beginning work.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.333(a) · Working near live electrical parts
Serious$1,500$1,500Feb 27, 2004Final
Citation 1, item 2
29 CFR 1910.333(b)(2)(i) · Working near live electrical parts
Serious$1,500$350Feb 27, 2004Final
Citation 1, item 3
29 CFR 1910.333(b)(2)(ivb) · Working near live electrical parts
Serious$1,500$1,500Feb 27, 2004Final

Injury and illness logs

From the Form 300A summaries employers file with OSHA each year. Rate = recordable cases per 100 full-time workers.

In 2017, the Houston site logged 1 recordable injury or illness among about 22 workers: 4.7 per 100 full-time workers, against a median of 1.8 for its industry.

Site and yearWorkersCasesDays-away casesRateIndustry median
Seco Industrial Maintenance & Controls, Inc.
Houston · 2017
22 104.71.8

Included with any plan: 1 more yearly log from these sites, back to 2016, with each site's average rate over its latest three years. Already a subscriber? Sign in.

See plans

Severe injury reports

Employers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 1 report on file.

Jun 2, 2015, Houston: Hospitalization · electrical burns, unspecified · hand(s), unspecified

An electrical contractor was installing a 480 volt electrical panel at a customer location. The employee pulled wires to the panel the day before the accident, but did not finish the job. When he returned to the facility the next day, he got on a ladder and touched the panel that he thought was cold. At some point between the time he left the panel and returned to finish the job the wires were…

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.333 · Working near live electrical parts

29 CFR 1910.333(a)

(a) General. Safety-related work practices shall be employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work is performed near or on equipment or circuits which are or may be energized. The specific safety-related work practices shall be consistent with the nature and extent of the associated electrical hazards.

29 CFR 1910.333(b)(2)(i)

(i) Procedures. The employer shall maintain a written copy of the procedures outlined in paragraph (b)(2) and shall make it available for inspection by employees and by the Assistant Secretary of Labor and his or her authorized representatives.

29 CFR 1910.333(b)(2)(ivb)

(B) A qualified person shall use test equipment to test the circuit elements and electrical parts of equipment to which employees will be exposed and shall verify that the circuit elements and equipment parts are deenergized. The test shall also determine if any energized condition exists as a result of inadvertently induced voltage or unrelated voltage backfeed even though specific parts of the circuit have been deenergized and presumed to be safe. If the circuit to be tested is over 600 volts, nominal, the test equipment shall be checked for proper operation immediately before and immediately after this test.

29 CFR 1926.416 · Electrical safety in construction

Other electrical contractors and other wiring installation contractors employers in Texas

Alert subscribers get notified of each newly cited employer in Texas the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.