Southern Technical Institute, LLC: OSHA inspections and violations

Tampa, Florida · Other Technical and Trade Schools · NAICS 611519

1inspections
3citation items
$35,469current penalties
Jan 16, 2025last inspection

OSHA has inspected Southern Technical Institute, LLC once in Florida.

The inspection began on Jan 16, 2025 on a referral, in Tampa.

That inspection ended with 3 citation items: 3 serious.

Penalties were first proposed at $35,469 and still stand at $35,469.

Working near live electrical parts comes up most often in these citations: 3 items under 1910.333.

How that compares: the median penalty per cited inspection for education employers since 2015 is $0, and Southern Technical Institute, LLC averages $35,469 (1 cited inspection).

It reported 1 severe injury to OSHA since 2015.

Southern Technical Institute, LLC: OSHA citation items per year, 2025 to 2025
Citation items per year, by inspection date.

Florida · latest 90 days of OSHA records

319employers cited

Get notified the morning OSHA posts each new citation in Florida: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Florida

Checking a subcontractor, a client or your own company? Watch Southern Technical Institute, LLC and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 347984270 OPENED JAN 16, 2025Closed

Referral · Partial · Safety · 50 employees at the site · Closed Aug 11, 2025

Tampa Campus 3910 Riga Blvd, Tampa, FL 33619 · Other Technical and Trade Schools · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.333(a)(1) · Working near live electrical parts
Serious$11,823$11,823Jun 18, 2025Final
Citation 1, item 2
29 CFR 1910.333(b)(2)(iii)(a) · Working near live electrical parts
Serious$11,823$11,823Jun 18, 2025Final
Citation 1, item 3
29 CFR 1910.333(b)(2)(iv)(b) · Working near live electrical parts
Serious$11,823$11,823Jun 18, 2025Final

Severe injury reports

Employers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 1 report on file.

Jan 8, 2025, Tampa: Hospitalization · electrical burns any degree · head and extremities

An employee was installing a temporary electrical line from one building to another. The employee was pulling a cable on a ladder to tie it into a panel when an arc flash occurred. The employee suffered hand and face burns.

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.333 · Working near live electrical parts

29 CFR 1910.333(a)(1)

(1) Deenergized parts. Live parts to which an employee may be exposed shall be deenergized before the employee works on or near them, unless the employer can demonstrate that deenergizing introduces additional or increased hazards or is infeasible due to equipment design or operational limitations. Live parts that operate at less than 50 volts to ground need not be deenergized if there will be no increased exposure to electrical burns or to explosion due to electric arcs.

29 CFR 1910.333(b)(2)(iii)(a)

(iii) Application of locks and tags. (A) A lock and a tag shall be placed on each disconnecting means used to deenergize circuits and equipment on which work is to be performed, except as provided in paragraphs (b)(2)(iii)(C) and (b)(2)(iii)(E) of this section. The lock shall be attached so as to prevent persons from operating the disconnecting means unless they resort to undue force or the use of tools.

29 CFR 1910.333(b)(2)(iv)(b)

(B) A qualified person shall use test equipment to test the circuit elements and electrical parts of equipment to which employees will be exposed and shall verify that the circuit elements and equipment parts are deenergized. The test shall also determine if any energized condition exists as a result of inadvertently induced voltage or unrelated voltage backfeed even though specific parts of the circuit have been deenergized and presumed to be safe. If the circuit to be tested is over 600 volts, nominal, the test equipment shall be checked for proper operation immediately before and immediately after this test.

Other other technical and trade schools employers in Florida

Alert subscribers get notified of each newly cited employer in Florida the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.