Inspection 345257679 OPENED APR 16, 2021Closed
3425 Service Road, Cleveland, OH 44111 · All Other Miscellaneous Chemical Product and Preparation Manufacturing · OSHA's record · Phone and website on Google Maps
Incident on Apr 14, 2021 (fatal): Employee is electrocuted, later dies
At 8:00 a.m. on April 14, 2021, an employee, a maintenance technician, was preparing a Miller, Millermatic 350P MIG portable welder machine to weld the frame of a dust collector. The employee plugged the welder into the 30 amp, 480 volt receptacle outlet when an electrical short occurred in a splice on the power cable. The electrical short occurred due to two or more bare and uninsulated conductors touching one another resulting in the grounding wire to become energized. The electricity traveled from the receptacle through the receptacle grounding conductor to the grounding lug terminal of the electrical cabinet. The branch circuit and cabinet did not have a grounding conductor or other grounding connection so the electricity energized the entire metal electrical cabinet. The circuit had 150 amp fuses installed so they did not interrupt the current when the electrical short occurred. The employee was standing at the electrical cabinet in an area of the floor that was wet and was electrocuted when he contacted the electrical cabinet. The employee was transported to the hospital and died two days later.
| Citation and rule | Type | Proposed | Current | Issued | Status |
|---|---|---|---|---|---|
| Citation 1, item 1 29 CFR 1910.22(a)(2) · Walking-working surfaces |
Serious | $13,653 | $9,557 | Jul 16, 2021 | Final |
| Citation 1, item 2a 29 CFR 1910.254(c)(3)(i) · Arc welding and cutting |
Serious | $13,653 | $9,557 | Jul 16, 2021 | Final |
| Citation 1, item 2b 29 CFR 1910.303(b)(4) · Electrical equipment, general requirements |
Serious | $0 | $0 | Jul 16, 2021 | Final |
| Citation 1, item 2c 29 CFR 1910.304(f)(1)(i) · Grounding and circuit protection |
Serious | $0 | $0 | Jul 16, 2021 | Final |
| Citation 1, item 3a 29 CFR 1910.254(d)(9)(i) · Arc welding and cutting |
Serious | $13,653 | $9,557 | Jul 16, 2021 | Final |
| Citation 1, item 3b 29 CFR 1910.254(d)(9)(iii) · Arc welding and cutting |
Serious | $0 | $0 | Jul 16, 2021 | Final |
| Citation 1, item 3c 29 CFR 1910.303(c)(3)(i) · Electrical equipment, general requirements |
Serious | $0 | $0 | Jul 16, 2021 | Final |
| Citation 1, item 3d 29 CFR 1910.334(a)(2)(i) · Using electrical equipment |
Serious | $0 | $0 | Jul 16, 2021 | Final |
| Citation 1, item 4a 29 CFR 1910.304(g)(5) · Grounding and circuit protection |
Serious | $13,653 | $9,557 | Jul 16, 2021 | Final |
| Citation 1, item 4b 29 CFR 1910.304(g)(6)(ii) · Grounding and circuit protection |
Serious | $0 | $0 | Jul 16, 2021 | Final |