OSHA SearchOSHA records by employer

SRC Worldwide, Inc.: OSHA inspections and violations

Cleveland, Ohio · All Other Miscellaneous Chemical Product and Preparation Manufacturing · NAICS 325998

4inspections
14citation items
$44,693current penalties
Apr 16, 2021last inspection

Since 2017, OSHA inspectors have visited SRC Worldwide, Inc. in Ohio 4 times.

The most recent inspection opened on Apr 16, 2021 after a fatality or catastrophe, in Cleveland.

In all, OSHA issued 14 citation items: 14 serious.

The proposed penalties came to $63,848; today they stand at $44,693, 30% less.

The rule cited most here is 1910.304 (grounding and circuit protection), 3 times.

Among manufacturing employers, the typical cited inspection since 2015 ends with a $4,500 penalty. SRC Worldwide, Inc. averages $22,347 across 2 cited inspections.

1 inspection on this page followed a fatal incident.

It reported 2 severe injuries to OSHA since 2015.

SRC Worldwide, Inc.: OSHA citation items per year, 2017 to 2021
Citation items per year, by inspection date.

Want to know if OSHA cites SRC Worldwide, Inc. again? Add it to a watchlist and we will email you the morning the citation shows up.

Watch this company

Inspection history

Inspection 345257679 OPENED APR 16, 2021Closed

Fatality or catastrophe · Partial · Safety · 20 employees at the site · Closed Apr 11, 2022

3425 Service Road, Cleveland, OH 44111 · All Other Miscellaneous Chemical Product and Preparation Manufacturing · OSHA's record · Phone and website on Google Maps

Incident on Apr 14, 2021 (fatal): Employee is electrocuted, later dies

At 8:00 a.m. on April 14, 2021, an employee, a maintenance technician, was preparing a Miller, Millermatic 350P MIG portable welder machine to weld the frame of a dust collector. The employee plugged the welder into the 30 amp, 480 volt receptacle outlet when an electrical short occurred in a splice on the power cable. The electrical short occurred due to two or more bare and uninsulated conductors touching one another resulting in the grounding wire to become energized. The electricity traveled from the receptacle through the receptacle grounding conductor to the grounding lug terminal of the electrical cabinet. The branch circuit and cabinet did not have a grounding conductor or other grounding connection so the electricity energized the entire metal electrical cabinet. The circuit had 150 amp fuses installed so they did not interrupt the current when the electrical short occurred. The employee was standing at the electrical cabinet in an area of the floor that was wet and was electrocuted when he contacted the electrical cabinet. The employee was transported to the hospital and died two days later.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.22(a)(2) · Walking-working surfaces
Serious$13,653$9,557Jul 16, 2021Final
Citation 1, item 2a
29 CFR 1910.254(c)(3)(i) · Arc welding and cutting
Serious$13,653$9,557Jul 16, 2021Final
Citation 1, item 2b
29 CFR 1910.303(b)(4) · Electrical equipment, general requirements
Serious$0$0Jul 16, 2021Final
Citation 1, item 2c
29 CFR 1910.304(f)(1)(i) · Grounding and circuit protection
Serious$0$0Jul 16, 2021Final
Citation 1, item 3a
29 CFR 1910.254(d)(9)(i) · Arc welding and cutting
Serious$13,653$9,557Jul 16, 2021Final
Citation 1, item 3b
29 CFR 1910.254(d)(9)(iii) · Arc welding and cutting
Serious$0$0Jul 16, 2021Final
Citation 1, item 3c
29 CFR 1910.303(c)(3)(i) · Electrical equipment, general requirements
Serious$0$0Jul 16, 2021Final
Citation 1, item 3d
29 CFR 1910.334(a)(2)(i) · Using electrical equipment
Serious$0$0Jul 16, 2021Final
Citation 1, item 4a
29 CFR 1910.304(g)(5) · Grounding and circuit protection
Serious$13,653$9,557Jul 16, 2021Final
Citation 1, item 4b
29 CFR 1910.304(g)(6)(ii) · Grounding and circuit protection
Serious$0$0Jul 16, 2021Final

Inspection 345228308 OPENED APR 1, 2021Closed

Referral · Partial · Safety · 20 employees at the site · Closed Jul 15, 2021

3425 Service Road, Cleveland, OH 44111 · All Other Miscellaneous Chemical Product and Preparation Manufacturing · OSHA's record · Phone and website on Google Maps

Incident on Mar 22, 2021: Employee amputates fingertip when caught between belt and pu

At 12:15 a.m. on March 22, 2021, an employee was unjamming a grinder machine. With the power turned off the grinder machine, the employee removed the belt and pulley guard. The employee then manually attempted to spin the belt to free up the machine. The employee's finger was pulled through the belt and pulley of the machine, causing a fingertip amputation. The employee was hospitalized.

No citations from this inspection.

Inspection 342877602 OPENED JAN 12, 2018Closed

Follow-up · Partial · Safety · 20 employees at the site · Closed Mar 29, 2018

3425 Service Road, Cleveland, OH 44111 · All Other Miscellaneous Chemical Product and Preparation Manufacturing · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

Inspection 342476181 OPENED JUL 6, 2017Closed

Complaint · Partial · Safety · 20 employees at the site · Closed Jul 24, 2018

3425 Service Road, Cleveland, OH 44111 · All Other Miscellaneous Chemical Product and Preparation Manufacturing · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.22(d)(1) · Walking-working surfaces
Serious$2,463$1,724Sep 21, 2017Final
Citation 1, item 2
29 CFR 1910.28(b)(1)(i) · Fall protection in general industry
Serious$2,463$1,724Sep 21, 2017Final
Citation 1, item 3
29 CFR 1910.147(c)(4)(i) · Lockout/tagout
Serious$2,463$1,724Sep 21, 2017Final
Citation 1, item 4
29 CFR 1910.305(g)(2)(iii) · Electrical wiring methods
Serious$1,847$1,293Sep 21, 2017Final

Severe injury reports

Employers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 2 reports on file.

Apr 5, 2023, Cleveland: Hospitalization · electrical burns, unspecified · hand(s) and arm(s), unspecified

On April 5, 2023, an employee was using a torch to melt product away from the tap hole of a furnace. The employee felt an electric shock in their left arm, which cased them to drop the torch and resulted in electrical burns to their arm and hand.

Mar 22, 2021, Cleveland: Hospitalization, amputation · amputations · fingertip(s)

An employee was spinning the belts on a machine after the machine had jammed. The employee's ring finger was caught between the belt and the sheave of the machine, causing a partial amputation to the fingertip.

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.147 · Lockout/tagout

29 CFR 1910.147(c)(4)(i)

(4) Energy control procedure. (i) Procedures shall be developed, documented and utilized for the control of potentially hazardous energy when employees are engaged in the activities covered by this section.

29 CFR 1910.22 · Walking-working surfaces

29 CFR 1910.22(a)(2)

(2) The floor of each workroom is maintained in a clean and, to the extent feasible, in a dry condition. When wet processes are used, drainage must be maintained and, to the extent feasible, dry standing places, such as false floors, platforms, and mats must be provided.

29 CFR 1910.22(d)(1)

(1) Walking-working surfaces are inspected, regularly and as necessary, and maintained in a safe condition;

29 CFR 1910.254 · Arc welding and cutting

29 CFR 1910.28 · Fall protection in general industry

29 CFR 1910.303 · Electrical equipment, general requirements

29 CFR 1910.304 · Grounding and circuit protection

29 CFR 1910.305 · Electrical wiring methods

29 CFR 1910.334 · Using electrical equipment

Other all other miscellaneous chemical product and preparation manufacturing employers in Ohio