OSHA SearchOSHA records by employer

STS Industrial Incorporated: OSHA inspections and violations

Orange, Texas · Hardware Merchant Wholesalers · NAICS 423710

1inspections
9citation items
$45,733current penalties
Aug 15, 2023last inspection

OSHA has inspected STS Industrial Incorporated once in Texas.

The inspection began on Aug 15, 2023 after a fatality or catastrophe, in Orange.

That inspection ended with 9 citation items: 9 serious.

Penalties were first proposed at $90,339 and now stand at $45,733, 49% lower after settlements or reviews.

Electrical wiring methods comes up most often in these citations: 2 items under 1910.305.

How that compares: the median penalty per cited inspection for wholesale employers since 2015 is $3,425, and STS Industrial Incorporated averages $45,733 (1 cited inspection).

1 inspection on this page followed a fatal incident.

STS Industrial Incorporated: OSHA citation items per year, 2023 to 2023
Citation items per year, by inspection date.

Texas · latest 90 days of OSHA records

393employers cited

Get notified the morning OSHA posts each new citation in Texas: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Texas

Checking a subcontractor, a client or your own company? Watch STS Industrial Incorporated and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 346909898 OPENED AUG 15, 2023Closed

Fatality or catastrophe · Complete · Safety · 20 employees at the site · Closed Apr 9, 2024

2917e East Roundbunch Road, Orange, TX 77630 · Hardware Merchant Wholesalers · OSHA's record · Phone and website on Google Maps

Incident on Aug 14, 2023 (fatal): Employee is electrocuted while troubleshooting outlet

At 11:04 a.m. on August 14, 2023, an employee was troubleshooting issues with a MSI NM1 Nut Assembly Table that would not operate. The employee went to the Warehouse Manager and informed him that the wall outlet used to provide power to the table was bad. The manager provided an extension cord for the employee to use to continue troubleshooting the nut assembly table. The employee began investigating the bad outlet, which was behind the table and a metal storage rack. While leaning over to reach the wall outlet, the employee grabbed the metal storage rack and simultaneously made contact with the body of the table. The electrical outlet the employee was investigating was not deenergized and the nut assembly table was switched on and plugged into an extension cord that did not have a ground prong. The employee was electrocuted and died.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.28(b)(11)(ii) · Fall protection in general industry
Serious$6,453$3,871Feb 9, 2024Final
Citation 1, item 2
29 CFR 1910.147(c)(1) · Lockout/tagout
Serious$11,292$6,775Feb 9, 2024Final
Citation 1, item 4
29 CFR 1910.212(a)(1) · Machine guarding
Serious$8,067$4,840Feb 9, 2024Final
Citation 1, item 5a
29 CFR 1910.303(f)(2) · Electrical equipment, general requirements
Serious$8,067$4,840Feb 9, 2024Final
Citation 1, item 5b
29 CFR 1910.305(b)(1)(ii) · Electrical wiring methods
Serious$11,292$0Feb 9, 2024Final
Citation 1, item 5c
29 CFR 1910.305(b)(2)(i) · Electrical wiring methods
Serious$11,292$0Feb 9, 2024Final
Citation 1, item 6
29 CFR 1910.303(g)(2)(i) · Electrical equipment, general requirements
Serious$11,292$8,469Feb 9, 2024Final
Citation 1, item 7
29 CFR 1910.304(g)(5) · Grounding and circuit protection
Serious$11,292$8,469Feb 9, 2024Final
Citation 1, item 10
29 CFR 1910.333(a)(1) · Working near live electrical parts
Serious$11,292$8,469Feb 9, 2024Final

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.147 · Lockout/tagout

29 CFR 1910.147(c)(1)

(c) General—(1) Energy control program. The employer shall establish a program consisting of energy control procedures, employee training and periodic inspections to ensure that before any employee performs any servicing or maintenance on a machine or equipment where the unexpected energizing, start up or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source, and rendered inoperative.

29 CFR 1910.212 · Machine guarding

29 CFR 1910.212(a)(1)

(a) Machine guarding—(1) Types of guarding. One or more methods of machine guarding shall be provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks. Examples of guarding methods are—barrier guards, two-hand tripping devices, electronic safety devices, etc.

29 CFR 1910.28 · Fall protection in general industry

29 CFR 1910.28(b)(11)(ii)

(ii) Each flight of stairs having at least 3 treads and at least 4 risers is equipped with stair rail systems and handrails as follows:

29 CFR 1910.303 · Electrical equipment, general requirements

29 CFR 1910.304 · Grounding and circuit protection

29 CFR 1910.305 · Electrical wiring methods

29 CFR 1910.333 · Working near live electrical parts

Other hardware merchant wholesalers employers in Texas

Alert subscribers get notified of each newly cited employer in Texas the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.