OSHA SearchOSHA records by employer

Tom Jenkins Electrical Service, Inc: OSHA inspections and violations

Lake Butler, Florida · Electrical Contractors and Other Wiring Installation Contractors · NAICS 238210

2inspections
4citation items
$7,206current penalties
Jun 22, 2018last inspection

OSHA has inspected Tom Jenkins Electrical Service, Inc 2 times in Florida since 2017.

The latest one began on Jun 22, 2018 to follow up on an earlier case, in Lake Butler.

Those inspections ended with 4 citation items: 3 serious and 1 other-than-serious.

Penalties were first proposed at $14,412 and now stand at $7,206, 50% lower after settlements or reviews.

Working near live electrical parts comes up most often in these citations: 2 items under 1910.333.

How that compares: the median penalty per cited inspection for construction employers since 2015 is $3,080, and Tom Jenkins Electrical Service, Inc averages $7,206 (1 cited inspection).

Tom Jenkins Electrical Service, Inc: OSHA citation items per year, 2017 to 2018
Citation items per year, by inspection date.

Florida · latest 90 days of OSHA records

320employers cited

4 of them in the same industry

Get notified the morning OSHA posts each new citation in Florida: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Florida

Checking a subcontractor, a client or your own company? Watch Tom Jenkins Electrical Service, Inc and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 343250015 OPENED JUN 22, 2018Closed

Follow-up · Partial · Safety · 3 employees at the site · Closed Jun 25, 2018

7765 County Rd 231, Lake Butler, FL 32054 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

Inspection 342818721 OPENED DEC 7, 2017Closed

Complaint · Complete · Safety · 3 employees at the site · Closed Aug 19, 2020

7765 County Rd 231, Lake Butler, FL 32054 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Incident on Sep 8, 2017: Three workers are burned in electric arc flash

At 2:00 p.m. on September 8, 2017, Employees #1, #2, and #3, employed by an electrical services company, were engaged in electrical work at a job site. They were hooking a phase tester to live wires when a 4,160-volt arc flash occurred. The three workers sustained electrical burns. The workers were treated at the hospital for their burns, and Employees #1 and #2 required hospitalization.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.333(a)(2) · Working near live electrical parts
Serious$3,880$2,402Feb 26, 2018Final
Citation 1, item 2a
29 CFR 1910.333(c)(2) · Working near live electrical parts
Serious$3,880$2,402Feb 26, 2018Final
Citation 1, item 3
29 CFR 1910.335(a)(1)(i) · Safeguards for personnel protection
Serious$3,880$2,402Feb 26, 2018Final
Citation 2, item 1
29 CFR 1904.39(a)(2) · Reporting deaths and severe injuries
Other-than-serious$2,772$0Feb 26, 2018Final

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1904.39 · Reporting deaths and severe injuries

29 CFR 1904.39(a)(2)

(2) Within twenty-four (24) hours after the in-patient hospitalization of one or more employees or an employee's amputation or an employee's loss of an eye, as a result of a work-related incident, you must report the in-patient hospitalization, amputation, or loss of an eye to OSHA.

29 CFR 1910.333 · Working near live electrical parts

29 CFR 1910.333(a)(2)

(2) Energized parts. If the exposed live parts are not deenergized (i.e., for reasons of increased or additional hazards or infeasibility), other safety-related work practices shall be used to protect employees who may be exposed to the electrical hazards involved. Such work practices shall protect employees against contact with energized circuit parts directly with any part of their body or indirectly through some other conductive object. The work practices that are used shall be suitable for the conditions under which the work is to be performed and for the voltage level of the exposed electric conductors or circuit parts. Specific work practice requirements are detailed in paragraph (c) of this section.

29 CFR 1910.333(c)(2)

(2) Work on energized equipment. Only qualified persons may work on electric circuit parts or equipment that have not been deenergized under the procedures of paragraph (b) of this section. Such persons shall be capable of working safely on energized circuits and shall be familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools.

29 CFR 1910.335 · Safeguards for personnel protection