OSHA SearchOSHA records by employer

Univar Solutions USA Inc.: OSHA inspections and violations

Murfreesboro, Tennessee · Other Chemical and Allied Products Merchant Wholesalers · NAICS 424690

1inspections
4citation items
$1,800current penalties
Oct 14, 2022last inspection

Univar Solutions USA Inc. has one OSHA inspection on record in Tennessee.

OSHA opened it on Oct 14, 2022 as a planned inspection, in Murfreesboro.

From that inspection OSHA issued 4 citation items: 4 serious.

OSHA proposed $1,800 in penalties and the amount has not been reduced.

Most often, OSHA cited 1910.106, flammable liquids (4 items).

For context, across all wholesale employers the median penalty per cited inspection since 2015 is $3,424. Univar Solutions USA Inc. averages $1,800 over 1 cited inspection in that time.

Univar Solutions USA Inc.: OSHA citation items per year, 2022 to 2022
Citation items per year, by inspection date.

Tennessee · latest 90 days of OSHA records

323employers cited

Get notified the morning OSHA posts each new citation in Tennessee: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Tennessee

Checking a subcontractor, a client or your own company? Watch Univar Solutions USA Inc. and get notified the morning OSHA posts a new citation for it.

Watch this company

Company-wide record

OSHA records show Univar Solutions USA Inc. at 2 sites in 2 states. Together they've had 2 inspections and $4,135 in current penalties.

We match records by employer name and industry, so these sites are likely the same company, not certainly. Franchises and subsidiaries can file under one name.

Included with any plan: the site-by-site record for all 2 sites, with repeat and willful violations and citations per year for the whole company. Already a subscriber? Sign in.

See plans

Inspection history

Inspection 346284854 OPENED OCT 14, 2022Closed

Planned · Complete · Health · 7 employees at the site · Closed Jan 3, 2023

912 Dashiel Street, Murfreesboro, TN 37129 · Other Chemical and Allied Products Merchant Wholesalers · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1a
29 CFR 1910.106(d)(4)(i) · Flammable liquids
Serious$1,800$1,800Nov 11, 2022Final
Citation 1, item 1b
29 CFR 1910.106(d)(4)(ii) · Flammable liquids
Serious$0$0Nov 11, 2022Final
Citation 1, item 1c
29 CFR 1910.106(d)(4)(iv) · Flammable liquids
Serious$0$0Nov 11, 2022Final
Citation 1, item 1d
29 CFR 1910.106(d)(4)(v) · Flammable liquids
Serious$0$0Nov 11, 2022Final

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.106 · Flammable liquids

29 CFR 1910.106(d)(4)(i)

(4) Design and construction of inside storage rooms—(i) Construction. Inside storage rooms shall be constructed to meet the required fire-resistive rating for their use. Such construction shall comply with the test specifications set forth in Standard Methods of Fire Tests of Building Construction and Materials, NFPA 251-1969. Where an automatic sprinkler system is provided, the system shall be designed and installed in an acceptable manner. Openings to other rooms or buildings shall be provided with noncombustible liquid-tight raised sills or ramps at least 4 inches in height, or the floor in the storage area shall be at least 4 inches below the surrounding floor. Openings shall be provided with approved self-closing fire doors. The room shall be liquid-tight where the walls join the floor. A permissible alternate to the sill or ramp is an open-grated trench inside of the room which dra

29 CFR 1910.106(d)(4)(ii)

(ii) Rating and capacity. Storage in inside storage rooms shall comply with Table H-13.

29 CFR 1910.106(d)(4)(iv)

(iv) Ventilation. Every inside storage room shall be provided with either a gravity or a mechanical exhaust ventilation system. Such system shall be designed to provide for a complete change of air within the room at least six times per hour. If a mechanical exhaust system is used, it shall be controlled by a switch located outside of the door. The ventilating equipment and any lighting fixtures shall be operated by the same switch. A pilot light shall be installed adjacent to the switch if Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), are dispensed within the room. Where gravity ventilation is provided, the fresh air intake, as well as the exhaust outlet from the room, shall be on the exterior of the building in which the room is located.

Other other chemical and allied products merchant wholesalers employers in Tennessee

Alert subscribers get notified of each newly cited employer in Tennessee the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.