OSHA SearchOSHA records by employer

Weisinger Electric Inc: OSHA inspections and violations

Lufkin, Texas · Electrical Contractors and Other Wiring Installation Contractors · NAICS 238210

1inspections
3citation items
$8,400current penalties
Aug 6, 2015last inspection

OSHA inspectors have visited Weisinger Electric Inc in Texas one time.

It opened on Aug 6, 2015 on a referral, in Lufkin.

In all, OSHA issued 3 citation items: 3 serious.

The penalties, $8,400 in total, stand where OSHA first set them.

The rule cited most here is 1910.269 (electric power generation, transmission, and distribution), 3 times.

Among construction employers, the typical cited inspection since 2015 ends with a $3,080 penalty. Weisinger Electric Inc averages $8,400 across 1 cited inspection.

It reported 1 severe injury to OSHA since 2015.

Weisinger Electric Inc: OSHA citation items per year, 2015 to 2015
Citation items per year, by inspection date.

Texas · latest 90 days of OSHA records

398employers cited

7 of them in the same industry

Get notified the morning OSHA posts each new citation in Texas: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Texas

Checking a subcontractor, a client or your own company? Watch Weisinger Electric Inc and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 340831825 OPENED AUG 6, 2015Closed

Referral · Partial · Safety · 18 employees at the site · Closed Dec 8, 2015

300 Winston Street, Lufkin, TX 75901 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.269(d)(2)(iv)(b) · Electric power generation, transmission, and distribution
Serious$2,800$2,800Oct 27, 2015Final
Citation 1, item 2
29 CFR 1910.269(d)(2)(iv)(d) · Electric power generation, transmission, and distribution
Serious$2,800$2,800Oct 27, 2015Final
Citation 1, item 3
29 CFR 1910.269(m)(3)(ii) · Electric power generation, transmission, and distribution
Serious$2,800$2,800Oct 27, 2015Final

Severe injury reports

Employers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 1 report on file.

Jul 31, 2015, Lufkin: Hospitalization · electrical burns, unspecified · hand(s), unspecified

An employee was changing out a pole-mounted transformer. A wire that the employee touched was still energized by the overhead powerlines. The employee was shocked by 7200K volts, suffering electrical burns to both hands and memory loss and requiring hospitalization.

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.269 · Electric power generation, transmission, and distribution

29 CFR 1910.269(d)(2)(iv)(b)

(B) Specific procedural steps for shutting down, isolating, blocking and securing machines or equipment to control hazardous energy;

29 CFR 1910.269(d)(2)(iv)(d)

(D) Specific requirements for testing a machine or equipment to determine and verify the effectiveness of lockout devices, tagout devices, and other energy control measures.

29 CFR 1910.269(m)(3)(ii)

(ii) The employer shall ensure that all switches, disconnectors, jumpers, taps, and other means through which known sources of electric energy may be supplied to the particular lines and equipment to be deenergized are open. The employer shall render such means inoperable, unless its design does not so permit, and then ensure that such means are tagged to indicate that employees are at work.