OSHA SearchOSHA records by employer

Zatt's Electric, LLC: OSHA inspections and violations

Jal, New Mexico · Electrical Contractors and Other Wiring Installation Contractors · NAICS 238210

1inspections
2citation items
$5,470current penalties
Oct 26, 2020last inspection

Zatt's Electric, LLC has one OSHA inspection on record in New Mexico.

OSHA opened it on Oct 26, 2020 on a referral, in Jal, and the case has not closed yet.

From that inspection OSHA issued 2 citation items: 2 serious.

OSHA proposed $5,470 in penalties and the amount has not been reduced.

Most often, OSHA cited 1910.269, electric power generation, transmission, and distribution (2 items).

For context, across all construction employers the median penalty per cited inspection since 2015 is $3,080. Zatt's Electric, LLC averages $5,470 over 1 cited inspection in that time.

Zatt's Electric, LLC: OSHA citation items per year, 2020 to 2020
Citation items per year, by inspection date.

New Mexico · latest 90 days of OSHA records

31employers cited

Get notified the morning OSHA posts each new citation in New Mexico: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in New Mexico

Checking a subcontractor, a client or your own company? Watch Zatt's Electric, LLC and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 344997598 OPENED OCT 26, 2020Open

Referral · Partial · Safety · 10 employees at the site · Open

S. Justice G30 Wellsite 32.081824-103.114478, Jal, NM 88252 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Incident on Aug 19, 2020: Employee suffers electric shock and burns while working on o

At 12:00 p.m. on August 19, 2020, Employee #1 was working for an electrical contractor. Employee #1 was working out of bucket truck on a powerline while replacing a transformer. Employee #1 was using an electric line pole while installing a center phase hot-line clamp as part of the process to replace a high voltage step down transformer. Employee #1 reached with his electric line pole for a line that was disconnected, when he accidentally contacted a ground wire. Due to a voltage leak into the ground wire Employee #1 suffered electric shock and burns to his left elbow and right hand. Employee #1 went unconscious and was airlifted to the hospital. Employee #1 was hospitalized to receive skin grafts and burn treatment.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.269(a)(4) · Electric power generation, transmission, and distribution
Serious$2,735$2,735Apr 26, 2021Open
Citation 1, item 2
29 CFR 1910.269(n)(2) · Electric power generation, transmission, and distribution
Serious$2,735$2,735Apr 26, 2021Open

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.269 · Electric power generation, transmission, and distribution

29 CFR 1910.269(a)(4)

(4) Existing characteristics and conditions. Existing characteristics and conditions of electric lines and equipment that are related to the safety of the work to be performed shall be determined before work on or near the lines or equipment is started. Such characteristics and conditions include, but are not limited to:

29 CFR 1910.269(n)(2)

(2) General. For any employee to work transmission and distribution lines or equipment as deenergized, the employer shall ensure that the lines or equipment are deenergized under the provisions of paragraph (m) of this section and shall ensure proper grounding of the lines or equipment as specified in paragraphs (n)(3) through (n)(8) of this section. However, if the employer can demonstrate that installation of a ground is impracticable or that the conditions resulting from the installation of a ground would present greater hazards to employees than working without grounds, the lines and equipment may be treated as deenergized provided that the employer establishes that all of the following conditions apply:

Other electrical contractors and other wiring installation contractors employers in New Mexico

Alert subscribers get notified of each newly cited employer in New Mexico the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.