OSHA has cited 29 CFR 1910.103 7 times since 2015, against 5 employers. Penalties on these items add up to $6,100 at their current amounts.
Citations per year
The parts of the rule cited most
1910.103(b)(1)(v) · 2 citations
(v) Marking. The hydrogen storage location shall be permanently placarded as follows: “HYDROGEN—FLAMMABLE GAS—NO SMOKING—NO OPEN FLAMES,” or equivalent.
1910.103(b)(1)(ivc) · 1 citations
(iv) Equipment assembly. (a) Valves, gauges, regulators, and other accessories shall be suitable for hydrogen service.
1910.103(b)(1)(ive) · 1 citations
(iv) Equipment assembly. (a) Valves, gauges, regulators, and other accessories shall be suitable for hydrogen service.
1910.103(b)(2)(iia) · 1 citations
(ii) Specific requirements. (a) The location of a system, as determined by the maximum total contained volume of hydrogen, shall be in the order of preference as indicated by Roman numerals in Table H-1.
1910.103(b)(5) · 1 citations
(5) Maintenance. The equipment and functioning of each charged gaseous hydrogen system shall be maintained in a safe operating condition in accordance with the requirements of this section. The area within 15 feet of any hydrogen container shall be kept free of dry vegetation and combustible material.
1910.103(c)(5) · 1 citations
(5) Maintenance. The equipment and functioning of each charged liquefied hydrogen system shall be maintained in a safe operating condition in accordance with the requirements of this section. Weeds or similar combustibles shall not be permitted within 25 feet of any liquefied hydrogen equipment.
Industries cited most
- Manufacturing 2
- Wholesale Trade 2
- Educational Services 2
- Utilities 1