29 CFR 1910.126: Additional requirements for special dipping and coating operations

Subpart H—Hazardous Materials

7citations since 2015
6employers cited
100%serious, willful or repeat
$1,630median penalty per item

OSHA has cited 29 CFR 1910.126 7 times since 2015, against 6 employers. Penalties on these items add up to $18,245 at their current amounts.

Citations per year

The parts of the rule cited most

1910.126(e) · 3 citations

(e) What additional requirements apply to cyanide tanks? You must ensure that cyanide tanks have a dike or other safeguard to prevent cyanide from mixing with an acid if a dip tank fails.

1910.126(a)(2) · 2 citations

(2) You must equip each tank with an alarm that will sound if the temperature of the liquid comes within 50 °F (10 °C) of its flashpoint (the alarm set point).

1910.126(a)(3) · 1 citations

(3) When practicable, you must also provide each tank with a limit switch to shut down the conveyor supplying work to the tank.

1910.126(d)(1) · 1 citations

(d) What additional requirements apply to vapor degreasing tanks? (1) You must ensure that the condenser or vapor-level thermostat keeps the vapor level at least 36 inches (91 cm) or one-half the tank width, whichever is less, below the top of the vapor degreasing tank.