OSHA SearchOSHA records by employer

Day and Zimmermann Incorporated: OSHA inspections and violations

Hartsville, South Carolina · Power and Communication Line and Related Structures Construction · NAICS 237130

1inspections
1citation items
$5,000current penalties
Jun 2, 2015last inspection

OSHA has inspected Day and Zimmermann Incorporated once in South Carolina.

The inspection began on Jun 2, 2015 after an accident, in Hartsville.

That inspection ended with 1 citation item: 1 serious.

Penalties were first proposed at $5,000 and still stand at $5,000.

How that compares: the median penalty per cited inspection for construction employers since 2015 is $3,080, and Day and Zimmermann Incorporated averages $5,000 (1 cited inspection).

Day and Zimmermann Incorporated: OSHA citation items per year, 2015 to 2015
Citation items per year, by inspection date.

South Carolina · latest 90 days of OSHA records

41employers cited

Get notified the morning OSHA posts each new citation in South Carolina: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in South Carolina

Checking a subcontractor, a client or your own company? Watch Day and Zimmermann Incorporated and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 317892891 OPENED JUN 2, 2015Closed

Accident · Partial · Safety · 410 employees at the site · Closed Nov 24, 2015

3581 West Entrance Road, Hartsville, SC 29550 · Power and Communication Line and Related Structures Construction · OSHA's record · Phone and website on Google Maps

Incident on Jun 1, 2015: Burn - electrical fault in transformer

Employees of an electrical contractor were at a power generation facility, condu cting voltage testing on a 4160/480-volt station service transformer, which was an upgrade replacing an old transformer. The transformer, which was 2 meters tal l and 3.7 meters long, with four 0.9-meter-wide sections, did not have any expos ed live parts. Each section had seven vent openings, which were about 38 millime ters wide and 610 millimeters long, at the top and bottom of each panel. The Pla nt Operator closed the circuit breaker for the transformer in the breaker room, energizing the transformer. The transformer had five positions on the tap change r, and the employees were moving from lower voltage to higher voltage, taking vo ltage readings. Three employees did a brief walk around to look at what was need ed to do the work. The tap changer was in position three, and the bus 3 meter re ad 4445 volts instead of the expected reading of 4160 volts. The work order stat ed that the transformer had to be energized to change the taps. The employees ha d to release the locking pin on the tap to turn the handle. At each position of the tap changer, Employee #2 released the locking pin, and Employee #1 turned th e handle. When Employee #1 turned the handle slowly, they saw a small electric a rc. They stopped and took a voltage reading. The employees were instructed move quicker and move to position one. As the employees moved the tap from position f our to five, they noticed another electric arc. After the arc, there was smoke a nd an electrical fault. Employee #2 pushed Employee #3 out of the way, and Emplo yee #1 yelled that his clothing had ignited. Employees were wearing hard hats, s afety glasses, leather gloves, and regular street clothes. Employee #1 received second-degree burns to his left arm, shoulder, right collar bone, and both butt cheeks. He was hospitalized for his injuries. Employees #2 and #3 received first -degree burns.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.269(l)(8)(v) · Electric power generation, transmission, and distribution
Serious$5,000$5,000Nov 25, 2015Contested

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.269 · Electric power generation, transmission, and distribution

29 CFR 1910.269(l)(8)(v)

(v) The employer shall ensure that each employee exposed to hazards from electric arcs wears protective clothing and other protective equipment with an arc rating greater than or equal to the heat energy estimated under paragraph (l)(8)(ii) of this section whenever that estimate exceeds 2.0 cal/cm 2. This protective equipment shall cover the employee's entire body, except as follows:

Other power and communication line and related structures construction employers in South Carolina

Alert subscribers get notified of each newly cited employer in South Carolina the morning it is posted. See the alert plans.