Inspection 317892891 OPENED JUN 2, 2015Closed
3581 West Entrance Road, Hartsville, SC 29550 · Power and Communication Line and Related Structures Construction · OSHA's record · Phone and website on Google Maps
Incident on Jun 1, 2015: Burn - electrical fault in transformer
Employees of an electrical contractor were at a power generation facility, condu cting voltage testing on a 4160/480-volt station service transformer, which was an upgrade replacing an old transformer. The transformer, which was 2 meters tal l and 3.7 meters long, with four 0.9-meter-wide sections, did not have any expos ed live parts. Each section had seven vent openings, which were about 38 millime ters wide and 610 millimeters long, at the top and bottom of each panel. The Pla nt Operator closed the circuit breaker for the transformer in the breaker room, energizing the transformer. The transformer had five positions on the tap change r, and the employees were moving from lower voltage to higher voltage, taking vo ltage readings. Three employees did a brief walk around to look at what was need ed to do the work. The tap changer was in position three, and the bus 3 meter re ad 4445 volts instead of the expected reading of 4160 volts. The work order stat ed that the transformer had to be energized to change the taps. The employees ha d to release the locking pin on the tap to turn the handle. At each position of the tap changer, Employee #2 released the locking pin, and Employee #1 turned th e handle. When Employee #1 turned the handle slowly, they saw a small electric a rc. They stopped and took a voltage reading. The employees were instructed move quicker and move to position one. As the employees moved the tap from position f our to five, they noticed another electric arc. After the arc, there was smoke a nd an electrical fault. Employee #2 pushed Employee #3 out of the way, and Emplo yee #1 yelled that his clothing had ignited. Employees were wearing hard hats, s afety glasses, leather gloves, and regular street clothes. Employee #1 received second-degree burns to his left arm, shoulder, right collar bone, and both butt cheeks. He was hospitalized for his injuries. Employees #2 and #3 received first -degree burns.
| Citation and rule | Type | Proposed | Current | Issued | Status |
|---|---|---|---|---|---|
| Citation 1, item 1 29 CFR 1910.269(l)(8)(v) · Electric power generation, transmission, and distribution |
Serious | $5,000 | $5,000 | Nov 25, 2015 | Contested |