OSHA SearchOSHA records by employer

Delta Utility Services, Inc.: OSHA inspections and violations

Gambrills, Maryland · Electric Bulk Power Transmission and Control · NAICS 221121

1inspections
1citation items
$2,050current penalties
Oct 13, 2017last inspection

OSHA inspectors have visited Delta Utility Services, Inc. in Maryland one time.

It opened on Oct 13, 2017 after an accident, in Gambrills.

In all, OSHA issued 1 citation item: 1 serious.

The penalties, $2,050 in total, stand where OSHA first set them.

Among utility employers, the typical cited inspection since 2015 ends with a $0 penalty. Delta Utility Services, Inc. averages $2,050 across 1 cited inspection.

Delta Utility Services, Inc.: OSHA citation items per year, 2017 to 2017
Citation items per year, by inspection date.

Maryland · latest 90 days of OSHA records

194employers cited

Get notified the morning OSHA posts each new citation in Maryland: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Maryland

Checking a subcontractor, a client or your own company? Watch Delta Utility Services, Inc. and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 342706405 OPENED OCT 13, 2017Closed

Accident · Partial · Safety · 3 employees at the site · Closed Mar 19, 2018

1003 Autumn Gold Drive, Gambrills, MD 21054 · Electric Bulk Power Transmission and Control · OSHA's record · Phone and website on Google Maps

Incident on Oct 13, 2017: Employee suffers second degree burns when exposed to an arc

At 12:15 p.m. on October 13, 2017, Employee #1, a crew leader, and his crew were removing the old transformer and replacing it with a new one. The power was supplied to the transformer by an underground cable, originating at the overhead A-phase power line. The phase-to-phase voltage was 13.2kV and the phase-to-ground voltage was 7620v. The underground cable was rated to handle as great as 600 amperes. The crew needed to isolate and de-energize the transformer prior to removing it. There were two underground cables coming off of the A-phase overhead power line and neither one was labeled or identified, so the employees needed to test the amperage of the cables to determine which cable was associated with the transformer to be replaced and which cable fed power to an unrelated loop. Employee #1 used an insulated bucket truck to raise himself approximately 35 feet, to access the underground cable at the pole where it met the overhead power line. The employee was using an Amprobe ACDC-100 TMRS amperage/voltage tester, rated for up to 800 amperes, to attempt to determine the correct cable. He received an irregular or faulty reading that was inconclusive and thought that the meter was malfunctioning. The employee lowered himself to the ground and obtained the wire leads for the testing equipment, which are intended to be used for voltage testing at a maximum rated voltage of 600 volts. He ascended back to the work area. Employee #1 touched the positive probe lead of his tool to the primary conductor and touched the negative lead to the concentric neutral of the same cable, causing a phase-to-ground contact and resulting in an arc flash. The blown fuse created a very loud popping sound. The employee, now covered in soot, lowered himself to the ground and began to remove his personal protective equipment which included a hard hat, safety glasses, rubber sleeves, rubber gloves, and leather gloves, as well as FR clothing. He was transported to a nearby hospital and treated for second degree burns to his forehead, cheeks, chin, and left ear. The employee was release from the hospital the following day. hospital the following day.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 05-104(A)
Serious$2,050$2,050Feb 8, 2018Final

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

Other electric bulk power transmission and control employers in Maryland

Alert subscribers get notified of each newly cited employer in Maryland the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.